Operating InstructionsVEGASWING 51- contactlesselectronic switchDocument ID:30212Vibration
4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and
1 2 Fig. 3: Horizontalinstallation1 Switching point2 Switching point (recommended mounting position, particularly for adhesiveproducts)Use the recomme
Donot hold VEGASWING 51 on the tuning fork.The process fitting must be sealed if there is gauge or low pressure inthe vessel. Before use, check if the
Incase of horizontal mounting in adhesive and viscous products, thesurfaces of the tuning fork should be vertical in order to reduce buildupon the tun
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
5.2 Wiring plan1 2Fig. 7: Overviewof the connection versions1 Valve plug ISO 44002 Valve plug ISO 4400 with IDC method of terminationValve plug ISO 44
1456789102 3Fig. 8: Connection, valveplug ISO 44001 Pressure screw2 Pressure disc3 Seal ring4 Fixing screw5 Seal washer6 Plug housing7 Plug insert8 P
1 2 3 45Fig. 9: Connection, valveplug ISO 4400 with IDC crimping technology1 Compression nut2 Cable3 Seal ring4 Terminal insert5 Plug housingWe recomm
RL RL 3 2 1 3 2 1 N- L1+ L1+ N- Max. Min. PE PE Fig. 10: Wiringplan, contactless electronic switch with valve plug ISO 4400PE Protective groundRL L
6 Setup6.1 Indication of the switching statusThe switching status of the electronics can be checked via the signallamp integrated in the upper part of
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
6.3 Function chartThe following chart provides an overview of the switching conditionsdepending on the adjusted mode and level.Level Switching status
7 Maintenance and fault rectification7.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.7.2 Remov
Error Cause RemovalThesignal lampflashes alternatelyred and greenShortcircuit oroverloadCheck the electrical connectionDepending on the failure reason
41235678Fig. 16: Exchangeof the electronics1 Fixing screw2 Valve plug ISO 44003 Profile seal4 Electronics module5 Rotary switch (16-steps)6 Connection
Youcan download a return form (23 KB) from our Internet homepagewww.vega.com under: "Downloads - Forms and certificates - Repairform".By doin
8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Tuning fork 316L- Process seal Klinger
120°C(32°F)-20°C(-4°F)40°C(104°F)20°C(68°F)80°C(176°F)60°C(140°F)-40°C(-40°F)0°C(32°F)70°C(158°F)50°C(122°F)-40°C(-40°F)100°C(2
OperationPlug connections Specification see "Connecting to power supply"Signal lamp (LED)- Green Switch closed- Red Switch open- Red (flashing
ApprovalsInstruments with approvals can have different technical data depending on the version.That's why the associated approval documents have t
Editing status: 2011-09-27VEGASWING 51 •- contactless electronic switch 3Contents30212-EN-111006
9.2 DimensionsVEGASWING 51 - standard version158mm (6 7/32")35mm(1 3/8")27mm(1 1/16")36mm(1 27/64")L40mm(1 37/64")13mm(33/64&
VEGASWING 51 - hightemperature version~88mm (3 15/32")~101mm (3 31/32")L40mm(1 37/64")13mm(33/64")ø21,3mm(27/32")ø31,7mm(1 1/
1 23~115mm (7 13/32")L40mm(1 37/64")~105mm (4 9/64")L13mm(33/64")Fig. 21: VEGASWING 51 - hightemperature version1 Bolting (valve p
9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only i
34 VEGASWING 51 • - contactless electronic sw itch9 Supplement30212-EN-111006
VEGASWING 51 •- contactless electronic switch 359 Supplement30212-EN-111006
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
2.5 Safetylabel on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the l
3 Product description3.1 StructureThe scope of delivery encompasses:l VEGASWING 51 point level switchl Test magnetl Documentation- this operating inst
3.2 Principle of operationVEGASWING 51 is a point level sensor with tuning fork for leveldetection.It is designed for industrial use in all areas of p
3.4 Storage and transportThe device was protected by packaging during transport. Its capacityto handle normal loads during transport is assured by a t