Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 614 … 20 mA/HART - four-wireDocument ID: 36500

Page 2 - Quick start

103 Product descriptionVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210113 Product description3.1 CongurationThe type label contains the most

Page 3

113 Product descriptionVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The instrument is available in two dierent electronics versions. Each v

Page 4 - Contents

123 Product descriptionVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Transport must be carried out under consideration of the notes on the tr

Page 5

133 Product descriptionVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The PLICSMOBILE T61 is an external GSM/GPRS radio unit for transmission

Page 6 - 1 About this document

144 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded process tting, s

Page 7 - 2 For your safety

154 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fig. 5: Flange mounting of the radar sensor4.3 Mounting preparations, mounting str

Page 8 - 2.7 Radio license for Europe

164 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fig. 6: Adjustment of the angle of inclinationFig.7:Turningbyfasteninginthec

Page 9

174 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011dished or round vessel tops, multiple echoes can arise. These can, however, be supp

Page 10 - 3 Product description

184 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fig.11:MountingoftheradarsensorwithinowingmediumA corresponding collar a

Page 11 - 3.2 Principle of operation

194 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011dhThe below charts specify the max. socket piece length h depending on the diameter

Page 12

2Quick startVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Quick startThe quick start enables a quick setup with many applications. You can n

Page 13

204 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The socket piece should be dimensioned in such a way that the an-tenna end protrude

Page 14 - 4 Mounting

214 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Make sure when planning your measuring site that the radar sensor has a "clear

Page 15

224 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011When using a surge pipe in a vessel, inuences from vessel installa-tions and turbu

Page 16

234 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011• The tube diameter must be at least DN 40 or 1½" with antenna size 40 mm (1½&

Page 17 - > 200 mm

244 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210110 %100 %125436Fig.21:Congurationbypass1 Radar sensor2 Marking of the polarisa

Page 18

254 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011• The measurement through a ball valve with complete run is pos-sibleConstructional

Page 19

264 MountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101123 ... 4 x hmax90°hmaxd1BFig.23:FlowmeasurementwithKhafagi-Venturiume:d=M

Page 20 - Fig. 17: Alignment in liquids

275 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210115 Connecting to power supply5.1 Preparing the connectionAlways

Page 21 - Fig. 19: Agitators

285 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Warning:Signicant potential dierences exist inside galvanizatio

Page 22

295 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210115. Insert the cable into the sensor through the cable entryFig.

Page 23

3Quick startVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210114. Carry out the adjustment in the menu items "Min. adjustment" and &quo

Page 24

305 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101156784...20mA212+( )(-)1Fig.25:Electronicscompartment,double

Page 25 - ≥ 2 mm x h

315 Connecting to power supplyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011power supply 4...20mA activepassivecommonIS GND51/L/N2+( )(-)67

Page 26 - 2 Venturiume

326 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210116 Set up with the indicating and adjustmen

Page 27 - 5 Connecting to power supply

336 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210111 2Fig. 29: Insertion of the indicating and

Page 28 - 5.2 Connecting

346 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011 – Edit parameter – Save value• [->] key

Page 29

356 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011You can nd in the operating instructions m

Page 30

366 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The selection "Standpipe" opens a

Page 31

376 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011 – Fast lling and emptying – Vessel is ver

Page 32

386 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011 – Extreme damping of output signal due to

Page 33 - 6.2 Adjustment system

396 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011 – Automatic false signal suppression with

Page 34 - 6.3 Parameter adjustment

4ContentsVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Contents1 About this document1.1 Function ...

Page 35

406 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011With this selection, the operating range of

Page 36

416 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011100%0%0,5 m(19.68")5 m(196.9")21F

Page 37

426 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210114. Enter the suitable distance value in m

Page 38

436 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The "Echocurve" shows the signal

Page 39

446 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011• Vessel installations such as struts• Agit

Page 40

456 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The menu item "Delete" is used to

Page 41

466 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011signal suppression, user-programmed lineari

Page 42

476 Set up with the indicating and adjustment moduleVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Menu Menu item Default valueAdditional adju

Page 43

487 Setup with PACTwareVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210117 Setup with PACTware7.1 Connect the PC312Fig. 32: Connection of the P

Page 44

497 Setup with PACTwareVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011• Power supply unit or processing systemNote:With power supply units wit

Page 45

5ContentsVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210119.4 Rectify faults ...

Page 46

507 Setup with PACTwareVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011All device DTMs are available as a free-of-charge standard version and a

Page 47

518 Set up with other systemsVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210118 Set up with other systems8.1 DD adjustment programsDevice desc

Page 48 - 7 Setup with PACTware

529 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210119 Diagnosis, Asset Management and service9.1 Mainte

Page 49

539 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Further echo curves: Up to 10 echo curves can be sto

Page 50

549 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011The following table shows the error codes in the sta

Page 51 - 8 Set up with other systems

559 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011CodeText mes-sageCause RecticationF264Installation/

Page 52 - 9.1 Maintenance

569 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011CodeText mes-sageCause RecticationM501Error in the

Page 53 - 4 Maintenance - blue

579 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Error Cause Rectication4 … 20 mA signal not stable

Page 54

589 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210119.4 Measurement error with constant levelFault desc

Page 55

599 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fault description Error pattern Cause Rectication7.

Page 56 - 9.4 Rectify faults

61 About this documentVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210111 About this document1.1 FunctionThis operating instructions manual prov

Page 57

609 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Fault description Error pattern Cause Rectication13

Page 58 - 36500-EN-121011

619 Diagnosis, Asset Management and serviceVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011You can nd the actual sensor software as well as de

Page 59

6210 DismountingVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101110 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of da

Page 60 - 9.6 Software update

6311 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101111 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.443

Page 61

6411 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Max. torque for NPT cable glands and Conduit tubes Ʋ Plastic housing 10 Nm (7.37

Page 62 - 10 Dismounting

6511 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Signal resolution 0.3 µAFailure signal current output (adjustable) mA-value unch

Page 63 - 11 Supplement

6611 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210110,5 m (1.6 ft)10 mm (0.394 in)- 10 mm (- 0.394 in)2 mm (0.079 in)- 2 mm (- 0.079

Page 64 - 4 Usefulmeasuringrange

6711 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Beam angle2) Ʋ Encapsulated antenna system 22° Ʋ Plastic horn antenna 10°Emitted

Page 65 - 2 Antenna edge

6811 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Wire cross-section (spring-loaded terminals) Ʋ Massive wire, cord 0.2 … 2.5 mm²

Page 66

6911 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101111.2 DimensionsThe following dimensional drawings represent only an extract of t

Page 67

72 For your safetyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210112 For your safety2.1 Authorised personnelAll operations described in this o

Page 68

7011 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011VEGAPULS61,hygienictting1 23SW 50 mm(1.97")SW 50 mm(1.97")SW 50 mm

Page 69 - VEGAPULS 61, threaded version

7111 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011VEGAPULS 61, version with mounting strap75 mm(2.95")107 mm(4.21")115 m

Page 70

7211 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011VEGAPULS61,versionwithcompressionange126 mm(4.96")10,5 mm(0.41")

Page 71

7311 SupplementVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-12101111.3 Industrial property rightsVEGA product lines are global protected by indus

Page 72

74INDEXVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011INDEXAAccessories – External indicating and adjustment unit 12 – External radio unit 1

Page 73 - 11.4 Trademark

75INDEXVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011Socket 18, 20Status messages 53Storage 12Surge pipe 22TType label 10VVessel form 4

Page 74

Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36500-EN-121011All statements concerning scope of delivery, application, practi

Page 75

82 For your safetyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-1210112.5 CE conformityThe device fullls the legal requirements of the applicable

Page 76 - Printing date:

92 For your safetyVEGAPULS 61 • 4 … 20 mA/HART - four-wire36500-EN-121011tection. The environment management system is certied according to DIN EN IS