Vega VVO VEGA Visual Operating User Manual

Browse online or download User Manual for Equipment Vega VVO VEGA Visual Operating. VEGA VVO VEGA Visual Operating User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 64
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
in
out
Level and Pressure
Manual
VEGA Visual Operating (VVO)
Page view 0
1 2 3 4 5 6 ... 63 64

Summary of Contents

Page 1 - VEGA Visual Operating (VVO)

inoutLevel and PressureManualVEGA Visual Operating (VVO)

Page 2 - Contents

10 VEGA Visual OperatingStart VVOTo remove failure 2 (interface cable orVEGACONNECT 2 connected to thewrong standard interface) you can plugthe interf

Page 3 - VEGA Visual Operating 3

VEGA Visual Operating 11Start VVOThis message appears when during VVO-start or during connection an instrument isconnected for the first time to the P

Page 4 - 1 Product description

12 VEGA Visual OperatingNow click to , then to.Set-up of a process pressure transmitter VEGABAR 205 Set-up of a process pressure transmitter VEGABAR

Page 5 - 2 Installation

VEGA Visual Operating 13Set-up of a process pressure transmitter VEGABAR 20You can give another name to the measure-ment loop (max. 16 figures) and a

Page 6 - 3 Instrument connection

14 VEGA Visual OperatingNow click to , then to.Set-up of an ultrasonic sensor VEGASON 52K6 Set-up of an ultrasonic sensor VEGASON 52K6.1 Configure se

Page 7 - VEGA Visual Operating 7

VEGA Visual Operating 15Set-up of an ultrasonic sensor VEGASON 52KClick to , then to .From this window ("Instrument dataparameter adjustment“) y

Page 8 - 4 Start VVO

16 VEGA Visual OperatingSet-up of a VBUS-radar sensor VEGAPULS 81F7 Set-up of a VBUS-radar sensor VEGAPULS 81F7.1 Configure sensorConnect the sensor b

Page 9 - VEGA Visual Operating 9

VEGA Visual Operating 17Set-up of a VBUS-radar sensor VEGAPULS 81FClick to , then to .From the window "Sensor optimisation“you can carry out all

Page 10 - 10 VEGA Visual Operating

18 VEGA Visual OperatingSet-up of a VBUS-radar sensor VEGAPULS 81FAfter the operating range you determinethe measuring conditions. Click to "Sol

Page 11 - VEGA Visual Operating 11

VEGA Visual Operating 19Set-up of a VBUS-radar sensor VEGAPULS 81FThe window "Pulse velocity“ can be onlychosen, if in the window "Mounting

Page 12 - 5.1 Configure sensor

2 VEGA Visual OperatingContentsContents1 Product description1.1 Function of VEGA Visual Operating ... 41.2 System requir

Page 13 - VEGA Visual Operating 13

20 VEGA Visual OperatingSet-up of a VBUS-radar sensor VEGAPULS 81FThe echo curve shows all reflec-tions of the radar signal, i.e. not onlythe product

Page 14 - 6.1 Configure sensor

VEGA Visual Operating 21Set-up of a VBUS-radar sensor VEGAPULS 81FIn the false echo storage it is deter-mined which echoes are not causedby the medium

Page 15 - VEGA Visual Operating 15

22 VEGA Visual OperatingSet-up of a capacitive electrode EK8 Set-up of a capacitive electrode EK8.1 Configure sensorConnect the sensor by means ofVEGA

Page 16 - 7.1 Configure sensor

VEGA Visual Operating 23Set-up of a capacitive electrode EKClick to , then to .8.2 Sensor parameter adjustmentFrom the window "Instrument datapa

Page 17 - VEGA Visual Operating 17

24 VEGA Visual OperatingSet-up of a signal conditioning instrument VEGAMET 6149 Set-up of a signal conditioning instrument VEGAMET 6149.1 Configuratio

Page 18 - 18 VEGA Visual Operating

VEGA Visual Operating 25Set-up of a signal conditioning instrument VEGAMET 614With the reset to factory setting(corresponds to "Reset to De-fault

Page 19 - VEGA Visual Operating 19

26 VEGA Visual OperatingSet-up of a signal conditioning instrument VEGAMET 6149.2 Create new measurement loopA new measurement loop should becreated w

Page 20 - 20 VEGA Visual Operating

VEGA Visual Operating 27Set-up of a signal conditioning instrument VEGAMET 614On signal conditioning instruments withtwo sensor inputs (VEGAMET 515,51

Page 21 - VEGA Visual Operating 21

28 VEGA Visual OperatingSet-up of a signal conditioning instrument VEGAMET 6149.3 Modify measurement loopClick to , point to and click to .With ,

Page 22 - 8.1 Configure sensor

VEGA Visual Operating 29Set-up of a signal conditioning instrument VEGAMET 6149.4 Delete measurement loopClick to , point to and click to .Click to

Page 23 - VEGA Visual Operating 23

VEGA Visual Operating 3Contents8 Set-up of a capacitive electrode EK8.1 Configure sensor ...

Page 24 - 24 VEGA Visual Operating

30 VEGA Visual OperatingSet-up of a signal conditioning instrument VEGAMET 6149.5 Configuration measurement loopClick to , then to .Click to the requ

Page 25 - VEGA Visual Operating 25

VEGA Visual Operating 31Set-up of a signal conditioning instrument VEGAMET 614For the adjustment with medium you have toknow the actual level in perce

Page 26 - 26 VEGA Visual Operating

32 VEGA Visual OperatingSet-up of a signal conditioning instrument VEGAMET 614Here you can adapt the measurementto the vessel geometry. This is onlyim

Page 27 - VEGA Visual Operating 27

VEGA Visual Operating 33Set-up of a signal conditioning instrument VEGAMET 614With in the window "Condi-tioning“ you reach the window "Int

Page 28 - 9.3 Modify measurement loop

34 VEGA Visual OperatingSet-up of a signal conditioning instrument VEGAMET 614In the window "Outputs“ you first of allclick to . In the window&q

Page 29 - 9.4 Delete measurement loop

VEGA Visual Operating 35Set-up of a signal conditioning instrument VEGAMET 614In the window "Switching output“ youdetermine the mode of the relay

Page 30 - 30 VEGA Visual Operating

36 VEGA Visual OperatingSet-up of a signal conditioning instrument VEGAMET 614For processing of linearisation curves,click to , then to .Choose the c

Page 31 - VEGA Visual Operating 31

VEGA Visual Operating 37Establishing of a linked measurement loop with VEGAMET 515V10 Establish a linked measurement loop with VEGAMET 515VThe connect

Page 32 - 32 VEGA Visual Operating

38 VEGA Visual OperatingEstablishing of a linked measurement loop with VEGAMET 515VNow click to , point to and click to In this window choose first o

Page 33 - VEGA Visual Operating 33

VEGA Visual Operating 39Establishing of a linked measurement loop with VEGAMET 515VClick to .Now you see that the two sensors are"not configured

Page 34 - 34 VEGA Visual Operating

4 VEGA Visual OperatingProduct description1 Product description1.1 Function of VEGA VisualOperatingThe adjustment software VEGA Visual Ope-rating (VVO

Page 35 - VEGA Visual Operating 35

40 VEGA Visual OperatingEstablishing of a linked measurement loop with VEGAMET 515VChoose now (do not configure yet) input 2and click again to .Choos

Page 36 - 36 VEGA Visual Operating

VEGA Visual Operating 41Establishing of a linked measurement loop with VEGAMET 515VIt happens often that an existing meas-urement loop configuration s

Page 37 - VEGA Visual Operating 37

42 VEGA Visual OperatingEstablishing of a linked measurement loop with VEGAMET 515VIn the window "Modify sensor coordination“you are informed tha

Page 38 - 38 VEGA Visual Operating

VEGA Visual Operating 43Set-up of the processing system VEGALOG11 Set-up of the processing system VEGALOGConnect the CPU-card of VEGALOGand the PC wit

Page 39 - VEGA Visual Operating 39

44 VEGA Visual OperatingSet-up of the processing system VEGALOGFrom this window you can also de-lete sensor data, modify sensordesignations (Sensor-TA

Page 40 - 40 VEGA Visual Operating

VEGA Visual Operating 45General VVO-functions12 General VVO-functions12.1 LanguageWith the installation of VVO a language had tobe selected. When you

Page 41 - VEGA Visual Operating 41

46 VEGA Visual Operating12.3 Modify standard interfaceIf you want to modify the interface of yourcomputer which you have chosen during theVVO-installa

Page 42 - 42 VEGA Visual Operating

VEGA Visual Operating 47General VVO-functions12.4 Program- preadjustmentsClick to , point to andclick to . The window with the pread-justed and re

Page 43 - VEGA Visual Operating 43

48 VEGA Visual OperatingGeneral VVO-functions12.5 DatabaseDuring the installation of VVO the directorieshad been installed on your hard drive asshown.

Page 44 - 44 VEGA Visual Operating

VEGA Visual Operating 49General VVO-functionsYou can add notes to the created databaseor delete the database. Click to andthen to .First of all you

Page 45 - 12 General VVO-functions

VEGA Visual Operating 5InstallationImportant note!Exclusively use the yellow diskettes of VEGA.This ensures that the original software will beinstalle

Page 46 - 46 VEGA Visual Operating

50 VEGA Visual OperatingGeneral VVO-functionsBackupWith this function you can make additionalbackups of the connected instruments.These backups are no

Page 47 - 12.4 Program- preadjustments

VEGA Visual Operating 51General VVO-functionsProbably you have connected severalsensors to one VBUS-line (e.g. to an AV-card of VEGALOG). It is possib

Page 48 - Edit database

52 VEGA Visual OperatingGeneral VVO-functionsRestore configurationWhen a safety file was made of one of theinstrument adjustments (e.g. configuration

Page 49 - VEGA Visual Operating 49

VEGA Visual Operating 53General VVO-functions12.6 PrintAll information such as instrument configura-tion, serial number etc. of all current meas-ureme

Page 50 - 50 VEGA Visual Operating

54 VEGA Visual Operating12.7 User levelAs no modifications can be madeon the connected instruments. Just observa-tion and monitoring are possible. Wi

Page 51 - VEGA Visual Operating 51

VEGA Visual Operating 5512.8 ConnectionThe connection to the connected instrumentsis always made automatically by VVO. Insome cases it is necessary to

Page 52 - Restore configuration

56 VEGA Visual OperatingGeneral VVO-functions12.9 Display of measured valueThe current measured values of the meas-urement loops can be displayed from

Page 53 - 12.6 Print

VEGA Visual Operating 57General VVO-functions12.10 Instrument statusWhen you want to know if your measurementloops function without problems, you canc

Page 54 - 12.7 User level

58 VEGA Visual OperatingGeneral VVO-functions12.11 SimulationIt is often requested to simulate certain levelsor other measured values, e.g. to test co

Page 55 - 12.8 Connection

VEGA Visual Operating 5913 Help program VVO-ViewerWith the software VVO-Viewer you can havea look to the database created in VVO. VVOmust not be start

Page 56 - 56 VEGA Visual Operating

6 VEGA Visual Operating+-VEGACONNECT 2to sensorR = 100 WInstrument connection3 Instrument connection3.1 VVO directly on the sensorVEGACONNECT2VEGACONN

Page 57 - 12.10 Instrument status

60 VEGA Visual Operating14 Help program tank calculationHelp program tank calculationWith the help program "Tank Calculation“linearisation curves

Page 58 - 12.11 Simulation

VEGA Visual Operating 61Help program tank calculationAfter the calculation the window "Linearisationtable“ shows the curve. Click to OK.From the

Page 59 - 13 Help program VVO-Viewer

62 VEGA Visual OperatingVVO-menu bar15 VVO-menu barProgramMeasurementloopMeasuring systemLinearisation curvesParameter adjust-mentStatusSimulationDisp

Page 60 - 60 VEGA Visual Operating

VEGA Visual Operating 63VVO-menu barNewModifyDeleteLanguageUser accessCommunicationOptionsServicesQuit HelpPrintViewConnection F8VVO-Mode F7User level

Page 61 - VEGA Visual Operating 61

ISO 90012.20 597 / Dec. ‘98VEGA Grieshaber KGAm Hohenstein 113D-77761 SchiltachPhone (0 78 36) 50 - 0Fax (0 78 36) 50 - 201e-mail [email protected] st

Page 62 - 15 VVO-menu bar

VEGA Visual Operating 7RS 232RS 232Instrument connection3.4 VVO on the CPU-card ofVEGALOGThe PC is connected via a RS 232-cable tothe CPU-card of VEGA

Page 63 - VEGA Visual Operating 63

8 VEGA Visual OperatingStart VVO4 Start VVOClick to to terminate the info showand to continue the start procedure. Theshow can be terminated at any i

Page 64 - ISO 9001

VEGA Visual Operating 9Start VVOIn the VVO there are three differentuser levels. As you can makeno modifications on the connectedinstruments. Just ob