Vega VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four- User Manual

Browse online or download User Manual for Equipment Vega VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four-. VEGA VEGAPULS 62 (≥ 2.0.0 - ≤ 3.8) 4 … 20 mA_HART four-wire User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instruction

Operating InstructionsVEGAPULS 624 … 20 mA/HART four-wireRadar

Page 2 - Contents

The version with "Flangeand horn antenna with ø 48 … 95 mm(1.89 … 3.74 in)" is particularly suitable for storage tanks and processvessels, f

Page 3

The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foilis also used. Di

Page 4 - 1 About this document

4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i

Page 5 - 2 For your safety

1 32100%0%4Fig. 3: Measuring range (operating range), max. measuringdistance andreference plane1 full2 empty (max. measuring distance)3 Measuring rang

Page 6 - 2.7 Fulfillment o

You can find the specifications in chapter "Technical data" in the or onthe type label.4.2 Mounting preparations - Horn antennaInformation:Thi

Page 7

Note:VEGAPULS 62 with rinsing air connection or antenna extension isprovided with a notch on the antenna socket. This notch mustcorrespond to the mark

Page 8 - 3 Product description

7 Check, if the O-ring sealis available on the connection piece and ifit is not damaged.Note:A damaged O-ring seal must be replaced: FKM (Viton) artic

Page 9 - 3.2 Principle of operation

If you cannot keep this distance you should carry out a false echostoragebefore setup. This applies mainly if buildup on the vessel wallis expected. I

Page 10 - 3.3 Operation

Do not mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the inflowing product.Fig. 9: Inflowing li

Page 11 - 28440-EN-090305

dhmax.d1½"50 mm/2"80 mm/3"100 mm/4"150 mm/6"200 mm250 mm300 mm500 mm800 mmhmax.Fig. 11: Deviating socket dimensionsTip:VEGAPU

Page 12 - 4 Mounting

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Page 13

Fig. 13: Cover smooth profileswith deflectorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motio

Page 14

Note:Measurementin a standpipe is not recommended for very adhesiveproducts.Surge or bypass tubes must extend all the way down to the requestedmin. le

Page 15

100%0%1> 300 mmFig. 16: VEGAPULS 62 in a bypasstube. The polarisation marking on theprocess fitting must be in one plane with the tube holes or the

Page 16 - 4.4 Mounting instructions

1234Fig. 17: Polarisation level with flangeversion, view from top on the sensor andbypass tube. The sensor housing is not shown.1 Position of the polar

Page 17 - > 200 mm

3 ... 4 hmax≥ 50 mm90°231hmaxdmin≥ 2 mm x hmax90°4Fig. 18: Flow measurement withrectangular flume: d = min. distance of thesensor; hmax. = max. filling

Page 18

23 ... 4 x hmax90°hmaxd1BFig. 19: Flowmeasurementwith Khafagi-Venturi flume: d = Min. distanceof thesensor; hmax. = max. filling of the flume; B = bigges

Page 19

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 20

If screened cable is necessary, connect the cable screen on both endsto ground potential. In the sensor, the screen must be connecteddirectly to the i

Page 21

12 Screw the housing cover onTheelectrical connection is finished.Fig. 20: Connection steps 5 and 65.3 Wiringplan, double chamber housingThe following

Page 22 - > 300 mm

132Display1 2 5 6 7 8I²CFig. 22: Electronics compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 23

7.4 Saving theparameter adjustment data. . . . . . . . . . . .458 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . .

Page 24

Information:Keep inmind that the indicating and adjustment module must only beused in the electronics compartment.4 ... 20 mAPE/ L/ NL1 NGND1 21 2344.

Page 25

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 26 - 5 Connecting to power supply

Fig. 25: Insert indicating andadjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous mea

Page 27 - 5.2 Connection procedure

6.3 Adjustment system1.1231Fig. 26: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 28 - 5.3 Wiring

6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You w

Page 29

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basic adjustment" with [->] and confirm with[OK]. Now the menu item

Page 30 - 4...20mA IS

LiquidInformation:With VEGAPULS 62 with electronics version "Increased safety","Solid" is preset as factory setting. However, the

Page 31 - 6.1 Short description

and vessel volume. By activating the appropriate curve, the volumepercentage of the vessel is displayed correctly. If the volume shouldnot be displaye

Page 32

Note:Since with the function "Quick level change > 1 m/min." the generationof an average value of the signal processing is considerably r

Page 33 - - Select editing position

Menu item Reset valueMin. adjustment 30 m(d)(VEGAPULS 61, 63, 65, 67)35 m(d) (VEGAPULS 62, 66)70 m(d) (VEGAPULS 68)Medium LiquidVessel form not knownD

Page 34 - Address 0

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35

6.5 Menu schematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor sel ection

Page 36 - Storage tank

3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor statusOK3.3Curve selectionEcho curve▼3.4Echo curvePresenta

Page 37

6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa

Page 38 - Copy sensor data?

7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 27: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl

Page 39

Necessary components:l VEGAPULS 62l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system152 43OPENTWISTUSBLOCKF

Page 40 - 6.5 Menu schem

Note:Keep in mindthat for setup of VEGAPULS 62, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are provided in the

Page 41

8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte

Page 42 - 6.6 Saving the pa

? Current signal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return instrument for repairIn Ex applic

Page 43 - 7 Setup with PACTware and

Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q

Page 44

l Please ask the agency serving you for the address of your returnshipment. Youcan find the respective agency on our websitewww.vega.com under: "C

Page 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46 - ? 4 … 20 mA signal missing

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 47 - ? E041, E042, E043

10 Supplement10.1 TechnicaldataGeneral data316L corresponds to 1.4404 or 1.4435Materials, non-wetted parts- Housing Aluminium die-casting powder coate

Page 48 - 8.5 Instrument repair

Fulfilled NAMUR recommendations NE 43Input variableMeasured value distance between process fitting and product sur-faceMin. distance from antenna end 50

Page 49

- Average power < 5 µW- Averagepower with 1 m distance < 200 nW/cm2Max. emitted HF power of the antenna system - Version with increased sensitiv

Page 50 - 9 Dismounting

2,0 m (6.562 ft)30 m (98.43 ft)40 mm (1.574 in)3 mm (0.116 in)- 3 mm (- 0.116 in)- 40 mm (- 1.574 in)0Fig. 32: Deviation VEGAPULS 62 with parabolic an

Page 51 - 10 Supplement

Gas phase Temperature 1 bar/14.5 psig 10 bar/145 psig 50 bar/725 psigAir/Nitrogen 20 °C/68 °F 0.00 % 0.22 % 1.2 %Air/Nitrogen 200 °C/392 °F 0.00 % 0.1

Page 52

0,10,01,02,03,04,05,06,00,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2,0(bar)(m3/h)Fig. 34: Air quantity diagramThread G⅛ A

Page 53

Indicating and adjustment moduleVoltage supply and data transmission through the sensorIndication LC display in dot matrixAdjustment elements 4 keysPr

Page 54

10.2 DimensionsHousingø84mm~ 27/")120mm (4 23/32")* 129mm (5 5/64")5/16")M20x1,5/½ NPTM12xFig. 35: Double chamber housingof Alumin

Page 55

VEGAPULS 62 - horn antennain threaded versionmm inch 38 mm (1.50")22 mm (0.87")22 mm (0.87")118 mm (4.65")SW 46 mm(1.81")8.50

Page 56

During t he entire duration of use, the useris obliged to determine thecompliance of the required occupational safety measures with thecurrent valid r

Page 57

VEGAPULS 62 - horn antennain threaded version with purging air connection38 mm (1 1/2")22 mm(0.87")22 mm (0.87")118 mm (4.67")xyxy

Page 58 - 10.2 Dimensions

VEGAPULS 62 - horn antennain threaded version with antenna extensionmm inch 38 mm (1.50")22 mm (0.87")22 mm (0.87")118 mm (4.65")S

Page 59

VEGAPULS 62 - horn antennain flange version4xø0.75"4xø0.75"8xø0.75"8xø0.87"8xø0.88"4.75"4.92"6.30" 2.95"3.

Page 60

VEGAPULS 62 - horn antennain flange version with purging air connectionDkxdby12140mm (5.51")82,5 mm(3.25")4xø0.75"4xø0.75"8xø0.75&q

Page 61

VEGAPULS 62 - horn antennaand swivelling holdermm inch 120 mm (4.72")20 mm(0.79")20 mm(0.79")d 3.94" ø 1.58"ø 1.89"ø 2.9

Page 62

VEGAPULS 62 - horn antenna, swivelling holder and purging air connectionmminch120 mm (4.72")47,5 mm(1.87")20 mm(0.79")12DmmDINASMEb kdD

Page 63

VEGAPULS 62 - parabolic antenna in threaded version138 mm (5.43")ø 244 mm (9.61")SW 46 mm(1.81")22 mm (0.87")118 mm (4.65")38

Page 64

VEGAPULS 62 - parabolic antenna in flange versionD mm b k d DN 50 PN 40 165 20 125 4xø18 DN 80 PN 40 200 24 160 8xø18 DN 100 PN 16 220 20

Page 65

VEGAPULS 62 - parabolic antenna and swivelling holderd120 mm (4.72")130 mm (5.12")ø 243 mm (9.57")DmmDINASMEb kdDN 50 165 11,5 125 4x ø

Page 66

VEGAPULS 62 - parabolic antenna and swivelling holder with purging air connectiond47,5 mm(1.87")130 mm (5.12")ø 243 mm (9.57")120 mm (4

Page 67

l The device must be insensitive to interfering immissions, includingthose that may cause undesirable operating conditions.The instrument is designed

Page 68

10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 69

VEGAPULS 62 • 4 … 20 mA/HART four-wire 7110 Supplement28440-EN-090305

Page 70 - 10.4 Trademark

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 71

3 Product description3.1 ConfigurationThe VEGAPULS 62 radar sensor is available in two electronicsversions:l Standard electronics type PS60KVl Electron

Page 72 - ISO 9001

123Fig. 1: VEGAPULS 62 - threaded version with Aludouble chamber housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3