Vega VEGASON 66 Profibus PA User Manual

Browse online or download User Manual for Equipment Vega VEGASON 66 Profibus PA. VEGA VEGASON 66 Profibus PA User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instructions

Operating InstructionsVEGASON 66Profibus PA

Page 2 - Contents

homepage www.vega.com under "Services - Downloads -Software - Profibus". There you can also find the appropriatecertificates. InaPDM environmen

Page 3

4 Mounting4.1 General instructionsMake sure that the wetted parts of VEGASON 66, especiallythe seal and process fitting, are suitable for the existingp

Page 4 - 1 Sequence

The reference plane for the measuring range (version A) is thelower edge of the flange. The reference plane for versions B, Cand D is the lower edge of

Page 5 - 2 For your safety

1 32100%0%4Fig. 4: Version B, C, D - Measuring range (operating range) and max. measuringdistance1 full (dead zone)2 empty (max. measuring distance)3

Page 6

6 Plug the electronics housing to the transducer tube. Do notsqueeze any cables. The housing is in the correct position,if the lower notch (2) of the

Page 7 - Chapter "Disposal"

12345Fig. 5: Mounting - Version B1 Groove to lock the housing2 Marking notch3 Screw of swivelling holder (hexagon SW 13)4 Grub screw, fixing ring (hexa

Page 8 - 3 Product description

6 Plug the connection head to the transducer tube. Do notsqueeze any cables. The cylinder is in the correct position,if the lower notch (2) of the tra

Page 9 - 3.2 Principle of operation

12345Fig. 6: Mounting - Version C1 Groove for locking the connection head2 Marking notch3 Screw of swivelling holder (hexagon SW 13)4 Grub screw, fixin

Page 10 - 3.4 Storage and transport

7 Rotate the connection head in such a way that the cableentry points downwards (moisture can drain off). Fastenthe cylinder with screws (4); torque ma

Page 11 - 4 Mounting

1> 500 mmFig. 8: Installation location1 Reference planeIn vessels with conical vessel bottom it can be advantageousto direct the sensor in the cent

Page 12 - 28789-EN-060731

Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...

Page 13 - 4.2 Mounting preparations

If the reflective properties of the medium are good, you canmount VEGASON 66 on a socket piece. The socket endshould be smooth and burr-free, if possib

Page 14

If there are agitators in the vessel, a false echo storage shouldbe carried out with the agitators in motion. This ensures thatthe interfering reflecti

Page 15

Fig. 14: Inflowing mediumThrough the action of filling, stirring and other processes in thevessel, dense foams which considerably damp the emittedsignal

Page 16

Fig. 15: Heat fluctuationsVEGASON 66 - Profibus PA 23Mounting28789-EN-060731

Page 17

5 Connecting to voltage supply5.1 Preparing the connectionGenerally not the following safety instructions:l Connect only in the complete absence of li

Page 18 - 4.3 Mounting instructions

must be connected directly to the internal ground terminal. Theground terminal outside on the housing must be connected tothe potential equalisation (

Page 19 - > 500 mm

10 Tighten the compression nut of the cable entry, the sealring must completely encircle the cable11 Connect the lead cable for power supply in the sa

Page 20

132Display12 5678I2CFig. 18: Electronics compartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Intrnal connection cable

Page 21

PE/ L/ NL1 N1 21 234BUSFig. 20: Wiring plan, double chamber housing1 Voltage supply2 Signal output5.4 Switch-on phaseAfter VEGASON 66 is connected to

Page 22

6 Setup with the indicating andadjustment module PLICSCOM6.1 Short descriptionThe indicating and adjustment module PLICSCOM is used formeasured value

Page 23

7.3 Parameter adjustment with PDM...408 Maintenance and fault rectification8.1 Maintenance ...418.2 Fault rectification

Page 24 - 5.1 Preparing the connection

Fig. 21: Installation of the indicating and adjustment moduleNote:If you intend to retrofit VEGASON 66 with an indicating andadjustment module for cont

Page 25 - 5.2 Connection steps

6.3 Adjustment system1.1231Fig. 22: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- mo

Page 26

6.4 Setup procedureAfter VEGASON 66 is connected to voltage supply or aftervoltage recurrence, the instrument carries out a self-check forapprox. 30 s

Page 27

Proceed as follows:1 Move from the measured value display to the main menuby pushing [OK].▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the m

Page 28 - 5.4 Switch-on phase

Each product has different reflective properties. In addition,there are various interfering factors which have to be taken intoaccount: agitated product

Page 29 - 6.1 Short description

Damping0 sEnter the requested parameter via the appropriate keys, saveyour settings and jump to the next menu item with the [->] key.A linearizatio

Page 30

level measurement. A false echo memory should be createdwith empty vessel so that all potential interfering reflections willbe detected.Gating out of f

Page 31 - - modify value of a parameter

6.5 Menu schematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Sensor address0001.2Min. adjustment000.0 %=10.000 m(d)1.245 m(d)1.

Page 32 - 6.4 Setup procedure

3.1PointerDist.-min: 0.580 m(d)Dist. max: 16.785 m(d)T-min.: 30.6 °CT-min.: 4.5 °C3.2Meas. reliability36 dBSensor statusOK3.3Curve selectionEcho curve

Page 33

7 Setup with P ACTware™ and otheradjustment programs7.1 Connecting the PC~=Power supplyVEGACONNECT 3PACTware /TM>PA<231Fig. 23: Connection di

Page 34 - Storage tank

1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th

Page 35

Note:Keep in mind that for setup of VEGASON 66, DTM Collection10/2005 or a newer version must be used.All currently available VEGA DTMs are provided i

Page 36 - Change now?

8 Maintenance and fault rectification8.1 MaintenanceWhen used as directed in normal operation, VEGASON 66 iscompletely maintenance free.8.2 Fault recti

Page 37 - 6.5 Menu schematic

? In Simatic S7 the measured value is always presented as 0l Only four bytes are consistently loaded in the PLCà Use function component SFC14 to load

Page 38

? E017l Adjustment span too smallà Carry out a fresh adjustment and increase the distancebetween min. and max. adjustment? E036l no operable sensor so

Page 39 - >PA<

Information:When loading on site, the order data must be downloaded fromthe Internet (see Operating Instructions manual "Oscillator").The os

Page 40

9 Dismounting9.1 Dismounting procedureCaution:During operation, individual cores of the transducer cable carrya voltage of approx. 70 V. Therefore dis

Page 41 - 8.2 Fault rectification

10 Supplement10.1 Technical dataGeneral dataMaterials, wetted parts- Flange PP or Alu- Swivelling holder, flange galvanized steel- Transducer UP- Trans

Page 42

Input variableParameter- Version A distance between lower edge of the flange andproduct surface- version B, C and D distance between lower edge of the

Page 43

10 m3 m120 mm140 mm6 mm-6 mm20 mm40 mm60 mm80 mm100 mm-40 mm-20 mm-140 mm-120 mm-100 mm-80 mm-60 mm20 m 30 m 40 m 50 m 60 m 70 mFig. 24: Accuracy VEGA

Page 44 - 8.4 Instrument repair

10 m3 m120 mm140 mm6 mm-6 mm20 mm40 mm60 mm80 mm100 mm-40 mm-20 mm-140 mm-120 mm-100 mm-80 mm-60 mm20 m 30 m 40 m 50 m 60 m 70 mFig. 25: Accuracy VEGA

Page 45 - 9 Dismounting

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist

Page 46 - 10 Supplement

Vibration resistance mechanical vibration with 1 g in the frequencyrange 5 … 200 Hz7)Electromechanical dataCable entry- Double chamber housingl 1x cab

Page 47

Electrical protective measuresProtection IP 66/IP 67Overvoltage category IIIProtection class IApprovalsATEX II 2 GEExmII T6, ATEX II 1/2 DIP66 TSupple

Page 48

10.2 Profibus PAInstrument master fileThe instrument master file (GSD) contains the characteristic data of the Profibus PAinstrument. These data are, e.g.

Page 49

m(d)% Lin%Min-MaxadjustmentLinearizationPROFIBUS PA-outputPrimaryValueSecondaryValue 1SecondaryValue 2TargetModeFailuremodeAlarmsScalingSource forscal

Page 50

Note:The modules are available in two versions:l Short for Profibus master supporting only one "IdentifierFormat" byte, e.g. Allen Bradleyl Lo

Page 51

Byte-No.1234 5 6789 10StatusStatusStatusStatus(FB1)IEEE-754-Floating point valuePA-OUT(FB1)IEEE-754-Floating point valueAdditional CyclicValueFormatVa

Page 52 - 10.2 Profibus PA

StatuscodeDescription according to Profi-bus standardPossible cause0x44 uncertain - last unstable value Failsafe replacement value (Failsafe-Mode =&quo

Page 53

10.3 DimensionsHousingø84mm~27/")120mm (423/32")* 129mm (55/64")5/16")M20x1,5/½NPTM12xFig. 29: Aluminium double chamber housing* D

Page 54

VEGASON 663 434D200mm340mm405mm165mmb24mm24mm26mm20mmk160mm295mm355mm125mmdø18mmø22mmø26mmø18mmDN 80 PN16/40DN 200 PN16DN 250 PN16DN 50 PN16/408x12x12

Page 55

VEGASON 663 4D200mm340mm405mm165mmb24mm24mm26mm20mmk160mm295mm355mm125mmd8x ø18mm12x ø22mm12x ø26mm4x ø18mmDN 80 PN16/40DN 200 PN16DN 250 PN16DN 50 PN

Page 56

account, as is usual with a class A instrument acc. toEN 61326. If VEGASON 66 is used in a different environment,the electromagnetic compatibility to o

Page 57 - 10.3 Dimensions

10.4 CE declarations of conformity10.5 Industrial property rightsSupplement60 VEGASON 66 - Profibus PA28789-EN-060731

Page 58 - VEGASON 66

VEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only in U.S.A.: Further information

Page 59

Supplement62 VEGASON 66 - Profibus PA28789-EN-060731

Page 60

SupplementVEGASON 66 - Profibus PA 6328789-EN-060731

Page 61

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] 9001All statem

Page 62

Please help us fulfil this obligation by observing the environ-mental instructions in this manual:l Chapter "Storage and transport"l Chapter

Page 63

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGASON 66 ultrasonic sensorl unassembled cable glandl Documentation- this op

Page 64 - ISO 9001

1234Fig. 1: VEGASON 66 compact with swivelling holder1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Swivelling holder

Comments to this Manuals

No comments