Vega VEGABAR 63 Foundation Fieldbus User Manual Page 63

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 62
Secondary_value_2
scale_in_0 scale_in_100 Sensor_value
0 %
100 %
bar
0,500-0,500
0
%
100
%
scale_in_100scale_in_0
Abb
. 30: A/jointfilesconvert/1358493/bgleich VEGABAR 63
Parameterliste
Die folgende Liste enthält die wichtigsten Parameter und ihre Bedeutung:
l primary_value
- Process Value
after min/max-adjustment and linearization. Selected as input to AIFB by setting
'Channel' = 1. Unit derives from 'Primary_value_unit'
l primary_value_unit
- Unit code of 'Primary_value'
- %
l secon
dar
y_value_1
- Process pressure. Selected as input to AIFB by setting 'Channel' = 2. Unit derives from
'Secondary_value_1_unit'
l secondary_value_1_unit
- Unit code of 'Secondary_value_1'
- bar, PSI,
…, m, ft,
…; in case of length type engineering unit and access to parameters the
corresponding values will be converted by density factor
l secondary_value_2
- Value after min/max-adjust
ment. Selected as input to AIFB by setting 'Channel' = 3. Unit derives
from 'Secondary_value_2_unit'
l secondary_value_2_unit
- Selected unit code for "secon
dary_value_2"
l sensor_value
- Raw
sensor value, i.e. the
uncalibrated measurement value from the sensor. Unit derives from
'Sensor_range.unit'
VEGABAR 63 Foun
dation Fieldbus 63
10 Anh
ang
32464-DE-090109
Page view 62