Operating InstructionsVEGAVIB 61- Relay (DPDT)Document ID:29265Vibration
4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and
The max. permissible pressure is specified in chapter "Technical data"or on the type label of the sensor.The vibrating level switch is a meas
In silos for bulk solids, material cones can form and change theswitching point. Please keep this in mind when installing the sensor inthe vessel. We
dd6123Fig. 5: Filling in the centre, emptying laterally1 VEGAVIB 612 Discharge opening3 Filling openingTo achieve a very precise switching point, you
20° Fig. 6: Horizontal installationIf VEGAVIB 61 is mounted in the filling stream, unwanted falsemeasurement signals can be generated. For this reason,
VEGAVIB 61 • - Relay (DPDT) 154 Mounting29265-EN-120418
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
5 Lift the opening levers of the terminals with a screwdriver (seefollowing illustration)Fig. 8: Connection steps 5 and 66 Insert the wire ends into t
14442 3Fig. 9: Material versions, single chamber housing1 Plastic (not with EEx d)2 Aluminium3 Stainless steel (not with EEx d)4 Filter element for pr
6 Set up6.1 General informationThe figures in brackets refer to the following illustrations.On the electronics module you will find the following indica
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
As a default setting, the potentiometer of VEGAVIB 61 is set to thecomplete right position (> 0.3 g/cm³/0.011 lbs/in³). In very light solidsyou hav
Level Switching status Control lampMode min.Dry run protection53 4(8)(6) (7)Relay deenergized RedFailure of the sup-ply voltage(min./max. mode)any53 4
7 Maintenance and fault rectification7.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.7.2 Remov
Error Cause RectificationWrong mode selected Set the correct mode on the mode switch (overflowprotection, dry run protection). Wiring should be carriedo
6 Pull out the old electronics module7 Compare the new electronics module with the old one. The typelabel of the electronics module must correspond to
8 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
9 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - thread 316L- Process
- Max. 3 A AC, 1 A DCBreaking capacity- Min. 50 mW- Max. 750 VA AC, 54 W DCIf inductive loads or stronger currents are switchedthrough, the gold plati
123-50°C(-58°F)50°C(122°F)40°C(104°F)-40°C(-40°F)80°C(176°F)0°C(32°F)100°C(212°F)150°C(302°F)200°C(392°F)250°C(482°F)Fig. 27: Ambient temperature - Pr
20 … 253 V AC, 50/60 Hz, 20 … 72 V DC (atU >60 V DC, the ambient temperature can be max.50 °C/122 °F)Power consumption 1 … 8 VA (AC), approximately
9.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30Supplementary documentationInformation:Supplementary documents appropria
9.2 DimensionsVEGAVIB 61 - housing3214~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5/½ NPT~ 59 mm(2.32")ø 80 mm(3.15")112
25 mm(0.98")20 mm(0.79")160 mm (6.3")125 mm (4.92")ø16 mm (0.63")ø 29 mm (1.14")G1AFig. 29: VEGAVIB 61, threaded version
33 mm(1.30")22 mm(0.87")162 mm (6.38")ø16mm (0.63")G1½Aø 29 mm (1.14")125 mm (4.92")Fig. 30: VEGAVIB 61, threaded versi
ø 34 mm(1 11/32")178 mm (7 1/64")Fig. 31: Temperature adapterVEGAVIB 61 • - Relay (DPDT) 339 Supplement29265-EN-120418
9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only i
VEGAVIB 61 • - Relay (DPDT) 359 Supplement29265-EN-120418
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the
3 Product description3.1 StructureThe scope of delivery encompasses:l VEGAVIB 61 point level switchl Documentation- this operating instructions manual
3.2 Principle of operationVEGAVIB 61 is a point level sensor with vibrating rod for leveldetection.It is designed for industrial use in all areas of p
l Signal lamp for indication of the switching condition (green/red)l Potentiometer for adaptation to the product densityl Mode switch for selecting th