Vega VEGAPULS 65 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four- User Manual

Browse online or download User Manual for Equipment Vega VEGAPULS 65 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four-. VEGA VEGAPULS 65 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four-wire User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instruction

Operating InstructionsVEGAPULS 654 … 20 mA/HART four-wireRadar

Page 2 - Contents

With the serial number, youcan access the delivery data of theinstrument viawww.vega.com, "VEGA Tools" and "serial numbersearch".

Page 3

3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport i

Page 4 - 1 About this document

4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i

Page 5 - 2 For your safety

1 32100%0%4Fig. 3: Measuring range (operating range) andmax. measuring distance1 full2 empty (max. measuring distance)3 Measuring rangeInformation:If

Page 6 - 2.7 Fulfillment o

1Fig. 4: Position of thepolarisation plane with VEGAPULS 651 Marking holeMake sure that all parts of the instrument in contact with the measuredproduc

Page 7

When mounting VEGAPULS 65, keepa distance of at least 500 mm(19.69 in) to the vessel wall. If the sensor is installed in the center ofdished or round

Page 8 - 3 Product description

Fig. 6: Vessel with conicalbottomDo not mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the infl

Page 9

Fig. 8: Recommended socket mountingIncase of very big socket diameters, the active antenna part can beslightly recessed in the socket. The following r

Page 10 - 3.3 Operation

Fig. 10: Cover smooth profileswith deflectorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motio

Page 11 - 3.4 Packaging, trans

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 12 - 4 Mounting

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Page 13 - 28442-EN-090305

If screened cable is necessary, connect the cable screen on both endsto ground potential. In the sensor, the screen must be connecteddirectly to the i

Page 14 - 4.2 Mounting instructions

12 Screw the housing cover onTheelectrical connection is finished.Fig. 12: Connection steps 5 and 65.3 Wiringplan, double chamber housingThe following

Page 15 - > 500 mm

132Display1 2 5 6 7 8I²CFig. 14: Electronics compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 16

Information:Keep inmind that the indicating and adjustment module must only beused in the electronics compartment.4 ... 20 mAPE/ L/ NL1 NGND1 21 2344.

Page 17

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 18

Fig. 17: Insert indicating andadjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous mea

Page 19 - 5 Connecting to power supply

6.3 Adjustment system1.1231Fig. 18: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 20 - 5.2 Connection procedure

6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You w

Page 21 - 5.3 Wiring

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basic adjustment" with [->] and confirm with[OK]. Now the menu item

Page 22 - 4... 20mA

LiquidAccording to the conductivity and the dielectric value of liquids, thereflection properties can differ considerably. Therefore additionaloptions s

Page 23 - 5.4 Switch on phase

8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .398.2 Remove interferences. . . . . . .

Page 24 - 6.1 Short description

High sockets or vessel installations, such ase. g. struts or agitators aswell as buildup and weld joints on the vessel walls cause interferingreflectio

Page 25

The following data are read out or written with this function:l Measuredvalue presentationl Adjustmentl Mediuml Inner diameter of the standpipe (with

Page 26 - - Select editing position

Menu item Reset valueCurrentoutput - failure < 3.6 mAUnit of measurement m(d)The values of the following menu items are not reset to the resetvalue

Page 27 - Address 0

6.5 Menu schematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor sel ection

Page 28

3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor statusOK3.3Curve selectionEcho curve▼3.4Echo curvePresenta

Page 29 - Linearisation curve

6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa

Page 30 - Extended setting

7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 19: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl

Page 31 - Copy sensor data?

Necessary components:l VEGAPULS 65l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system152 43OPENTWISTUSBLOCKF

Page 32

Note:Keep in mindthat for setup of VEGAPULS 65, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are provided in the

Page 33 - 6.5 Menu schem

8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte

Page 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35 - 6.6 Saving the pa

? Current signal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return instrument for repairIn Ex applic

Page 36 - 7 Setup with PACTware and

Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q

Page 37

You can download a return form (23 KB) from our Internet homepagewww.vega.com under: "Downloads - Forms and certificates - Repairform".By doi

Page 38

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 39 - ? 4 … 20 mA signal missing

10 Supplement10.1 TechnicaldataGeneral data316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread PVDF, 316L- Seal - thr

Page 40 - ? E041, E042, E043

Input variableMeasuredvalue distance between process fitting and product sur-faceMin. distance from antenna end 50 mm (1.969 in)Measuring range up to 3

Page 41 - 8.5 Instrument repair

1,0 m (3.28 ft)30 m (98.43 ft)20 mm (0.788 in)10 mm (0.394 in)- 10 mm (- 0.394 in)- 20 mm (- 0.788 in)0Fig. 22: Deviation VEGAPULS 65Influence ofthe

Page 42

Vessel pressure- Screwed part PVDF -100 … 300 kPa/-1 … 3 bar (-14.5 … 43.5 psig)- Screwed part and flange 316L -100 … 1600 kPa/-1 … 16 bar (-14.5 … 232

Page 43 - 9 Dismounting

Electrical protective measuresProtection IP 66/IP 67Overvoltage category IIIProtection class IFunctional safety (SIL)The functional safety is already

Page 44 - 10 Supplement

10.2 DimensionsHousingø84mm~ 27/")120mm (4 23/32")* 129mm (5 5/64")5/16")M20x1,5/½ NPTM12xFig. 23: Double chamber housingof Alumin

Page 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46

VEGAPULS 6541 mm(1.61")ø 40 mm(1.58")ø 33 mm(1.30")ø 33 mm(1.30")82 mm (3.23")415 mm (16.34")120 mm (4.72")270 mm (

Page 47

dø 33 mm(1.30")395 mm (15.55")120 mm (4.72")270 mm (10.63")545 mm (21.46")94 mm (3.70")2 mm (0.08")bkD4xø0.75"

Page 48

10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 49 - 10.2 Dimensions

VEGAPULS 65 • 4 … 20 mA/HART four-wire 5310 Supplement28442-EN-090305

Page 50

54 VEGAPULS 65 • 4 … 20 mA/HART four-wire10 Supplement28442-EN-090305

Page 51

VEGAPULS 65 • 4 … 20 mA/HART four-wire 5510 Supplement28442-EN-090305

Page 52 - 10.4 Trademark

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 53

During t he entire duration of use, the useris obliged to determine thecompliance of the required occupational safety measures with thecurrent valid r

Page 54

l The instrument must not cause any interfering emissionsl Thedevice must be insensitive to interfering immissions, includingthose that may cause unde

Page 55

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAPULS 65 radar sensorl Documentation- this operating instructions manual-

Page 56 - ISO 9001

123Fig. 1: VEGAPULS 65 - threaded version with Aludouble chamber housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3