104MountingVEGASON 63 • Foundation Fieldbus28792-EN-1304174 Mounting4.1 General instructionsMakesurethatallpartsoftheinstrumentcomingindir
114MountingVEGASON 63 • Foundation Fieldbus28792-EN-13041712Fig. 3: Minimum distance to the max. level1 Dead band2 Reference planeInformation:If th
124MountingVEGASON 63 • Foundation Fieldbus28792-EN-130417is expected. In this case, we recommend repeating a false echo stor-age later with existing
134MountingVEGASON 63 • Foundation Fieldbus28792-EN-130417d45°hmax.d100 mm/4"150 mm/6"200 mm/8"250 mm/10"300 mm400 mm500 mm600 mm
144MountingVEGASON 63 • Foundation Fieldbus28792-EN-130417vessel nearly to maximum. Such an arrangement is suitable primarily foropenvesselssucha
154MountingVEGASON 63 • Foundation Fieldbus28792-EN-130417Fig. 12: AgitatorsDonotmounttheinstrumentsinorabovethellingstream.Makesuretha
164MountingVEGASON 63 • Foundation Fieldbus28792-EN-130417Byusingastandpipe(surgeorbypasstube),theinuenceofvesselinstallations, foam gen
175 Connecting to power supplyVEGASON 63 • Foundation Fieldbus28792-EN-1304175 Connecting to power supply5.1 Preparing the connectionAlways keep in
185 Connecting to power supplyVEGASON 63 • Foundation Fieldbus28792-EN-130417low frequency potential equalisation currents are thus suppressed, butth
195 Connecting to power supplyVEGASON 63 • Foundation Fieldbus28792-EN-13041710. Connect the screen to the internal ground terminal, connect the oute
2ContentsVEGASON 63 • Foundation Fieldbus28792-EN-130417Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGASON 63 • Foundation Fieldbus28792-EN-130417I²C34512DisplayTyp:12 5678 BusSim.Fig. 17: Electronics and connection com
215 Connecting to power supplyVEGASON 63 • Foundation Fieldbus28792-EN-1304175.4 Wiring plan, double chamber housing1 2 345Fig. 19: Double chamber ho
225 Connecting to power supplyVEGASON 63 • Foundation Fieldbus28792-EN-130417123Display12I2CFig. 21: Connection compartment, double chamber housing1
235 Connecting to power supplyVEGASON 63 • Foundation Fieldbus28792-EN-1304175.6 Switch-on phaseAfter VEGASON 63 is connected to voltage supply or af
246SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-1304176 Set up with the display and adjustment mod
256SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-130417Fig. 24: Insert display and adjustment module
266SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-130417 – Save value• [->] key to select: – Menu
276SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-1304172. Selectthemenuitem"Basic adjustme
286SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-130417Apartfromthemedium,thevesselshapecana
296SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-130417False signal suppressionChange now?Proceed as
3ContentsVEGASON 63 • Foundation Fieldbus28792-EN-1304178.4 Software update ...
306SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-130417• PINCopy sensor dataCopy sensor data?Basic a
316SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-130417Basic adjustment▶Basic adjustment 1DisplayDia
326SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 63 • Foundation Fieldbus28792-EN-130417ServiceBasic adjustment 4DisplayDiagnostics▶S
337 Set up with PACTware and other adjustment programsVEGASON 63 • Foundation Fieldbus28792-EN-1304177 Set up with PACTware and other adjustment prog
347 Set up with PACTware and other adjustment programsVEGASON 63 • Foundation Fieldbus28792-EN-1304177.2 Parameter adjustment with PACTwareFurther se
358MaintenanceandfaultrecticationVEGASON 63 • Foundation Fieldbus28792-EN-1304178 Maintenanceandfaultrectication8.1 MaintenanceIf the instru
368MaintenanceandfaultrecticationVEGASON 63 • Foundation Fieldbus28792-EN-130417Error Cause RecticationInstrument does not appear during connect
378MaintenanceandfaultrecticationVEGASON 63 • Foundation Fieldbus28792-EN-130417Information:Whenloadingonsite,rstofalltheorderdatamust
388MaintenanceandfaultrecticationVEGASON 63 • Foundation Fieldbus28792-EN-1304178.5 Instrument repairIf a repair is necessary, please proceed as
399 DismountingVEGASON 63 • Foundation Fieldbus28792-EN-1304179 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous pro
41 About this documentVEGASON 63 • Foundation Fieldbus28792-EN-1304171 About this document1.1 FunctionThis operating instructions manual provides all
4010 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-13041710 Supplement10.1 Technical dataGeneral dataMaterials,wettedparts Ʋ Processtting UP
4110 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-130417Referenceconditionstomeasuringaccuracy(accordingtoDINEN60770-1)Referencecondit
4210 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-130417Process conditionsProcess pressure Ʋ withcompressionange -20…100kPa/-0.2…1bar(
4310 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-130417 Ʋ Standard length 5m(16.4ft) Ʋ Max.length 1000m(3280ft) Ʋ Min.bendingradius 25
4410 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-130417For that reason the associated approval documents of these instruments have to be carefu
4510 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-130417Secondary_value_1CalibrationLowest PointCalibrationHighest PointSensor_valuecal_level_lo
4610 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-130417• CURVE_STATUS – Resultoftableplausibilitycheck• SUB_DEVICE_NUMBER• SENSOR_ELEMENT_T
4710 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-130417• solids_vessel_type – Setuptosuittheprocessconditions.IfSpecial-Parameteradjus
4810 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-13041710.3 DimensionsHousing in protection IP 66/IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.0
4910 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-130417Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(
52 For your safetyVEGASON 63 • Foundation Fieldbus28792-EN-1304172 For your safety2.1 Authorised personnelAll operations described in this operating
5010 SupplementVEGASON 63 • Foundation Fieldbus28792-EN-13041710.4 Industrial property rightsVEGA product lines are global protected by industrial pr
51NotesVEGASON 63 • Foundation Fieldbus28792-EN-130417
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany28792-EN-130417All statements concerning scope of delivery, application, practi
62 For your safetyVEGASON 63 • Foundation Fieldbus28792-EN-130417successfultesting.YoucanndtheCEconformitydeclarationinthedownloadareaof
73 Product descriptionVEGASON 63 • Foundation Fieldbus28792-EN-1304173 Product description3.1 CongurationThe scope of delivery encompasses:• VEGASO
83 Product descriptionVEGASON 63 • Foundation Fieldbus28792-EN-130417is proportional to the distance and hence the level. The determined level is conv