Operating InstructionsVEGAFLEX 624 … 20 mA/HART two-wireDocument ID:31837Guided Microwave

Page 2

Unless otherwise indicated, the packages must be stored only underthe following conditions:l Not in the openl Dry and dust freel Not exposed to corros

Page 3

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Page 4 - 1.3 Symbolism used

Fig. 2: Measuresagainst moisture penetrationThe reference plane for the measuring range of the sensors is thesealing surface of the thread or flange.Ke

Page 5 - 2.3 Warning about misuse

keep in mind that measurement down to the tip of the probe is notpossible. The exact value of the min. distance (lower dead band) isstated in chapter

Page 6

Lxø 16 mm(5/8")123Fig. 4: Extensionrod ø 16 mm (0.63 in)1 Probe2 Retaining ring3 Extension rodL Rod length 100 … 2000 mm (3.937 … 78.74 in)x Thre

Page 7 - 3 Produc

≥ 300mm (11 13/16")150mm (5 29/32")150mm (5 29/32")1SW 13LFig. 5: Bow-shapedsegment ø 16 mm (0.63 in)1 Max. filling heightL 150 mm (5

Page 8 - 3.2 Principle of operation

1 2Fig. 6: Installationin plastic silo1 Flange2 Metal sheetConcrete vesselWhen installed in thick concrete ceilings, VEGAFLEX 62 should bemounted fron

Page 9 - 3.3 Operation

Ifpossible, avoid sockets. Mount the sensor flush with the vessel top. Ifthis is not possible, use short sockets with small diameter.Higher sockets or

Page 10 - 31837-EN-100426

Standpipes or bypass tubes are normally metal tubes with a diameterof 30 … 200 mm (1.18 … 7.87 in). In measurement technology such atube corresponds t

Page 11 - 4.1 General instructions

Make sure that the probe is not subjected to strong lateral forces.Mount VEGAFLEX 62 at a position in the vessel where nodisturbances, e.g. from fillin

Page 12 - 4.2 Mounting instructions

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 14

Caution:Nogrease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that cor

Page 15

7 Insertthe wire ends into the open terminals according to the wiringplanFig. 12: Connectionsteps 6 and 78 Press down the opening levers of the termin

Page 16

I²CDisplay1 2 5 6 7 83412Fig. 13: Electronicsand connection compartment with single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 S

Page 17

132Display1 2 5 6 7 8I²CFig. 15: Electronicscompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 18

I2C11 2Fig. 17: Wiringplan with double chamber housing1 Voltage supply/Signal output5.5 Wiring plan with double chamber housing Ex d132Display1 2 5 6

Page 19

121 2Fig. 19: Connectioncompartment with double chamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for c

Page 20 - 5.1 Preparing the connection

5.6 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 21: Wireassignment connection cable1 brown (+) and blue (-) to power supply or to the processing

Page 21 - 5.2 Connection procedure

6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 22

Fig. 22: Insertindicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuous meas

Page 23

8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .438.2 Rectify malfunctions . . . . . .

Page 24

6.3 Adjustment system1.1231Fig. 23: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 25

6.4 SetupstepsAfter connecting VEGAFLEX 62 to power supply or after a voltagerecurrence, the instrument carries out a self-check for approx. 30seconds

Page 26

Keepin mind that interfaces can cause faulty measurements.If you want to measure the total height of both liquids reliably, pleasecontact our service

Page 27

2 Enter the appropriate distance value in m (corresponding to thepercentage value) for the full vessel. Keep in mind that the max.level must lie below

Page 28 - 6.1 Short description

these vessels. They represent the correlation between the levelpercentage and vessel volume. By activating the appropriate curve,the volume percentage

Page 29

Proceed as follows:1 Move from the measured value display to the main menu bypushing [OK].2 Select the menu item "Service" with [->] and

Page 30

BasicadjustmentIf the function "Reset" is carried out, the sensor resets the values of thefollowing menu items to the reset values (see char

Page 31 - Standard

6.5 MenuschematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Min. adjustment0.00 %=10.000 m(d)8.000 m(d)1.2Max. adjustment100.00

Page 32

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Sensor5.00 m(d)▼Rod▼4.2ApplicationLiquid▼Standard(DK ≥ 2)▼4.3Gating out of false sig nalsChan

Page 33

6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar

Page 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35 - Copy sensor data?

7 Setup with PACTware and other adjustmentprograms7.1 Connecting the PC312Fig. 24: Connectionof the PC via VEGACONNECT directly to the sensor1 USB cab

Page 36

Necessary components:l VEGAFLEX 62l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFi

Page 37 - 6.5 Menu

Note:Keepin mind that for setup of VEGAFLEX 62, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are included as a D

Page 38

8 Maintenance and fault rectification8.1 MaintenanceWhen used as directed in normal operation, VEGAFLEX 62 iscompletely maintenance free.8.2 Rectify ma

Page 39 - 6.6 Saving

Error Cause RemovalVoltagesupplymissingCheck cables for breaks; repair ifnecessaryOperating voltagetoo low or loadresistance toohighCheck, adapt if ne

Page 40 - 7.1 Connecting the PC

8.3 Exchange or shorten cable/rodThe cable or rod (meas. part) of the probe can be shortened, ifnecessary. To loosen the meas. part you need two fork

Page 41

3 Cable: Pullthe cable out of the gravity weight4 Shorten the cable/rod with a cut-off wheel or metal saw a t thelower end. Make sure the length is cor

Page 42

The electronics modules are adapted to the respective sensor anddistinguish also in the signal output or power supply.Electronics module FX-E.60H suit

Page 43 - 8.2 Rectify malfunctions

8.6 Instrument repairIf a repair is necessary, please proceed as follows:You can download a return form (23 KB) from our Internet homepagewww.vega.com

Page 44

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 45 - 8.3 Exch

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46

10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting 316L and PTFE, Hastel

Page 47 - 8.5 Software update

- Trimming accuracy - rod < 1 mm (0.039 in)- Cable: ø 6 mm (0.236 in) up to 60 m (196.9 ft)- Trimming accuracy - cable ±0.05 %Lateral load with rod

Page 48 - 8.6 Instru

Failure signal current output (adjustable) mA value unchanged 20.5 mA, 22 mA, < 3.6 mA(adjustable)Max. output current 22 mALoad see load diagram un

Page 49 - 9 Dismou

L0-3mm (-0.118")3mm (0.118")15mm(0.591")-10mm (-0.394")0,3 m(11.811")0,08 m(3.15")0,02 m(0.787")1Fig. 30: Devia

Page 50 - 10 Supplem

03mm(0.118")-3mm(-0.118")15mm(0.591")15mm(0.591")0,08 m(3.15")0,3 m(11.811")0,3 m(11.811")L1Fig. 32: Deviation

Page 51

L3mm(0.118")0-3mm(-0.118")15mm(0.591")20mm(0.787”)0,08 m(3.15")0,3 m(11.811")20 m(787.4")1Fig. 34: Deviation VEGAFLE

Page 52

Ambient conditionsAmbient, storage and transport temperature -40 … +80 °C (-40 … +176 °F)Process conditionsProcess pressure -1 … +40 bar/-100 … +4000

Page 53

- Doublechamber housing l 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm),1 x blind stopper M20 x 1.5; 1 x blind stopperM16 x 1 .5 or optionally availab

Page 54

- Inspection window Polyester foilVoltage supplyOperating voltage- Non-Ex instrument 14 … 36 V DC- EEx-ia instrument 14 … 30 V DC- EEx-d-ia instrument

Page 55

Overvoltage category IIIProtection class IIFunctional safety (SIL)Functional safety is already activated on instruments with SIL qualification ex facto

Page 56

2.5 Safetylabel on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the l

Page 57

10.2 DimensionsThe following dimensional drawings represent only an extract of thepossible versions. Detailed dimensional drawings can be downloadedon

Page 58

Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm (4.72")~ 105 mm (4.13")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.31

Page 59

VEGAFLEX 62LG1½, 1½ NPT22 mm(0.87")73 mm(2.87")150 mm (5.91")53 mm(2.09")ø 16 mm(0.63")12 mm(0.47")ø 54 mm(2.13")ø

Page 60 - 10.2 Dim

10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 61

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 62

3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAFLEX 62 level sensorl Documentation- this operating instructions manual- Saf

Page 63 - 10.4 Trademark

123Fig. 1: VEGAFLEX 62 incable version with plastic housing1 Housing cover with integrated indicating and adjustment module (optional)2 Housing with e

Page 64 - ISO 9001

Two-wire electronics 4 … 20 mA/HART for power supply andmeasured value transmission over the same cable.The supply voltage range can differ depending o