Operating InstructionsVEGAFLEX 66-20 … +250 °CProfibus PADocument ID:34171Guided Microwave
The delivery must be checked for completeness and possible transitdamage immediately at receipt. Ascertained transit damage orconcealed defects must b
4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and
Fig. 2: Measuresagainst moisture penetrationThe reference plane for the measuring range of the sensors is thesealing surface of the thread or flange.Ke
keep in mind that measurement down to the tip of the probe is notpossible. The exact value of the min. distance (lower dead band) isstated in chapter
Excessive system vibration or shocks, e.g. caused by agitators orturbulence in the vessel (e.g. from fluidisation) can cause the coaxprobe of VEGAFLEX
1Fig. 5: Positionof the spacer1 SpacerNote:Measurement in a standpipe is not recommended for very adhesiveproducts.If there is a danger of the probe t
1 2 Fig. 6: Vesselwith temperature insulation1 Temperature insulation2 Ambient temperature on the housing16 VEGAFLEX 66 • Profibus PA4 Mounting34171-EN
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
Insystems with potential equalisation, connect the cable screendirectly to ground potential at the power supply unit, in the connectionbox and at the
7 Insertthe wire ends into the open terminals according to the wiringplanFig. 7: Connectionsteps 6 and 78 Press down the opening levers of the termina
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
I²CDisplay1 2 5 6 7 83412Fig. 8: Electronicsand connection compartment with single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Sp
132Display1 2 5 6 7 8I²CFig. 10: Electronicscompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c
I2C11 2Fig. 12: Wiringplan with double chamber housing1 Voltage supply/Signal output5.5 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 13: Wireassig
6 Setup with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 14: Insertindicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating and adjustmentmodule for continuous meas
6.3 Adjustment system1.1231Fig. 15: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 SetupstepsAfter VEGAFLEX 66 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30secon
Start your parameter adjustment with the following menu items of thebasic adjustment:Proceed as follows:1 Move from the measured value display to the
Eachproduct has different reflective properties. In addition, there arevarious interfering factors which have to be taken into account:agitated product
percentage and vessel volume. Byactivating the appropriate curve,the volume percentage of the vessel is displayed correctly. If thevolume should not b
8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .388.2 Rectify malfunctions . . . . . .
Gating out of false sig nalsChange now?Proceed as follows:1 Move from the measured value display to the main menu bypushing [OK].2 Select the menu ite
Copy sensor dataCopy sensor data?Basic adjustmentIf the function "Reset" is carried out, the sensor resets the values of thefollowing menu i
Additional adjustment and diagnosis options such as e.g. scaling,simulation or trend curve presentation are shown in the following menuschematic. You
6.5 MenuschematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Sensor address0001.2Min. adjustment0.00 %=10.000 m(d)8.000 m(d)1.3M
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Sensor5 mRod4.2ApplicationLiquidStandard(DK ≥ 2)4.3Gating out of false sig nalsChange now?4.4
6.6 Savingthe parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwar
7 Setup with PACTware and other adjustmentprograms7.1 Connecting the PC312Fig. 16: Connectionof the PC via VEGACONNECT directly to the sensor1 USB cab
Necessary components:l VEGAFLEX 66l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustmen
8 Maintenance and fault rectification8.1 MaintenanceWhen used as directed in normal operation, VEGAFLEX 66 iscompletely maintenance free.8.2 Rectify ma
Error Cause RemovalIn Simatic S7 themeasuredvalue isalways presentedas 0Only four bytesare consistentlyloaded in the PLCUse function component SFC 14
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
Statusaccor-ding to NE 107Error code Text message Cause/RectificationE017 Adjustment span too small Adjustment not within the specifica-tion. Carry out
l FX-E.60PX (X = withoutapprovals)l FX-E.60PA (A = approvals CA, DA according to product list)l FX-E.60PC (C = approvals XM, CX, CM, CK, GX according
l Print and fill out one form per instrumentl Clean the instrument and pack it damage-proofl Attach the completed form and, if need be, also a safety d
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - coax version 316L a
- Rod: ø 6 mm (0.236 in) approx. 220 g/m (2.365 oz/ft)- Cable: ø 2 mm (0.079 in) approx. 20 g/m (0.215 oz/ft)- Cable: ø 4 mm (0.157 in) approx. 80 g/m
24315Fig. 18: Measuringrange of VEGAFLEX 66 - coax version1 Reference plane2 Probe length3 Measuring range4 Upper dead band (see diagrams under Accura
2431245315Fig. 19: Measuringranges of the VEGAFLEX 66 - rod and cable version1 Reference plane2 Probe length3 Measuring range (default setting refers
- Relative humidity 45 … 75 %- Air pressure +860 … +1060 mbar/+86 … +106 kPa(+12.5 … +15.4 psig)Installation reference conditions- Min. distance to in
L0-3mm (-0.118")3mm (0.118")15mm(0.591")-10mm (-0.394")0,25 m(9.843")0,08 m(3.15")0,02 m(0.787")1Fig. 20: Devia
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
L0-3mm (-0.118")3mm (0.118")15mm(0.591")-15mm (-0.591")0,25 m(9.843")0,08 m(3.149")0,25 m(9.843")1Fig. 22: Devi
L0-3mm (-0.118")3mm (0.118")-50mm (1.969")5mm (0.197")0,15 m (5.906")0,03 m (1.181")0,02 m(0.787")1Fig. 24: Dev
Process conditionsProcess pressure -1 … +100 bar/-100 … +10000 kPa (--14.5 … +1450 psig), depending on the processfittingProcess temperature -20 … +250
l 1 xclosing cap ½ NPT, 1 x blind stopper½ NPT , 1 x blind stopper M16 x 1.5 oroptionally 1 x plug M12 x 1 for VEGADIS 61or:l 1 x plug (depending on t
Voltage supplyOperating voltage- Non-Ex instrument 9 … 32 V DC- EEx-ia instrument 9 … 24 V DC- EEx-d instrument 16 … 32 V DCOperating voltage with lig
10.2 Profibus PAInstrument master fileThe instrument master file (GSD) contains the characteristic data of the Profibus PA instrument.These data are, e.g.
Module of the PA sensorsFor the cyclic data traffic, VEGAFLEX 66 provides the following modules:l AI (PA-OUT)- PA-OUT value of the FB1 after scalingl Ad
l Free PlaceByte-No.1 2 3 4 5StatusStatus(FB1)IEEE-754-Floating point valuePA- OUT(FB1)FormatValueDataformat of the output signalByte4Byte3Byte2Byte1B
StatuscodeDescriptionaccording to Pro-fibus standardPossible cause0x0C bad - sensor failure l Hardware errorl Converter errorl Leakage pulse errorl Tri
10.3 DimensionsThe following dimensional drawings represent only an extract of thepossible versions. Detailed dimensional drawings can be downloadedon
2.5 Safetylabel on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the l
Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm (4.72")~ 105 mm (4.13")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.31
VEGAFLEX 66 - cable, rodversion (-20 … +250 °C/-4 … +482 °F)SW41 (G1 / 1 NPT)SW46 (G1½ / 1½ NPT)G1 / 1 NPT,G1½ / 1½ NPTL140 mm (5.51")20 mm (0.79
VEGAFLEX 66 - coax version (-20 … +250 °C/-4 … +482 °F)LG¾ / ¾ NPT,G1 / 1 NPT,G1½ / 1½ NPT140 mm (5.51")20 mm (0.79")27 mm (1.06")ø 21,
10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAFLEX 66 level sensorl Documentation- this operating instructions manual- Ope
123Fig. 1: VEGAFLEX 66 incable version with plastic housing1 Housing cover with integrated indicating and adjustment module (optional)2 Housing with e
Power supply via the Profibus DP/PA segment coupler or VEGALOG571 EP cards. A two-wire cable according to Profibus specificationserves a s carrier of bot