Vega VEGABAR 64 4 … 20 mA_HART User Manual

Browse online or download User Manual for Equipment Vega VEGABAR 64 4 … 20 mA_HART. VEGA VEGABAR 64 4 … 20 mA_HART User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instruction

Operating InstructionsVEGABAR 644 … 20 mA/HARTDocument ID:27525Processpressure/Hydrostaticp

Page 2 - Contents

l with indicating and adjustment modulel with the suitable VEGA DTM in conjunction with an adjustmentsoftware according to the FDT/DTM standard, e .g.

Page 3

4 Mounting4.1 General instructionsMake sure that all parts of the instrument in contact with the measuredproduct, especially the sensor element, proce

Page 4 - 1 About this document

21222111Fig. 3: Position of the filterelements1 Filter element for ventilation of the electronics housing2 Filter element for ventilation of the measur

Page 5 - 2 For your safety

12Fig. 4: Temperature ranges1 Process temperature2 Ambienttemperature4.2 Mounting stepsFor mounting VEGABAR 64, a we lded socket is required. You can

Page 6

90 mm (3.54")R 3,5 mm(0.14")3mm(0.12")70 mm (2.76")8 mm(0.32")93 mm (3.66")110 mm (4.33")Fig. 5: Drilling template

Page 7

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 8 - 3 Product description

Caution:No grease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that co

Page 9 - 3.3 Operation

11 Tighten thecompression nut of the cable entry. The seal ring mustcompletely encircle the cable12 Screw the housing cover onThe electrical connectio

Page 10 - 27525-EN-081209

2 Remove the housing socket from the mounting plate321Fig. 7: Components of theexternal housing for plics®devices1 Screws2 Wall mounting plate3 Cable

Page 11 - 4 Mounting

5.3 Wiring plan, singlechamber housingThe following illustrations apply to the non-Ex as well as to the Ex-iaversion.1 243Fig. 8: Material versions, s

Page 12

Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .

Page 13 - 4.2 Mounting steps

I²CDisplay1 2 5 6 7 83412Fig. 9: Electronics and connectioncompartment, single chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Spring

Page 14

123465Fig. 11: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1 for VEGADIS 61 (optional)3 Housing cover, e

Page 15 - 5 Connecting to power supply

312Display1 2I²CFig. 13: Connection compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Ground terminal for connection

Page 16 - 5.2 Connection procedure

5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 15: Double chamber housing1 Housingcover, connection compartment2 Blind stopper or plug M12 x 1

Page 17

121 2Fig. 17: Connection compartment doublechamber housing Ex d1 Spring-loaded terminals for power supply and cable screen2 Ground terminal for connec

Page 18

+-12Fig. 19: Wire assignment, connection cable1 brown (+) andblue (-) to power supply or to the processing system2 Shielding5.7 Wiring plan, exte rnal

Page 19 - 5.3 Wiring plan, single

5 6 7 81 2DisplayI²C45123Fig. 21: Electronics and connectioncompartment1 Plug connector for VEGACONNECT (I²C interface)2 Spring-loaded terminals for c

Page 20

1 2 3 4 6 3 4 1 2 5Fig. 22: Connection of thesensor in the housing socket1 Brown2 Blue3 Yellow4 White5 Shielding6 Breather capillariesI2CDisplay11

Page 21

5.8 Switch on phaseAfter connecting VEGABAR 64 to power supply or after a voltagerecurrence, the instrument carries out a self-check for approx. 30sec

Page 22

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 23

7.3 Parameter adjustment with AMS™ and PDM .. . . . . .468 Maintenance and fault rectification8.1 Maintain. . . . . . . . . . . . . . . . . . . . . . .

Page 24

Fig. 24: Mounting the indicatingand adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuo

Page 25

6.3 Adjustment system1.1231Fig. 25: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 26 - 5 6 7 81 2

6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You w

Page 27 - 1 2 3 4

To select the adjustment unit (in theexample switching over from barto mbar) you have to proceed as follows:2)1 Push the [OK] button in the measured v

Page 28 - 5.8 Switch on pha

Unit of measurementDensity0001000kg/dm³6 Enter the requested density value with [->] and [+], confirm with[OK] and move to position correction with

Page 29 - 6.1 Short description

5 Confirm with [+] andmove to max. adjustment with [->].The min. adjustment is finished.Information:For an adjustment with filling, you simply enter t

Page 30

The position correction compensates the influenceof the mountingposition or static pressure on the measurement. It does not influencethe adjustment valu

Page 31 - - Select editing position

▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Confirm the menu "Basic adjustment" with [OK], the menu item"Unit" will be displaye

Page 32 - Address 0

Proceed as follows:1 Edit thembar value in the menu item "zero" with [OK].Zero adjustment000.0 %P=+0000.0 mbar0000.0 mbar2 Set the requested

Page 33

A linearization is necessary for all vessels in which the vessel volumedoes notincrease linearly with the level - e. g. with a cylindrical orspherical

Page 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35 - 0000.0 mbar

Copy sensor dataCopy sensor data?Basic adjustmentIf the "Reset" (sensor-specific basic adjustment) is carried out, thesensor resets the value

Page 36

Factory settingLike basicadjustment, furthermore special parameters are reset todefault values.6)PointerThe min. and max. temperature or pressure valu

Page 37

6.5 Menu schematicInformation:Depending on the version and application, the highlighted menuwindows are not always available.Basic adjustment1▶Basic a

Page 38

Diagnostics3Basic adjustmentDisplay▶DiagnosticsServiceInfo3.1Pointerp-min.: -5.8 mbarp-max.: 167.5 mbarT-min.: -12.5 °CT-max.: +85.5 °C3.2Sensor statu

Page 39 - Linearisation curve

7 Setup with PACTware andother adjustmentprograms7.1 Connect the PC via VEGACONNECT312Fig. 26: Connection of the PC via VEGACONNECT directlyto the sen

Page 40 - Copy sensor data?

Necessary components:l VEGABAR 64l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFig

Page 41

All currently available VEGADTMs are provided in the DTM Collectionon CD and can be obtained from the responsible VEGA agency for atoken fee. This CD

Page 42 - 6.5 Menu schem

8 Maintenance and fault rectification8.1 MaintainWhenused in the correct way, no special maintenance is required innormal operation.In some application

Page 43

? 4 … 20 mA signal notstablel Level fluctuationsà Set the integration time via the indicating and adjustmentmodule or PACTwarel no atmospheric pressure

Page 44

8.3 Calculationof total deviation (similar toDIN 16086)The total deviation Ftotalaccording to DIN 16086 is the sum of basicaccuracy Fperfand longterm

Page 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46

Basic accuracy analogue output signal in percent:Fperf= √((FT)2+ (FKl)2+ (Fa)2)FT= (0.05 % + 0.1 % x TD)FKl= 0.075 %Fa= 0.15 %Fperf= √((0.05 % + 0.1 %

Page 47 - 8.2 Remove interferences

Connect the sensor to power supply and provide connection from PCto theinstrument via VEGACONNECT. Start PA CTware and provideconnection to the sensor

Page 48

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 49 - DIN 16086)

10 Supplement10.1 TechnicaldataGeneral dataParameter, pressure Gauge pressure, absolute pressure, vacuumMeasuring principle Ceramic-capacitive, dry me

Page 50 - 8.5 Software update

HART output values- HART value (Primary Value) Process pressure- HART value (Secondary Value) TemperatureSignal resolution 1.6 µAFailure signal curren

Page 51 - 8.6 Instrument repair

Accuracy- in therange of 0 … +100 °C(+32 … +212 °F)±3 K- in the range of -50 … 0 °C (-58 … +32 °F)and +100 … +150 °C (+212 … +302 °F)typ. ±4 KInput va

Page 52 - 9 Dismounting

Nominal range Overload, max. pressure Overload, min. pressureAbsolutepressure0 … 0.1 bar/0 … 10 kPa 15 bar/1500 kPa0 bar abs.0 … 1 bar/0 … 100 kPa 35

Page 53 - 10 Supplement

Nominal range Overload, max. pressure Overload, min. pressure0 … 900 psi 2900 psi0 psiReferenceconditions and actuating variables (similar to DIN EN 6

Page 54

Thermal change zero signal and output sp an with absolute pressure measuring range 0.1 bar,referencetemperature 20 °C (68 °F):- In the compensated tem

Page 55

- FFKM (Kalrez 63 75) -10 … +150 °C (+14 … +302 °F)- FFKM (Chemraz 535) -30 … +150 °C (-22 … +302 °F)Vibration resistance mechanical vibrations with 4

Page 56

2.5 Safety approval markings and safety tipsThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fu

Page 57

Electromechanical data - version IP 66/IP 68, 1 barCableentry- Single chamber housing l 1 x IP 68 cable gland M20 x 1.5; 1 x blindstopper M20 x 1.5or:

Page 58

Connection cable between IP 68 instrument and external housing:- Configuration four wires, one suspension cable, one breathercapillary, screen braiding

Page 59

100075050025012 181614 20 22 24 26 28 30 32 34 36ΩV4123Fig. 30: Voltage diagram1 HART load2 Voltage limit EEx-iainstrument3 Voltage limit non-Ex/Exd i

Page 60

You can find detailed information in the supplied Safety Manual of the instrument series or under"www.vega.com", "Downloads", "

Page 61

10.2 DimensionsHousing~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")ø 77 mm(3.03")117 mm (4.61"

Page 62

Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")120 mm (4.72")~ 103 mm(4.06")~ 105 mm (4.13")ø 77 mm(3.03")116 mm (4.5

Page 63

External housing with IP 68 version1265 mm(2 9/16")68 mm(2 43/64")92 mm(3 5/8")42mm(1 21/32")40mm(1 37/64")90 mm (3 35/64&quo

Page 64 - 10.2 Dimensions

VEGABAR 64 - threaded fitting 1GI GO/GRGV/GT/GHBFGSGJ/GK/GM/GUG½AG¼AG½AG¼AG½A½"NPTM20x1,5SW 27 mm(1 1/16")G½A23 mm(29/32")73 mm(2 7/8&qu

Page 65

VEGABAR 64 - threaded fitting 2SW41 SW46 SW55 G1A G1 ½ A G1 ¼ A G1 ½ A 21mm (53/64") 75mm (2 61/64") 50mm (1 31/32") 55mm (2 11/64"

Page 66

VEGABAR 64 - hygienic fitting 1SW4651 mm(2 1/64")51 mm(2 1/64")51 mm(2 1/64")60 mm(2 23/64")ø 64 mm(2 33/64")ø 51 mm(2 1/64&qu

Page 67

l Chapter "Packaging, transportand storage"l Chapter "Disposal"VEGABAR 64 • 4 … 20 mA/HART 72 For your safety27525-EN-081209

Page 68

VEGABAR 64 - hygienic fitting 2SW4650 mm(1 31/32")51 mm(2 1/64")60 mm(2 23/64")51 mm(2 1/64")51 mm(2 1/64")ø 78 mm (3 5/64&quo

Page 69

VEGABAR 64 - flangeconnection3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 45/64"4xø 45/64"8xø 45/64"4 21/64&qu

Page 70 - TA TC RA/RB

VEGABAR 64 - flangeconnection with extensionRL50 mm(1 31/32")d57 1/2"3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4xø 4

Page 71

VEGABAR 64 - threaded fitting for paper industry52 mm(2 3/64")21 mm(53/64")46M44x1,2560M56x1,2552 mm(2 3/64")21 mm(53/64")BA/BB BEF

Page 72

VEGABAR 64 - extension fitting for paper industry158 mm (6 7/32")40 mm(1 37/64")ø 38 mm(1 1/2")43 mm(1 11/16")23 mm(29/32")ø 4

Page 73 - BA/BB BE

10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 74

76 VEGABAR 64 • 4 … 20 mA/HART10 Supplement27525-EN-081209

Page 75 - 10.4 Trademark

VEGABAR 64 • 4 … 20 mA/HART 7710 Supplement27525-EN-081209

Page 76

78 VEGABAR 64 • 4 … 20 mA/HART10 Supplement27525-EN-081209

Page 77

VEGABAR 64 • 4 … 20 mA/HART 7910 Supplement27525-EN-081209

Page 78

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGABAR 64 pressure transmitterl Documentation- this operating instructions m

Page 79

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 80 - ISO 9001

l Technical data: Measuringrange, process pressure, processtemperature, signal output, voltage supply, protection, protectionclassl Order numberl Arti