l sensor_ran
ge
- "Sensor_range.unit' refers to 'Sensor_value', 'Max/Min_peak_sensor_value', 'Cal_point_hi/lo'
- includes sensor unit: bar, PSI …; only
unit part of DS-68 is writable
l simulate_primary_value
l simulate_secondary_value_1
l simulate_secondary_value_2
l device status
- "0: ""OK"" 13: ""non-sp
ecific error"" 17: ""Cal span too small"" 34: ""EEPROM memory fault"" 36:
""ROM memory fault"" 37: ""RAM memory fault"" 40: ""non-specific hardware fault"" 41: ""Sensor
element not found"" 42: ""No leaking pulse"" 43: ""No trigger signal"" 44: ""EMI error"" 113:
""Communication hardware fault"""
l linearization type
- Possible types of linearization are: linear, user defined, cylindrical lying container, spherical
container
- "0: ""Line
ar"" 1: ""User
def"" 20: ""Cylindrical lying container"" 21: ""Spherical container"""
l curve_points_1_10
- X and Y values
for
the user defined linearization curve
l curve_points_11_20
- X and Y values
for the user defined linearization curve
l curve_points_21_30
- X and Y values for
the user defined linearization curve
l curve_points_31_33
- X and Y values for the user defined linearization curve
l curve status
- Result of table plausibility check
- "0: ""Uninitialized"" 1: ""Good"" 2: ""Not
monotonous increasing"" 3: ""Not monotonous
decreasing"" 4: ""Not enough values transmitted"" 5: ""Too many values transmitted"" 6:
""Gradient of edge too high"" 7: ""Values not excepted"" 8: ""Table currently loaded"" 9: ""Sorting
and checking table"""
l SUB_DEVICE_NUMBER
l SENSOR_ELEMENT_TYPE
- 0: "non-sp
ecific"
l displa
y_source_selector
- Selects the type of value that is displayed on the indication-/adjustement-module
- "0: ""Physical
value"" 1: ""Percent value"" 2: ""Lin percent value"" 6: ""Out(AI1)"" 7: ""Level"" 8:
""Out(AI2)"" 9: ""Out(AI3)"""
l max_peak_sensor_value
- Holds the maximum sensor value. Write access resets to current value. Unit derives from
'Sensor_range.unit'
- Write
access resets to current value
l min_pea
k_sensor_value
- Holds the minimum sensor value. Write access resets to current value. Unit derives from
'Sensor_range.unit'
- Write access resets to current value
l CAL_POINT_HI
64 VE
GABAR 63 • Foundation Fieldbus
10 Anhang
32464-DE-090109
Comments to this Manuals