Operating InstructionsVEGAPULS 66 enamel4 … 20 mA/HART two-wireRadar

Page 2

3.2 Principle of operationVEGAPULS 66 is a radar sensor in C-band technology for continuouslevel measurement.The version with enamelled antenna is par

Page 3

3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport i

Page 4 - 1.3 Symbolism used

4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i

Page 5 - 2.3 Warning about misuse

1 32100%0%4Fig. 3: Measuringrange (operating range) and max. measuring distance1 full2 empty (max. measuring distance)3 Measuring range4 Reference pla

Page 6 - 2.7 Fulfillmen

1Fig. 4: Positionof the polarisation plane with VEGAPULS 661 Marking holeMake sure that all parts of the instrument in contact with the measuredproduc

Page 7

Ifyou cannot keep this distance you should carry out a false ec hostorage before setup. This applies mainly if buildup on the vessel wallis expected.

Page 8 - 3 Produc

Donot mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the inflowing product.Fig. 7: Inflowingliqu

Page 9

Fig. 9: Alignmentin liquidsThe mounting location of the radar sensor should be a place where noother equipment or fixtures cross the path of the microw

Page 10 - 3.3 Operation

Fig. 11: AgitatorsThrough the action of filling, stirring and other processes in the vessel,dense foams which considerably damp the emitted signals may

Page 11 - 3.4 Pack

max.min.21Fig. 12: Pipeantenna system in a tank. The vent hole in the surge pipe must bein one plane with the polarisation marking on the sensor.1 Mar

Page 12 - 4.1 General instructions

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13 - 31953-EN-090305

100% 0% 1 > 500 mm Fig. 13: VEGAPULS 66 ina bypass tube. The polarisation marking on theprocess fitting must be in one plane with the tube holes or

Page 14 - 4.2 Mounting instructions

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 15 - > 500 mm

Caution:Nogrease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that cor

Page 16

7 Insertthe wire ends into the open terminals according to the wiringplanFig. 14: Connectionsteps 6 and 78 Press down the opening levers of the termin

Page 17

55551 243Fig. 15: Materialversions, single chamber housing1 Plastic2 Aluminium3 Stainless steel, investment casting4 Stainless steel, electro-polished

Page 18

I2CDisplay11 2 56 7 8Fig. 17: Wiringplan, single chamber housing1 Voltage supply/Signal output5.4 Wiring plan, double chamber housingThe following ill

Page 19

132Display1 2 5 6 7 8I²CFig. 19: Electronicscompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 20

I2C11 2Fig. 21: Wiringplan, double chamber housing1 Voltage supply/Signal output5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 22: Doublechamb

Page 21 - 5.1 Preparing the connection

132Display1 2 5 6 7 8I²CFig. 23: Electronicscompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 22 - 5.2 Connection procedure

11 2Fig. 25: Wiringplan double chamber housing Ex d1 Voltage supply/Signal output5.6 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 26: Wireassignme

Page 23

7.3 Parameter adjustment with AMS™ and PDM . . . . . . .447.4 Saving the parameter adjustment data . . . . . . . . . . . .448 Maintenance and fault re

Page 24

6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 25

Fig. 27: Insertindicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuous meas

Page 26

6.3 Adjustment system1.1231Fig. 28: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 27

6.4 SetupprocedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You wi

Page 28

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basic adjustment" with [->] and confirm with[OK]. Now the menu item

Page 29 - 5.7 Switch on phase

LiquidAccording to the conductivity and the dielectric value of liquids, thereflection properties can differ considerably. Therefore additionaloptions s

Page 30 - 6.1 Short description

Caution:Notethe following, if VEGAPULS 66 is used as part of an overfillprotection system according to WHG:If a linearisation curve is selected, the me

Page 31

Note:Sincewith the function "Quick level change > 1 m/min." the generationof an average value of the signal processing is considerably re

Page 32 - - Select editing position

Menuitem Reset valueVessel form not knownDamping 0 sLinearisation linearSensor-TAG SensorDisplayed value DistanceExtended settings NoneCurrent output

Page 33 - Address 0

6.5 MenuschematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor selection p

Page 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35 - Linearisation curve

3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor statusOK3.3Curve selectionEcho curve▼3.4Echo curvePresenta

Page 36 - Extended setting

6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar

Page 37 - Copy sensor data?

7 Setupwith PACTware and other adjustmentprograms7.1 Connecting the PC312Fig. 29: Connectionof the PC via VEGACONNECT directly to the sensor1 USB cabl

Page 38

Necessary components:l VEGAPULS 66l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFi

Page 39 - 6.5 Menu

Note:Keepin mind that for setup of VEGAPULS 66, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are provided in the

Page 40

8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte

Page 41 - 6.6 Saving

? Currentsignal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return instrument for repairIn Ex applica

Page 42 - 7.1 Connecting the PC

Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q

Page 43

l Please ask the agency serving you for the address of your returnshipment. You can find the respective agency on our websitewww.vega.com under: "

Page 44

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pr essure in the vessel, high tempe

Page 45 - ? 4 … 20 mA signal missing

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46 - ? E041, E042, E043

10 Supplement10.1 Technical dataGeneral data316L corresponds to 1.4404 or 1 .4435Materials, wetted parts- Antenna Enamel- Antenna cone PTFE (TFM 1600)

Page 47 - 8.5 Instrument repair

Reference conditions to measuring accuracy (similar to DIN EN 60770-1)Reference conditions according to DIN EN 61298-1- Temperature +18 … +30 °C (+64

Page 48

1,0 m (3.28 ft)35 m (114.8 ft)20 mm (0.788 in)10 mm (0.394 in)- 10 mm (- 0.394 in)- 20 mm (- 0.788 in)0Fig. 32: Deviation VEGAPULS 66 enamelInfluence

Page 49 - 9 Dismou

- Versions IP 66/IP 68, 1 bar and IP 68, PEconnection cable-20 … +60 °C (-4 … +140 °F)- Versions IP 66/IP 68, 1 bar and IP 68,PUR connection cable-20

Page 50 - 10 Supplem

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry/plug8)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø

Page 51

- Diameter approx. 8 mm (0.315 in)- Colour - standard PE Black- Colour - standard PUR Blue- Colour - Ex-version BlueIndicating and adjustment moduleVo

Page 52

1000750500250141816 20 22 24 26 28 30 32 34 36ΩV4123Fig. 35: Voltagediagram1 HART load2 Voltage limit EEx-ia instrument3 Voltage limit non-Ex/Exd inst

Page 53

ApprovalsDepending on the version, instruments with approvals can have different technical data.For these instruments, the corresponding approval docum

Page 54

10.2 DimensionsHousing in protection IP 66/IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")

Page 55

Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(3.03")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.

Page 56

Duringthe entire duration of use, the user is obliged to determine thecompliance of the required occupational safety measures with thecurrent valid ru

Page 57

VEGAPULS 66, enamelD b k ydDN 150 PN 16DN 200 PN 16285 22 240 8xø22340 24 295 12xø22276226D1 D2212 144268 162D b k ydDN 150 PN 16DN 200 PN 16D1 D2mmin

Page 58 - 10.2 Dim

10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 59 - M20x1,5M20x1,5

62 VEGAPULS 66 enamel • 4 … 20 mA/HART two-wire10 Supplement31953-EN-090305

Page 60

VEGAPULS 66 enamel • 4 … 20 mA/HART two-wire 6310 Supplement31953-EN-090305

Page 61 - 10.4 Trademark

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 62

l The instrument must not cause any interfering emissionsl The device must be insensitive to interfering immissions, includingthose that may cause und

Page 63

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAPULS 66 radar sensorl Documentation- this operating instructions manual-

Page 64 - ISO 9001

321Fig. 1: VEGAPULS 66 - enamelversion with plastic housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Process fitti