Operating InstructionsVEGAPULS 654 … 20 mA/HART four-wireRadar
With the serial number, youcan access the delivery data of theinstrument viawww.vega.com, "VEGA Tools" and "serial numbersearch".
3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport i
4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i
1 32100%0%4Fig. 3: Measuring range (operating range) andmax. measuring distance1 full2 empty (max. measuring distance)3 Measuring rangeInformation:If
1Fig. 4: Position of thepolarisation plane with VEGAPULS 651 Marking holeMake sure that all parts of the instrument in contact with the measuredproduc
When mounting VEGAPULS 65, keepa distance of at least 500 mm(19.69 in) to the vessel wall. If the sensor is installed in the center ofdished or round
Fig. 6: Vessel with conicalbottomDo not mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the infl
Fig. 8: Recommended socket mountingIncase of very big socket diameters, the active antenna part can beslightly recessed in the socket. The following r
Fig. 10: Cover smooth profileswith deflectorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motio
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .
If screened cable is necessary, connect the cable screen on both endsto ground potential. In the sensor, the screen must be connecteddirectly to the i
12 Screw the housing cover onTheelectrical connection is finished.Fig. 12: Connection steps 5 and 65.3 Wiringplan, double chamber housingThe following
132Display1 2 5 6 7 8I²CFig. 14: Electronics compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c
Information:Keep inmind that the indicating and adjustment module must only beused in the electronics compartment.4 ... 20 mAPE/ L/ NL1 NGND1 21 2344.
6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 17: Insert indicating andadjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous mea
6.3 Adjustment system1.1231Fig. 18: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You w
▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basic adjustment" with [->] and confirm with[OK]. Now the menu item
LiquidAccording to the conductivity and the dielectric value of liquids, thereflection properties can differ considerably. Therefore additionaloptions s
8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .398.2 Remove interferences. . . . . . .
High sockets or vessel installations, such ase. g. struts or agitators aswell as buildup and weld joints on the vessel walls cause interferingreflectio
The following data are read out or written with this function:l Measuredvalue presentationl Adjustmentl Mediuml Inner diameter of the standpipe (with
Menu item Reset valueCurrentoutput - failure < 3.6 mAUnit of measurement m(d)The values of the following menu items are not reset to the resetvalue
6.5 Menu schematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor sel ection
3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor statusOK3.3Curve selectionEcho curve▼3.4Echo curvePresenta
6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa
7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 19: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl
Necessary components:l VEGAPULS 65l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system152 43OPENTWISTUSBLOCKF
Note:Keep in mindthat for setup of VEGAPULS 65, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are provided in the
8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
? Current signal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return instrument for repairIn Ex applic
Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q
You can download a return form (23 KB) from our Internet homepagewww.vega.com under: "Downloads - Forms and certificates - Repairform".By doi
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 TechnicaldataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread PVDF, 316L- Seal - thr
Input variableMeasuredvalue distance between process fitting and product sur-faceMin. distance from antenna end 50 mm (1.969 in)Measuring range up to 3
1,0 m (3.28 ft)30 m (98.43 ft)20 mm (0.788 in)10 mm (0.394 in)- 10 mm (- 0.394 in)- 20 mm (- 0.788 in)0Fig. 22: Deviation VEGAPULS 65Influence ofthe
Vessel pressure- Screwed part PVDF -100 … 300 kPa/-1 … 3 bar (-14.5 … 43.5 psig)- Screwed part and flange 316L -100 … 1600 kPa/-1 … 16 bar (-14.5 … 232
Electrical protective measuresProtection IP 66/IP 67Overvoltage category IIIProtection class IFunctional safety (SIL)The functional safety is already
10.2 DimensionsHousingø84mm~ 27/")120mm (4 23/32")* 129mm (5 5/64")5/16")M20x1,5/½ NPTM12xFig. 23: Double chamber housingof Alumin
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
VEGAPULS 6541 mm(1.61")ø 40 mm(1.58")ø 33 mm(1.30")ø 33 mm(1.30")82 mm (3.23")415 mm (16.34")120 mm (4.72")270 mm (
dø 33 mm(1.30")395 mm (15.55")120 mm (4.72")270 mm (10.63")545 mm (21.46")94 mm (3.70")2 mm (0.08")bkD4xø0.75"
10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
VEGAPULS 65 • 4 … 20 mA/HART four-wire 5310 Supplement28442-EN-090305
54 VEGAPULS 65 • 4 … 20 mA/HART four-wire10 Supplement28442-EN-090305
VEGAPULS 65 • 4 … 20 mA/HART four-wire 5510 Supplement28442-EN-090305
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
During t he entire duration of use, the useris obliged to determine thecompliance of the required occupational safety measures with thecurrent valid r
l The instrument must not cause any interfering emissionsl Thedevice must be insensitive to interfering immissions, includingthose that may cause unde
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAPULS 65 radar sensorl Documentation- this operating instructions manual-
123Fig. 1: VEGAPULS 65 - threaded version with Aludouble chamber housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3