Operating InstructionsSuspension pressure transmitter with ceramic measuring cellVEGABAR 86Modbus and Levelmaster protocolDocument ID: 46296
103 Product descriptionVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311073.3 Packaging, transport and storageYour instrument was protected b
113 Product descriptionVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Youcanndfurtherinformationintheoperatinginstructionsofthe
124 MountingVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311074 Mounting4.1 General instructions to use the instrumentMake sure that all par
134 MountingVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110721Fig. 4: Temperature ranges1 Process temperature2 Ambient temperature4.2 Ve
144 MountingVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107213434Fig. 5: Position of the lter element - Ex-d version1 Single chamber hou
154 MountingVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Fig. 7: Measurement setup for level measurement4.4 External housing1234Fig. 8:
164 MountingVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110790 mm(3.54")R 3,5 mm(0.14")3mm(0.12")70 mm(2.76")8 mm(0.32&
175 Connecting to power supply and bus systemVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311075 Connecting to power supply and bus system5.
185 Connecting to power supply and bus systemVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311075.2 ConnectionThe voltage supply and signal ou
195 Connecting to power supply and bus systemVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311077. Connect the screen to the internal ground
2ContentsVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Contents1 About this document1.1 Function ...
205 Connecting to power supply and bus systemVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Information:The connection of an external disp
215 Connecting to power supply and bus systemVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311075.4 External housing with version IP 68 (25 b
225 Connecting to power supply and bus systemVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311071234634125Fig. 16: Connection of the sensor in
235 Connecting to power supply and bus systemVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Terminal Function Polarity5 Function ground wi
246 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311076 Set up with the display and adjustment
256 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311076.2 Adjustment system12Fig. 19: Display a
266 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Carry out the following steps in the below
276 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311076. Min. adjustmentIn this menu item you ca
286 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107• Special characters +, -, /, -In this men
296 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Temperature unit:Enter the requested param
3ContentsVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311078.6 Exchange process assembly with version IP 68 (25 bar) ...
306 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110721100%0%2 m(78.74")Fig. 20: Parameter
316 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311075. Save settings with [OK] and move with
326 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107user especially when adjusting the switchi
336 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107The default setting for the display value
346 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Selecttherequestedsimulationsizeanda
356 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Reset - SetupMenu item Parameter Default v
366 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Menu item Parameter Default valueSimulatio
376 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107In this menu item you gain access to the p
386 Set up with the display and adjustment moduleVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311076.5 Saving the parameter adjustment dataW
397 Setting up sensor and Modbus interface with PACTwareVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311077 Setting up sensor and Modbus int
41 About this documentVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311071 About this document1.1 FunctionThis operating instructions manual
407 Setting up sensor and Modbus interface with PACTwareVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311071Fig. 22: Connecting the PC via USB
417 Setting up sensor and Modbus interface with PACTwareVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Note:To ensure that all instrument
427 Setting up sensor and Modbus interface with PACTwareVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311077.3 Saving the parameter adjustmen
438 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311078 Diagnosis, asset management and service8.1 Ma
448 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107the following tables there are more detailed err
458 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107CodeText mes-sageCause RecticationF013no measur
468 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107CodeText mes-sageCause RecticationF265Measureme
478 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107CodeText mes-sageCause RecticationM501Error in
488 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311078.5 Calculation of total deviation (according t
498 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311078.6 Exchange process assembly with version IP 6
52 For your safetyVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311072 For your safety2.1 Authorised personnelAll operations described in th
508 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311076. Mount the cable assembly on the process asse
518 Diagnosis, asset management and serviceVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311078.9 How to proceed in case of repairYoucannd
529 DismountingVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311079 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of d
5310 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110710 Supplement10.1 Technical dataMaterials and weightsMaterials, wetted part
5410 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Connection cable with IP 68 (1 bar) versionPEConnection cable, master and sl
5510 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Nominal range Overload capacity, max. pressureOverload capacity, min. pres-s
5610 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110790 %100 %10 %ttTAttS21Fig. 27: Behaviour in case of sudden change of the pro
5710 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Deviation (according to IEC 60770)Applies to the digitalsignaloutput(HART
5810 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Long-term drift of the zero signal - Version climate-compensatedNominal meas
5910 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107 Ʋ Suspension cable 4gat5…200HzaccordingtoEN60068-2-6(vibrationw
62 For your safetyVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107radiated emissions must be taken into account, as is usual with a class A
6010 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107 Ʋ Wire resistance <0.036Ω/m(0.011Ω/ft) Ʋ Standard length 5 m (16.40
6110 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Integrated clockDate format Day.Month.YearTime format 12 h/24 hTimezoneEx
6210 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110710.2 Basics ModbusBus descriptionThe Modbus protocol is a communication pro
6310 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Parameters for the bus communicationThe VEGABAR 86 is preset with the defaul
6410 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Input registerThe input registers consist of 16 bits. They can only be read
6510 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Register Name Register Number Type NoteStatus 2100 DWord See Register 100PV
6610 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Request:Parameter Length Code/DataFunction Code 1 Byte 0x03Start Address 2 B
6710 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Parameter Length Code/DataRegister Value 2 Bytes DataFC8 DiagnosticsWiththi
6810 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Parameter Length Code/DataData 2 Bytes 0x01 to 0x7BFC17 Report Slave IDWith
6910 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110710.5 Levelmaster commandsThe VEGABAR 86 is also suitable for connection to
73 Product descriptionVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-1311073 Product description3.1 CongurationThenameplatecontainsthemos
7010 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Response:Parameter Length Code/DataReport Level (and Temperature) 24 charact
7110 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Response:Parameter Length Code/DataSet number of Floats 6 characters ASCII U
7210 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Response:Parameter Length Code/DataSet Receive to Transmit Delay 5 character
7310 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110710.6 CongurationoftypicalModbushostsFisher ROC 809Wiring plan++power
7410 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107ABB Total FlowWiring plan++power supplyMODBUSD0D1IS GNDUSB1 213452offon(
7510 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Thermo Electron AutopilotWiring plan++power supplyMODBUSD0D1IS GNDUSB12313
7610 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107Bristol ControlWave MicroWiring plan++power supplyMODBUSD0D1IS GNDUSB12313
7710 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107ScadaPackWiring plan++power supplyMODBUSD0D1IS GNDUSB13213455213496782offo
7810 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107dimensional drawings can be downloaded at www.vega.com under "Downloads
7910 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107External housing with IP 68 version1234582 mm(3.23")80 mm(3.15")10
83 Product descriptionVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107This operating instructions manual applies to the following instrumen
8010 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107VEGABAR 8621 3 4175 mm(6.89")52 mm(2.05")171 mm(6.73")ø 8 mm(
8110 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107VEGABAR 86, plastic versions1 2 320 mm(0.79")22 mm(0.87")40 mm(1.5
8210 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107VEGABAR86,angeconnectionDN PN Dkb. .2540 115 18 85A8 40 40 150 18 110B2
8310 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107VEGABAR86,hygienicttingø 78 mm (3.07")ø 92 mm (3.62")51 mm(2.0
8410 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107VEGABAR 86, threaded versionL175 mm (6.89")20 mm(0.79")68 mm(2.68&
8510 SupplementVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-13110710.8 Industrial property rightsVEGA product lines are global protected by i
86INDEXVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107INDEXAAdjust Date/Time 34Adjustment – Level 30, 31 – Overview 29 – System 25 – U
87NotesVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany46296-EN-131107All statements concerning scope of delivery, application, practi
93 Product descriptionVEGABAR 86 • Modbus and Levelmaster protocol46296-EN-131107The VEGABAR 86 is a suspension pressure transmitter for level measure