Operating InstructionsVEGAVIB 61- Relay (DPDT)Document ID:29265Vibration

Page 2 - Contents

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Page 3

The max. permissible pressure is specified in chapter "Technical data"or on the type label of the sensor.The vibrating level switch is a meas

Page 4 - 1 About this document

In silos for bulk solids, material cones can form and change theswitching point. Please keep this in mind when installing the sensor inthe vessel. We

Page 5 - 2 For your safety

dd6123Fig. 5: Filling in the centre, emptying laterally1 VEGAVIB 612 Discharge opening3 Filling openingTo achieve a very precise switching point, you

Page 6 - 2.7 SIL conformity

20° Fig. 6: Horizontal installationIf VEGAVIB 61 is mounted in the filling stream, unwanted falsemeasurement signals can be generated. For this reason,

Page 7 - 3 Product description

VEGAVIB 61 • - Relay (DPDT) 154 Mounting29265-EN-120418

Page 8 - 3.3 Operation

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 9 - 3.4 Storage and transport

5 Lift the opening levers of the terminals with a screwdriver (seefollowing illustration)Fig. 8: Connection steps 5 and 66 Insert the wire ends into t

Page 10 - 4 Mounting

14442 3Fig. 9: Material versions, single chamber housing1 Plastic (not with EEx d)2 Aluminium3 Stainless steel (not with EEx d)4 Filter element for pr

Page 11 - 29265-EN-120418

6 Set up6.1 General informationThe figures in brackets refer to the following illustrations.On the electronics module you will find the following indica

Page 12

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13

As a default setting, the potentiometer of VEGAVIB 61 is set to thecomplete right position (> 0.3 g/cm³/0.011 lbs/in³). In very light solidsyou hav

Page 14

Level Switching status Control lampMode min.Dry run protection53 4(8)(6) (7)Relay deenergized RedFailure of the sup-ply voltage(min./max. mode)any53 4

Page 15

7 Maintenance and fault rectification7.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.7.2 Remov

Page 16 - 5 Connecting to power supply

Error Cause RectificationWrong mode selected Set the correct mode on the mode switch (overflowprotection, dry run protection). Wiring should be carriedo

Page 17

6 Pull out the old electronics module7 Compare the new electronics module with the old one. The typelabel of the electronics module must correspond to

Page 18

8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 19 - 6 Set up

9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L- Process

Page 20 - 6.3 Function chart

- Max. 3 A AC, 1 A DCBreaking capacity- Min. 50 mW- Max. 750 VA AC, 54 W DCIf inductive loads or stronger currents are switchedthrough, the gold plati

Page 21

123-50°C(-58°F)50°C(122°F)40°C(104°F)-40°C(-40°F)80°C(176°F)0°C(32°F)100°C(212°F)150°C(302°F)200°C(392°F)250°C(482°F)Fig. 27: Ambient temperature - Pr

Page 22 - 7.2 Remove interferences

20 … 253 V AC, 50/60 Hz, 20 … 72 V DC (atU >60 V DC, the ambient temperature can be max.50 °C/122 °F)Power consumption 1 … 8 VA (AC), approximately

Page 23

9.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Supplementary documentationInformation:Supplementary documents appropria

Page 24 - 7.4 Instrument repair

9.2 DimensionsVEGAVIB 61 - housing3214~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5/½ NPT~ 59 mm(2.32")ø 80 mm(3.15")112

Page 25 - 8 Dismounting

25 mm(0.98")20 mm(0.79")160 mm (6.3")125 mm (4.92")ø16 mm (0.63")ø 29 mm (1.14")G1AFig. 29: VEGAVIB 61, threaded version

Page 26 - 9 Supplement

33 mm(1.30")22 mm(0.87")162 mm (6.38")ø16mm (0.63")G1½Aø 29 mm (1.14")125 mm (4.92")Fig. 30: VEGAVIB 61, threaded versi

Page 27

ø 34 mm(1 11/32")178 mm (7 1/64")Fig. 31: Temperature adapterVEGAVIB 61 • - Relay (DPDT) 339 Supplement29265-EN-120418

Page 28

9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only i

Page 29

VEGAVIB 61 • - Relay (DPDT) 359 Supplement29265-EN-120418

Page 30 - 112 mm (4.41")

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 31

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 32

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 33

2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the

Page 34 - 9.4 Trademark

3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAVIB 61 point level switchl Documentation- this operating instructions manual

Page 35

3.2 Principle of operationVEGAVIB 61 is a point level sensor with vibrating rod for leveldetection.It is designed for industrial use in all areas of p

Page 36 - ISO 9001

l Signal lamp for indication of the switching condition (green/red)l Potentiometer for adaptation to the product densityl Mode switch for selecting th