Operating InstructionsVEGAWAVE 62- transistor (NPN/PNP)Document ID:32253Vibration
4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and
The max. permissible pressure is specified in chapter "Technical data"or on the type label of the sensor.The vibrating level switch is a meas
dd6123Fig. 4: Filling in the centre, emptying laterally1 VEGAWAVE 622 Discharge opening3 Filling openingThe vibrating element should protrude into the
Fig. 5: Inflowing mediumTo minimise flow resistance caused by the tuning fork, VEGAWAVE62 should be mounted in such a way that the surfaces of the blade
In applications su ch as grit chambers or settling basins for coarsesediments, the vibrating element must be protected against damagewith a suitable b
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
5 Lift the opening levers of the terminals with a screwdriver (seefollowing illustration)Fig. 8: Connection steps 5 and 66 Insert the wire ends into t
14442 3Fig. 9: Material versions, single chamber housing1 Plastic (not with EEx d)2 Aluminium3 Stainless steel (not with EEx d)4 Filter element for pr
1 2 3 4Fig. 11: NPN action1 2 3 4Fig. 12: PNP action5.4 Wiring plan - version IP 66/IP 68, 1 bar12345Fig. 13: Wire assignment connection cable. The nu
6 Set up6.1 General informationThe figures in brackets refer to the following illustrations.On the electronics module you will find the following indica
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
By default, the potentiometer of VEGAWAVE 62 is set to the right stop(> 0.02 g/cm³ or 0.0008 lbs/in³). In case of very light-weight solids, turnthe
Level Switching status Control lampFailure of the sup-ply voltage(min./max. mode)any openMalfunction any openflashes redVEGAWAVE 62 • - transistor (NPN
7 Maintenance and fault rectification7.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.7.2 Remov
Error Cause RectificationWrong mode selected Set the correct mode on the mode switch (overflowprotection, dry run protection). Wiring should be carriedo
6 Pull out the old electronics module7 Compare the new electronics module with the old one. The typelabel of the electronics module must correspond to
8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L- Process
Sensor length (L) - suspension cable FEP(-40 … +150 °C/-40 … +302 °F)0.6 … 80 m (1.969 … 262.47 ft)Output variableOutput Floating transistor output, p
Electromechanical data - version IP 66/IP 68 (1 bar)Cable entry- Single chamber housing l 1 x IP 68 cable gland M20 x 1.5; 1 x blindstopper M20 x 1.5o
That's why the associated approval documents have to be noted with these instruments. They arepart of the delivery or can be downloaded underwww.
9 Supplement9.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .269.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . .
9.2 DimensionsHousing in protection IP 66/IP 67 and IP 66/IP 68; 0.2 bar3214~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5/½ NPT~ 59
150mm (5 29/32")L22mm(55/64")40mm(1 37/64")33mm(1 19/64")G1½Aø 43mm (1 11/16")ø 11mm (7/16")ø 43mm (1 11/16")160mm
150mm (5 29/32") L 22mm (55/64") 40mm (1 37/64") 33mm (1 19/64") G1½A ø 43mm (1 11/16") ø 43mm (1 11/16") 160mm (6 19/64
9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only i
34 VEGAWAVE 62 • - transistor (NPN/PNP)9 Supplement32253-EN-120418
VEGAWAVE 62 • - transistor (NPN/PNP) 359 Supplement32253-EN-120418
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the
3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAWAVE 62 point level switchl Documentation- this operating instructions manua
l SIL identification (with SIL rating ex works)With the serial number, you can access the delivery data of theinstrument viawww.vega.com, "VEGA To
3.3 OperationWith the factory setting, products with a density of > 0.02 g/cm³(0.0008 lbs/in³) can be measured. The instrument can also be adaptedt