Vega VEGABAR 63 Foundation Fieldbus User Manual Page 65

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 64
- Highest calibrated value. For
calibration of the high limit point you give the high measurement
value (pressure) to the sensor and transfer this point as HIGH to t he transmitter. Unit derives from
'Sensor_range.unit'
l CAL_POINT_LO
- Low
est calibrated value. For
calibration of the low limit point you give the low measurement value
(pressure) to the sensor and transfer this point as LOW to the transmitter. Unit derives from
'Sensor_range.unit'
l CAL_MIN_SPAN
- Minimum calibration span value allowed. Necess
ary to ensure that when calibration is done, the
two calibrated points (high and low) are not too close together. Unit derives from 'Sensor_range.
unit'
l SCALE_IN
- Min/max-adjustmen
t: Upper and lower calibrated points of the sensor. Unit derives from
'Sensor_range.unit'
l trimmed_value
- Sensor value after the trim processing. Unit
derives from 'Sensor_range.unit'
l sensor_sn
- Sensor serial number
l temperature
- Proc
ess temperature. Sel
ected as input to AIFB by setting 'Channel' = 4. Unit derives from
'Temperature.unit'
l temperature_unit
- Unit code of 'Temperature', 'Max/Min_peak_temperature_value'
- °C, °F, K, °R
l max_peak_temperature_value
- Holds the maximum process temperature. Write access resets to current value. Unit derives
from 'Temperature.unit'
- Write access resets to current value
l min_pea
k_temperature_value
- Holds the minimum process temperature. Write access resets to current value. Unit derives
from 'Temperature.unit'
- Write
access resets to current value
VEGABAR 63 Foun
dation Fieldbus 65
10 Anh
ang
32464-DE-090109
Page view 64
1 2 ... 60 61 62 63 64 65 66 67 68 69 70 ... 79 80

Comments to this Manuals

No comments