Vega VEGABAR 17 User Manual

Browse online or download User Manual for Equipment Vega VEGABAR 17. VEGA VEGABAR 17 User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instruction

Operating InstructionsVEGABAR 17Document ID:27636Process pressure

Page 2 - Contents

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Page 3

Fig. 2: Mounting of VEGABAR 17VEGABAR 17 114 Mounting27636-EN-120531

Page 4 - 1 About this document

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 5 - 2 For your safety

Connect the cable screen on both ends to ground potential.If potential equalisation currents are expected, the connection on theprocessing side must b

Page 6

123Fig. 3: Loosen the pluginsert1 Cable gland2 Plug insert3 Plug housing4 Remove approx. 5 cm of the cable mantle, strip approx. 1 cminsulation from t

Page 7 - 3 Product description

1 Loosen the screw in the cover of the plug connector2 Open thecover and remove it3 Press the plug insert downwards4 Loosen the screws of the strain r

Page 8 - 3.3 Operation

8 Snap the plug insert into the plug housing and insert the sensorsealInformation:Note the correct arrangement, see illustration9 Tighten the screws o

Page 9

Wire colour SocketBrown 1White 2Blue 3Black 4123Fig. 9: Wiring plan cableoutlet1 brown (+) power supply and signal output2 green (-) power supply and

Page 10 - 4 Mounting

6 Setup6.1 Setup stepsAftermounting and electrical connection, VEGABAR 17 is ready foroperation.VEGABAR 17 delivers a current of 4 … 20 mA correspondi

Page 11 - 27636-EN-120531

123456Fig. 11: Open the instrument1 Plugconnector2 Plug seal3 Screwed ring4 Instrument plug5 Plug seal6 Housing3 Set zero in unpressurized status, che

Page 12 - 5 Connecting to power supply

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Page 13 - 5.2 Connection procedure

Proceed as follows:1 Screw onthe housing cover in connected status45Fig. 13: Adjustment of zeroand span1 zero (Z)2 span (S)2 Set zero in unpressurized

Page 14

7 Maintenance and fault rectification7.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.7.2 Remov

Page 15

Depending on the reason for the fault and the measures taken, thestepsdescribed in chapter "Set up" may have to be carried out again.7.3 Ins

Page 16 - 5.3 Wiring plan

8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 17

9 Supplement9.1 TechnicaldataGeneral dataParameter, pressure Gauge pressure, absolute pressure, vacuumMeasuring principle Piezoresistive/Thin film DMSC

Page 18 - 6.2 Recalibration

- Version for medium temperature < -30 °C(-22 °F)≤ 10 ms- Version for measuring ranges > 25 bar ≤ 10 ms- Version with front-flush diaphragm ≤ 10

Page 19

Nominal range Overload capacity, max.pressureOverloadcapacity, min.pressure0 … 25 bar/0 … 2500 kPa 50 bar/5000 kPa -1 bar/-100 kPa0 … 40 bar/0 … 4000

Page 20

Average temperature coefficient of the span typ. < 0.2 %/10 KLong-term stability (according to DIN 16086, DINV 19259-1 and IEC 60770-1)Long-term drif

Page 21 - 7.2 Remove interferences

- Version with plug connector or cableoutlet1000 gaccording to IEC 60068-2-27 (mechanicalshock)- Version with cooling element 400 g according to IEC 6

Page 22 - 7.3 Instrument repair

Interference resistance- HF 10 V/m- Burst 2 kVOtherprotective measures- Interpolation protection Available- Overvoltage protection up to 36 V DCApprov

Page 23 - 8 Dismounting

Supplementary documentationInformation:Supplementary documents appropriate to the ordered version comewith the delivery. You can find them listed in ch

Page 24 - 9 Supplement

9.2 DimensionsVEGABAR 17 - standard housingG1/4 ~116 mm (4.57 ")2 mm(0.08")13 mm(0.51")2 mmø 5 mm (0.20")ø 9,5 mm (0.37")SW27

Page 25

VEGABAR 17 - Standard housing (Ex version)SW27G1/4 G1/2 1/4NPT1/2NPTG1 10 mm(0.39")~136 mm (5.35 ")~136 mm (5.35")~143 mm (5.63 ")

Page 26

VEGABAR 17 - terminal housingSW27G1/4 G1/2 1/4NPT1/2NPTG1 20,5 mm(0.81")10 mm(0.39")~128 mm (5.04 ")~128 mm (5.04")~135 mm (5.31 &

Page 27

VEGABAR 17 - Cooling elements, plug, cable outletG1/2 G1 ~48 mm (1.89")~ 17,5 mm(0.69")27,5 mm(1.08")~ 17,5 mm(0.69")13,5 mm(0.53&

Page 28

34 VEGABAR 179 Supplement27636-EN-120531

Page 29

VEGABAR 17 359 Supplement27636-EN-120531

Page 30 - 9.2 Dimensions

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 31 - - Standard ho

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 32 - - terminal housing

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 33

2.5 Safety labelon the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThe device fulfills the le

Page 34

3 Product description3.1 StructureThe scope of delivery encompasses:l VEGABAR 17 process pressure transmitterl Depending on the version, with plug con

Page 35

3.2 Principle ofoperationVEGABAR 17 is a pressure transmitter for measurement of gaugepressure, absolute pressure or vacuum. Measured products aregase

Page 36 - ISO 9001

l Dry and dust freel Not exposed to corrosive medial Protected against solar radiationl Avoiding mechanical shock and vibrationl Storage and transport