Operating InstructionsVEGAPULS 624 … 20 mA/HART four-wireRadar
The version with "Flangeand horn antenna with ø 48 … 95 mm(1.89 … 3.74 in)" is particularly suitable for storage tanks and processvessels, f
The packaging of standard instruments consists of environment-friendly, recyclable cardboard. For special versions, PE foam or PE foilis also used. Di
4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i
1 32100%0%4Fig. 3: Measuring range (operating range), max. measuringdistance andreference plane1 full2 empty (max. measuring distance)3 Measuring rang
You can find the specifications in chapter "Technical data" in the or onthe type label.4.2 Mounting preparations - Horn antennaInformation:Thi
Note:VEGAPULS 62 with rinsing air connection or antenna extension isprovided with a notch on the antenna socket. This notch mustcorrespond to the mark
7 Check, if the O-ring sealis available on the connection piece and ifit is not damaged.Note:A damaged O-ring seal must be replaced: FKM (Viton) artic
If you cannot keep this distance you should carry out a false echostoragebefore setup. This applies mainly if buildup on the vessel wallis expected. I
Do not mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the inflowing product.Fig. 9: Inflowing li
dhmax.d1½"50 mm/2"80 mm/3"100 mm/4"150 mm/6"200 mm250 mm300 mm500 mm800 mmhmax.Fig. 11: Deviating socket dimensionsTip:VEGAPU
Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .
Fig. 13: Cover smooth profileswith deflectorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motio
Note:Measurementin a standpipe is not recommended for very adhesiveproducts.Surge or bypass tubes must extend all the way down to the requestedmin. le
100%0%1> 300 mmFig. 16: VEGAPULS 62 in a bypasstube. The polarisation marking on theprocess fitting must be in one plane with the tube holes or the
1234Fig. 17: Polarisation level with flangeversion, view from top on the sensor andbypass tube. The sensor housing is not shown.1 Position of the polar
3 ... 4 hmax≥ 50 mm90°231hmaxdmin≥ 2 mm x hmax90°4Fig. 18: Flow measurement withrectangular flume: d = min. distance of thesensor; hmax. = max. filling
23 ... 4 x hmax90°hmaxd1BFig. 19: Flowmeasurementwith Khafagi-Venturi flume: d = Min. distanceof thesensor; hmax. = max. filling of the flume; B = bigges
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
If screened cable is necessary, connect the cable screen on both endsto ground potential. In the sensor, the screen must be connecteddirectly to the i
12 Screw the housing cover onTheelectrical connection is finished.Fig. 20: Connection steps 5 and 65.3 Wiringplan, double chamber housingThe following
132Display1 2 5 6 7 8I²CFig. 22: Electronics compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c
7.4 Saving theparameter adjustment data. . . . . . . . . . . .458 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . .
Information:Keep inmind that the indicating and adjustment module must only beused in the electronics compartment.4 ... 20 mAPE/ L/ NL1 NGND1 21 2344.
6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 25: Insert indicating andadjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous mea
6.3 Adjustment system1.1231Fig. 26: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You w
▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basic adjustment" with [->] and confirm with[OK]. Now the menu item
LiquidInformation:With VEGAPULS 62 with electronics version "Increased safety","Solid" is preset as factory setting. However, the
and vessel volume. By activating the appropriate curve, the volumepercentage of the vessel is displayed correctly. If the volume shouldnot be displaye
Note:Since with the function "Quick level change > 1 m/min." the generationof an average value of the signal processing is considerably r
Menu item Reset valueMin. adjustment 30 m(d)(VEGAPULS 61, 63, 65, 67)35 m(d) (VEGAPULS 62, 66)70 m(d) (VEGAPULS 68)Medium LiquidVessel form not knownD
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
6.5 Menu schematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor sel ection
3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor statusOK3.3Curve selectionEcho curve▼3.4Echo curvePresenta
6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa
7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 27: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl
Necessary components:l VEGAPULS 62l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system152 43OPENTWISTUSBLOCKF
Note:Keep in mindthat for setup of VEGAPULS 62, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are provided in the
8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte
? Current signal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return instrument for repairIn Ex applic
Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q
l Please ask the agency serving you for the address of your returnshipment. Youcan find the respective agency on our websitewww.vega.com under: "C
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 TechnicaldataGeneral data316L corresponds to 1.4404 or 1.4435Materials, non-wetted parts- Housing Aluminium die-casting powder coate
Fulfilled NAMUR recommendations NE 43Input variableMeasured value distance between process fitting and product sur-faceMin. distance from antenna end 50
- Average power < 5 µW- Averagepower with 1 m distance < 200 nW/cm2Max. emitted HF power of the antenna system - Version with increased sensitiv
2,0 m (6.562 ft)30 m (98.43 ft)40 mm (1.574 in)3 mm (0.116 in)- 3 mm (- 0.116 in)- 40 mm (- 1.574 in)0Fig. 32: Deviation VEGAPULS 62 with parabolic an
Gas phase Temperature 1 bar/14.5 psig 10 bar/145 psig 50 bar/725 psigAir/Nitrogen 20 °C/68 °F 0.00 % 0.22 % 1.2 %Air/Nitrogen 200 °C/392 °F 0.00 % 0.1
0,10,01,02,03,04,05,06,00,2 0,3 0,4 0,5 0,6 0,7 0,8 0,9 1,0 1,1 1,2 1,3 1,4 1,5 1,6 1,7 1,8 1,9 2,0(bar)(m3/h)Fig. 34: Air quantity diagramThread G⅛ A
Indicating and adjustment moduleVoltage supply and data transmission through the sensorIndication LC display in dot matrixAdjustment elements 4 keysPr
10.2 DimensionsHousingø84mm~ 27/")120mm (4 23/32")* 129mm (5 5/64")5/16")M20x1,5/½ NPTM12xFig. 35: Double chamber housingof Alumin
VEGAPULS 62 - horn antennain threaded versionmm inch 38 mm (1.50")22 mm (0.87")22 mm (0.87")118 mm (4.65")SW 46 mm(1.81")8.50
During t he entire duration of use, the useris obliged to determine thecompliance of the required occupational safety measures with thecurrent valid r
VEGAPULS 62 - horn antennain threaded version with purging air connection38 mm (1 1/2")22 mm(0.87")22 mm (0.87")118 mm (4.67")xyxy
VEGAPULS 62 - horn antennain threaded version with antenna extensionmm inch 38 mm (1.50")22 mm (0.87")22 mm (0.87")118 mm (4.65")S
VEGAPULS 62 - horn antennain flange version4xø0.75"4xø0.75"8xø0.75"8xø0.87"8xø0.88"4.75"4.92"6.30" 2.95"3.
VEGAPULS 62 - horn antennain flange version with purging air connectionDkxdby12140mm (5.51")82,5 mm(3.25")4xø0.75"4xø0.75"8xø0.75&q
VEGAPULS 62 - horn antennaand swivelling holdermm inch 120 mm (4.72")20 mm(0.79")20 mm(0.79")d 3.94" ø 1.58"ø 1.89"ø 2.9
VEGAPULS 62 - horn antenna, swivelling holder and purging air connectionmminch120 mm (4.72")47,5 mm(1.87")20 mm(0.79")12DmmDINASMEb kdD
VEGAPULS 62 - parabolic antenna in threaded version138 mm (5.43")ø 244 mm (9.61")SW 46 mm(1.81")22 mm (0.87")118 mm (4.65")38
VEGAPULS 62 - parabolic antenna in flange versionD mm b k d DN 50 PN 40 165 20 125 4xø18 DN 80 PN 40 200 24 160 8xø18 DN 100 PN 16 220 20
VEGAPULS 62 - parabolic antenna and swivelling holderd120 mm (4.72")130 mm (5.12")ø 243 mm (9.57")DmmDINASMEb kdDN 50 165 11,5 125 4x ø
VEGAPULS 62 - parabolic antenna and swivelling holder with purging air connectiond47,5 mm(1.87")130 mm (5.12")ø 243 mm (9.57")120 mm (4
l The device must be insensitive to interfering immissions, includingthose that may cause undesirable operating conditions.The instrument is designed
10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
VEGAPULS 62 • 4 … 20 mA/HART four-wire 7110 Supplement28440-EN-090305
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
3 Product description3.1 ConfigurationThe VEGAPULS 62 radar sensor is available in two electronicsversions:l Standard electronics type PS60KVl Electron
123Fig. 1: VEGAPULS 62 - threaded version with Aludouble chamber housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3