Vega VEGAMET 514… D User Manual

Browse online or download User Manual for Equipment Vega VEGAMET 514… D. VEGA VEGAMET 514… D User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instruction

ESCOK-+12on100%CONNECT514 DLevel and PressureinoutOperating InstructionVEGAMET 514… D

Page 2 - Contents

10 VEGAMET 514… D1.5 DimensionsCircuit board 100 x 160 x 1,5European size Multiple plug162100128,4255 TE914,53Ser.No.12345678ESCOK-+12on100%CONNECT514

Page 3 - 5 Diagnosis

VEGAMET 514… D 111.6 Ex-technical dataPower supplyOperating voltage Unenn corresponds to the not-Ex-versionLimit voltage Unenn = 250 V AC or 125 V DCM

Page 4 - 1 Product description

12 VEGAMET 514… DMounting2 Mounting2.1 Mounting versionsVEGAMET 514 D … 514 VD signal conditioninginstruments can be either mounted with a module ina

Page 5 - 1.2 Types and versions

VEGAMET 514… D 13876540FEDCBA93321Mounting2.2 Instrument addressAdjust the instrument address on the appropriate switch on the circuit board. Address

Page 6 - 1.3 Applications

14 VEGAMET 514… D3 Electrical connectionElectrical connection22824223032d b z+-+-+-+--+L (+)N (-)61012201618+-+1 2 3VEGAMET 514 D, 514 D

Page 7

VEGAMET 514… D 15Ser.No.12345678ESCOK-+12on100%CONNECT514!1816[17]1513215710111213144689Set-up4 Set-up4.1 Indicating and operating elementswith ad

Page 8

16 VEGAMET 514… DSet-up4.2 Adjustment systemIndicating and adjustment moduleESCOK-+100%Acc. to the parameter, change value orselect from listSelect me

Page 9

VEGAMET 514… D 17Set-upAdjustments and coordinations must be provided todetermine the instrument functions. Thisdetermination is made by the following

Page 10 - >>

18 VEGAMET 514… DSer.No.12345678ESCOK-+12on100%CONNECT515!Set-up4.4 Adjustment via PCSignal conditioning instrument with operating moduleVEGACONNECTco

Page 11 - 1.7 Approvals

VEGAMET 514… D 19Set-up, configuration4.6 Set-up, configuration4.6.1 Configuration inputsThe inputs of the signal conditioning instruments areconfigur

Page 12 - 2 Mounting

2 VEGAMET 514… DContentsSafety informationThe described module must only be inser ted andoperated as described in this operating instruction.Please no

Page 13 - 2.2 Instrument address

20 VEGAMET 514… DConnection example 1Configuration, inputs–– Input 1 Sensor with analog transmission of measured data–– Input of this MET–– Channel no

Page 14 - 3 Electrical connection

VEGAMET 514… D 21Set-up, configuration4.6.2 Configuration meas. pointVEGAMET 514 D and 514 VD signal conditioning instruments in their basic configura

Page 15 - 4 Set-up

22 VEGAMET 514… DSet-up, configurationMonitoringFor the activation of the monitoring the following pre-requirements must be met:- Determine in the men

Page 16 - 4.2 Adjustment system

VEGAMET 514… D 23Set-up, configuration4.6.3 Configuration outputDependent on the basic configuration the outputs are automatically coordinated to the

Page 17 - 4.3 Menu list

24 VEGAMET 514… Dd b ztHighLowTasterRelay outp.d b ztHighLowRelay outp.TasterConfiguration, outputs–– Configuration relay outputs–– Operating rela

Page 18 - 4.5 Set-up sequence

VEGAMET 514… D 25Set-up, configurationConfiguration, outputs–– Configuration PC/PLC Dependent on the basic configuration outputsare automatically coo

Page 19

26 VEGAMET 514… DSet-up, parameter adjustment4.7 Set-up, parameter adjustmentThe menu described in the following is available for parameter adjustment

Page 20 - Set-up, configuration

VEGAMET 514… D 27Set-up, parameter adjustmentAdjustment- Application Flow measurement- Sensor ultrasonic sensorsradar sensorsParameter adjustment MST1

Page 21

28 VEGAMET 514… DSet-up, parameter adjustment4.7.2 Flow measurementGeneral informationIn the following section elementary information to dimensions in

Page 22

VEGAMET 514… D 29Set-up, parameter adjustmentMax. flow, QmaxIn the term Qmax (menu point 100 % corresponds to1000) the following flume specific factor

Page 23

VEGAMET 514… D 3Contents4 Set-up4.1 Indicating and operating elements ... 154.2 Adjustment system ...

Page 24

30 VEGAMET 514… DSet-up, parameter adjustmentTrapezoidal weir (Cipolletti)With sharp overflow edgeValues for QmaxBK QmaxhmaxQminhminin mm (Factor) in

Page 25

VEGAMET 514… D 31Rectangular overflow without contractionWith sharp overflow edge and throatSet-up, parameter adjustmentValues for QmaxBQmaxhmaxQminhm

Page 26

32 VEGAMET 514… DSet-up, parameter adjustmentPalmer-Bowlus-FlumeValues for QmaxDK QmaxhmaxQminhminin Zoll (Factor) in m3/h in mm in m3/h in mm6"

Page 27 - Set-up, parameter adjustment

VEGAMET 514… D 334.7.3 Parameter adjustment MST1 and MST2, processingParameter adjustment MST1, processing (level)–– Scaling–– 0 % corresponds to 0.

Page 28

34 VEGAMET 514… DSet-up, parameter adjustmentParameter adjustment MST2, processing (flow)With the scaling of MST2 the conditions for the signalconditi

Page 29

VEGAMET 514… D 35Set-up, parameter adjustment4.7.4 Parameter adjustment MST1 and MST2, outputsParameter adjustment MST1 and MST2, outputs–– Current ou

Page 30

36 VEGAMET 514… DSet-up, parameter adjustmentParameter adjustment MST1 and MST2, outputsCurrent output 3 (continuation)–– Pulse parameter–– Volume 100

Page 31

VEGAMET 514… D 37Set-up, parameter adjustmentParameter adjustment MST1, outputs–– Relay outputs–– Relay output 1 acc. to basic configuration coordinat

Page 32

38 VEGAMET 514… DSet-up, parameter adjustment–– Relay output 1 (continuation 1)–– Kind Overfill protectionThe relay of relay output 1 de-energizesat s

Page 33

VEGAMET 514… D 39Set-up, parameter adjustmentTendency determinationThe level change within the scanning time (ta) is determined and after all scanning

Page 34

4 VEGAMET 514… DProduct description1 Product description1.1 Function and configurationVEGAMET 514 D and 514 DV signal conditioninginstruments are desi

Page 35

40 VEGAMET 514… DSet-up, parameter adjustmentMonitoringThe following requirements must be met for activation of the monitoring:- Determine input 4 in

Page 36

VEGAMET 514… D 41Set-up, parameter adjustmentParameter adjustment MST2, outputs–– Relay outputs–– Relay output 2 acc. to basic configuration coordinat

Page 37

42 VEGAMET 514… DSet-up, parameter adjustmentParameter adjustment MST1 and MST2, outputs–– MET-indication–– relating to Percentscaled etc. choice acc.

Page 38

VEGAMET 514… D 434.8 Set-up, additional functions4.8.1 PasswordAdditional functions–– Password off each menu point can be enquired and modifiedon the

Page 39

44 VEGAMET 514… DAdditional functions–– Edit linearization curve–– Linearization curve 1–– Lin. curve 1–– Edit lin.curve 1 Number of index markers 1 …

Page 40

VEGAMET 514… D 45Set-up, additional functions4.8.5 VEGAMET ResetAdditional functions–– VEGAMET Reset–– Reset configuration–– to default With reset to

Page 41

46 VEGAMET 514… D–– Configuration outputs–– Configuration current outputs–– Current 1 to (coordination)–– Current 2 to (coordination)–– Current 2 Stan

Page 42

VEGAMET 514… D 47Additional functions–– Password–– Edit lin. curves–– Lin. curve 1–– Lin. curve 2–– Lin. curve 3–– Info–– Input info–– VEGAMET-Info––

Page 43

48 VEGAMET 514… DDiagnosis5.2 MaintenanceThe instrument is maintenance free.5.3 RepairDue to safety and guarantee reasons repair workbeside the wiring

Page 44 - Set-up, additional functions

VEGAMET 514… D 495.5 Error codesError code MeaningE004 This operation is not supported by the instrument (different software version). You tried toact

Page 45 - 4.8.6 Service

VEGAMET 514… D 5Product description1.2 Types and versionsAccording to the application and the appropriatesensor the type and version of the signalcond

Page 46

50 VEGAMET 514… DE029 Measured valuated. The measured value is generated by simulation and does not reflect thereal condition.E031 Same DISBUS-address

Page 47 - Diagnosis

VEGAMET 514… D 51Error code MeaningDiagnosisE070 Scaling span too small. The values of the scaling are too close together or are identical.Please chec

Page 48 - 5.4 Fault signal

52 VEGAMET 514… DVEGA Grieshaber KGAm Hohenstein 113D-77761 SchiltachPhone (0 78 36) 50 - 0Fax (0 78 36) 50 - 201Fax (0 78 36) 50 - 203Technical data

Page 49 - 5.5 Error codes

6 VEGAMET 514… DFig. 1.13 Correction in the pointOffset correction- in empty flume- preferably manually with key- parallel shifting of theadjustment c

Page 50

VEGAMET 514… D 71.4 Technical dataPower supplyOperating voltage Unenn= 24 V AC (20 … 53 V), 50/60 Hz= 24 V DC (20 … 72 V)Power consumption- VEGAMET 51

Page 51

8 VEGAMET 514… DProduct descriptionCurrent outputNumber 3 outputsFunction current output 2 and 3 can be configured andparameter adjusted as:- level pr

Page 52 - ISO 9001

VEGAMET 514… D 9Indicating elementClear text indication LC-display- 4 line, 6 figures each- background lightningAnalog indication 11 segments 0 % … 10