Operating InstructionsVEGAPULS 624 … 20 mA/HART two-wireRadar
The version with "Flangeand horn antenna with ø 48 … 95 mm(1.89 … 3.74 in)" is particularly suitable for storage tanks and processvessels, f
3.4 Packaging, transport and storageYour instrument was protected by packaging during transport. Itscapacity to handle normal loads during transport i
4 Mounting4.1 General instructionsSelect an installation position you can easily reach for mounting andconnecting as well as later retrofitting of an i
1 32100%0%4Fig. 3: Measuring range (operating range), max. measuringdistance andreference plane1 full2 empty (max. measuring distance)3 Measuring rang
You can find the specifications in chapter "Technical data" in the or onthe type label.4.2 Mounting preparations - Horn antennaInformation:Thi
Note:VEGAPULS 62 with rinsing air connection or antenna extension isprovided with a notch on the antenna socket. This notch mustcorrespond to the mark
7 Check, if the O-ring sealis available on the connection piece and ifit is not damaged.Note:A damaged O-ring seal must be replaced: FKM (Viton) artic
If you cannot keep this distance you should carry out a false echostoragebefore setup. This applies mainly if buildup on the vessel wallis expected. I
Do not mount the instruments in or above the filling stream. Make surethat you detect the product surface, not the inflowing product.Fig. 9: Inflowing li
dhmax.d1½"50 mm/2"80 mm/3"100 mm/4"150 mm/6"200 mm250 mm300 mm500 mm800 mmhmax.Fig. 11: Deviating socket dimensionsTip:VEGAPU
Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .
Fig. 13: Cover smooth profileswith deflectorsIf there are agitators in the vessel, a false echo storage should becarried out with the agitators in motio
Note:Measurementin a standpipe is not recommended for very adhesiveproducts.Surge or bypass tubes must extend all the way down to the requestedmin. le
100%0%1> 300 mmFig. 16: VEGAPULS 62 in a bypasstube. The polarisation marking on theprocess fitting must be in one plane with the tube holes or the
1234Fig. 17: Polarisation level with flangeversion, view from top on the sensor andbypass tube. The sensor housing is not shown.1 Position of the polar
3 ... 4 hmax≥ 50 mm90°231hmaxdmin≥ 2 mm x hmax90°4Fig. 18: Flow measurement withrectangular flume: d = min. distance of thesensor; hmax. = max. filling
23 ... 4 x hmax90°hmaxd1BFig. 19: Flowmeasurementwith Khafagi-Venturi flume: d = Min. distanceof thesensor; hmax. = max. filling of the flume; B = bigges
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
Caution:No grease should be used when screwing the NPT cable gland orsteel tube into the threaded insert. Standard grease can containadditives that co
7 Insert the wire ends into the open terminals according to the wiringplanFig. 20: Connection steps 6 and 78 Pressdown the opening levers of the termi
55551 243Fig. 21: Material versions, single chamberhousing1 Plastic2 Aluminium3 Stainless steel, investment casting4 Stainless steel, electro-polished
7 Setup with PACTwareand other adjustment programs7.1 Connecting the PC . . . . . . . . . . . . . . . . . . . . . . . . . .477.2 Parameter adjustment
I2CDisplay11 2 56 7 8Fig. 23: Wiring plan, single chamberhousing1 Voltage supply/Signal output5.4 Wiring plan, double chamber housingThe following ill
132Display1 2 5 6 7 8I²CFig. 25: Electronics compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c
I2C11 2Fig. 27: Wiring plan, double chamberhousing1 Voltage supply/Signal output5.5 Wiring plan double chamber housing Ex d1 2 345Fig. 28: Doublechamb
132Display1 2 5 6 7 8I²CFig. 29: Electronics compartment, double chamberhousing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c
11 2Fig. 31: Wiring plan doublechamber housing Ex d1 Voltage supply/Signal output5.6 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 32: Wireassignme
6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 33: Insert indicating andadjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous mea
6.3 Adjustment system1.1231Fig. 34: Indicating and adjustmentelements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov
6.4 Setup procedureIn HART-Multidrop mode (several sensors on one input) the addressmust be set before continuing with the parameter adjustment. You w
▶Basic adjustmentDisplayDiagnosticsServiceInfo2 Select the menu item "Basic adjustment" with [->] and confirm with[OK]. Now the menu item
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
LiquidAccording to the conductivity and the dielectric value of liquids, thereflection properties can differ considerably. Therefore additionaloptions s
linearEnter the requested parameter via the appropriate keys, save yoursettings and jump to the next menu item with the [->] key.Caution:Note the f
Extended settingquick level change > 1 m/min.Note:Since with the function "Quick level change > 1 m/min." the generationof an average
Menu item Reset valueMax. adjustment 0 m(d)Min. adjustment 30 m(d)(VEGAPULS 61, 63, 65, 67)35 m(d) (VEGAPULS 62, 66)70 m(d) (VEGAPULS 68)Medium Liquid
6.5 Menu schematicInformation:Depending on the version and application, the light-coloured menuwindows are not always available or offer nor sel ection
3.1PointerDistance min.: 0.234 m(d)Distance max.: 5.385 m(d)3.2Meas. reliability15 dBSensor statusOK3.3Curve selectionEcho curve▼3.4Echo curvePresenta
6.6 Saving the parameter adjustment dataIt is recommended noting the adjusted data, e.g. in this operatinginstructions manual and archive them afterwa
7 Setup with PACTware andother adjustmentprograms7.1 Connecting the PC312Fig. 35: Connection of the PC via VEGACONNECT directlyto the sensor1 USB cabl
Necessary components:l VEGAPULS 62l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system12 43OPENTWISTUSBLOCKFi
Note:Keep in mindthat for setup of VEGAPULS 62, DTM-Collection in theactual version must be used.All currently available VEGA DTMs are provided in the
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
8 Maintenance and fault rectification8.1 MaintenanceWhen used in the correct way, no special maintenance is required innormal operation.8.2 Remove inte
? Current signal greater than 22 mA or less than 3.6 mAl Electronics module defectiveà Exchange instrument or return instrument for repairIn Ex applic
Information:When loading on site, first of all the order data must be downloadedfrom the Internet (see operating instructions manual "Oscillator&q
l Please ask the agency serving you for the address of your returnshipment. Youcan find the respective agency on our websitewww.vega.com under: "C
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 TechnicaldataGeneral data316L corresponds to 1.4404 or 1.4435Materials, non-wetted parts- Housing Plastic PBT (polyester), Alu die-c
Failure signal current output (adjustable) mA-value unchanged 20.5 mA, 22 mA, < 3.6 mA(adjustable)Max. output current 22 mALoad see load diagram un
Max. level change Adjustableup to 1 m/min. (dependent on theparameter adjustment)Max. emitted HF power of the antenna system- Pulse peak power < 2
2,0 m (6.562 ft)30 m (98.43 ft)40 mm (1.574 in)15 mm (0.590 in)- 15 mm (- 0.590 in)- 40 mm (- 1.574 in)0Fig. 39: Deviation VEGAPULS 62 with horn anten
Influence of the ambient temperature to the sensor electronics5)Average temperature coefficient of the zerosignal (temperature error)0.03 %/10 KInfluence
During t he entire duration of use, the useris obliged to determine thecompliance of the required occupational safety measures with thecurrent valid r
Vessel pressure - horn antenna -1 … 40 bar/-100 … 4000 kPa (-14.5 … 580 psi)Vessel pressure - parabolic antenna -1 … 6 bar/-100 … 6000 kPa (-14.5 … 87
Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry/plug7)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø
- Diameter approx. 8 mm (0.315 in)- Colour - standard PE Black- Colour - standard PUR Blue- Colour - Ex-version BlueIndicating and adjustment moduleVo
1000750500250141816 20 22 24 26 28 30 32 34 36ΩV4123Fig. 43: Voltage diagram1 HART load2 Voltage limit EEx-iainstrument3 Voltage limit non-Ex/Exd inst
1000750500250151816 20 22 24 26 28 30 32 34 36ΩV4123Fig. 44: Voltage supply forversion with increased sensitivity1 HART load2 Voltage limit EEx-ia ins
ApprovalsDependingon the version, instruments with approvals can have d ifferent technical data.For these instruments, the corresponding approval docum
10.2 DimensionsHousingin protection IP 66 /IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.03")112 mm (4 13/32")M20x1,5/½ NPT~ 69 mm(2.72")
Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(3.03")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.
VEGAPULS 62 - horn antennain threaded versionmm inch 38 mm (1.50")22 mm (0.87")22 mm (0.87")118 mm (4.65")SW 46 mm(1.81")8.50
VEGAPULS 62 - horn antennain threaded version with purging air connection38 mm (1 1/2")22 mm(0.87")22 mm (0.87")118 mm (4.67")xyxy
l The device must be insensitive to interfering immissions, includingthose that may cause undesirable operating conditions.The instrument is designed
VEGAPULS 62 - horn antennain threaded version with antenna extensionmm inch 38 mm (1.50")22 mm (0.87")22 mm (0.87")118 mm (4.65")S
VEGAPULS 62 - horn antennain flange version4xø0.75"4xø0.75"8xø0.75"8xø0.87"8xø0.88"4.75"4.92"6.30" 2.95"3.
VEGAPULS 62 - horn antennain flange version with purging air connectionDkxdby12140mm (5.51")82,5 mm(3.25")4xø0.75"4xø0.75"8xø0.75&q
VEGAPULS 62 - horn antennaand swivelling holdermm D mm DINASMEb k d DN 50 165 11,5 125 4x ø 18DN 80 200 11,5 160 8x ø 18DN 100 220 11,5 180 8x ø 18D
VEGAPULS 62 - horn antenna, swivelling holder and purging air connectionmminch120 mm (4.72")47,5 mm(1.87")20 mm(0.79")12d3.94" ø 1
VEGAPULS 62 - parabolic antenna in threaded version138 mm (5.43")ø 244 mm (9.61")SW 46 mm(1.81")22 mm (0.87")118 mm (4.65")38
VEGAPULS 62 - parabolic antenna in flange versionD mm b k d DN 50 PN 40 165 20 125 4xø18 DN 80 PN 40 200 24 160 8xø18 DN 100 PN 16 220 20
VEGAPULS 62 - parabolic antenna and swivelling holderd120 mm (4.72")130 mm (5.12")ø 243 mm (9.57")DmmDINASMEb kdDN 50 165 11,5 125 4x ø
VEGAPULS 62 - parabolic antenna and swivelling holder with purging air connectiond47,5 mm(1.87")130 mm (5.12")ø 243 mm (9.57")120 mm (4
10.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
3 Product description3.1 ConfigurationThe VEGAPULS 62 radar sensor is available in two electronicsversions:l Standard electronics type PS60KHl Electron
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
213Fig. 1: VEGAPULS 62 - threaded version withplastic housing1 Housing cover with integrated PLICSCOM (optional)2 Housing with electronics3 Process fit