Operating InstructionsVEGAFLEX 67-40 … +150 °C, PFA insulatedFoundation FieldbusDocument ID:32306Guided Microwave
The data for power supply are specified in chapter "Technical data".The optional heating requires its own operating voltage. You can finddetai
4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and
Fig. 3: Measures against moisture penetrationThe reference plane for the measuring range of the sensors is thesealing surface of the thread or flange.K
keep in mind that measurement down to the tip of the probe is notpossible. The exact value of the min. distance (lower dead band) isstated in chapter
Fig. 5: Lateral loadExtreme vibration caused by the system, e.g. due to agitators orturbulence in the vessel from inflowing medium, can cause the coaxp
5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o
In systems without potential equalisation, connect the cable screendirectly to ground potential at the power supply unit and at the sensor.In the conn
7 Insert the wire ends into the open terminals according to the wiringplanFig. 6: Connection steps 6 and 78 Press down the opening levers of the termi
I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 7: Electronics and connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inte
132Display1 2 5 6 7 8I2CFig. 9: Electronics compartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c
Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .
I2C11 2Fig. 11: Wiring plan, double chamber housing1 Voltage supply, signal output5.5 Wiring plan - version IP 66/IP 68, 1 bar12Fig. 12: Wire assignme
6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,
Fig. 13: Insert indicating and adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous me
6.3 Adjustment system2311.1Fig. 14: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mo
6.4 Setup stepsAfter VEGAFLEX 67 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30seco
Dielectric valueUpper medium0003 Enter the dielectric figure (DK value) of the upper medium andconfirm with [OK].Save the settings with [OK] and move to
ApplicationLiquidStandard(dielectric figure ≥ 2)Depending on the dielectric figure (dielectric figure or εr), measuredproducts can have a different reflect
2 Select the menu item "Service" with [->] and confirm with [OK].Now the menu item "False signal suppression" is displayed.3 Con
l PINl Sensor length/Sensor typel False signal suppressionCopy sensor dataCopy sensor data?Basic adjustmentIf the function "Reset" is carrie
6.5 Menu schematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Upper mediumDielectric figure of the uppermediumenter/calculate1.2M
8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .348.2 Remove interferences. . . . . . .
Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Sensor5.00 m(d)Rod4.2SimulationStart simulation?4.3ResetSelect reset?4.4Unit of measurementm(
6.6 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operatinginstructions manual, and archiving them afterwa
7 Set up with PACTware and other adjustmentprograms7.1 Connect the PC312Fig. 15: Connection of the PC via VEGACONNECT directly to the sensor1 USB cabl
Necessary components:l VEGAFLEX 67l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustmen
8 Maintenance and fault rectification8.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.8.2 Remov
Error Cause RectificationInstrument doesnot appear duringconnection setupProfibus DP cab-le pole-reversedCheck cable and correct, if necessaryIncorrect
8.3 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications only one instrument and
At "www.vega.com/downloads" go to "Software". Select under "plicssensors and instruments", "Firmware updates"
9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper
10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting PFA and TFM PTFE 1600
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
- Rod: ø 10 mm (0.394 in) approx. 620 g/m (6.7 oz/ft)- Cable: ø 4 mm (0.157 in) approx. 80 g/m (0.86 oz/ft)- Gravity weight 325 g (11.5 oz)Insulation
2453124531Fig. 17: Measuring ranges of the VEGAFLEX 67 - rod and cable version1 Reference plane2 Probe length3 Measuring range (default setting refers
10 m (32.82 ft)11 m (36.09 ft)12 m (39.37 ft)13 m (42.65 ft)14 m (45.93 ft)15 m (49.21 ft)16 m (52.49 ft)17 m (55.77 ft)18 m (59.06 ft)23 m (75.46 ft)
TSd1h1h2d21L2L1Fig. 19: Interface measurement (interface is between L1 and L2)1 Reference planed1 Distance to the interface (Secondary Value 2)d2 Dist
considerably on t he application. Hard and fastaccuracy specifications are thus not available.Deviation see diagramsThe accuracy values of the diagrams
L015 mm(0.591")-15 mm(-0.591")10 mm(0.394")-10 mm(-0.394")0,35 m(13.78")0,2 m(7.874")0,2 m(7.874")0,05 m(1.969"
0°C(32°F)40°C(104°F)20°C(58°F)60°C(140°F)80°C(176°F)50°C(122°F)-40°C(-40°F)100°C(212°F)150°C(302°F)12Fig. 22: Ambient temperature -
Spring-loaded terminals for wire cross-sec-tion< 2.5 mm² (AWG 14)Electromechanical data - version IP 66/IP 68 (1 bar)Cable entry- Single chamber ho
Power supply by/max. number of sensors- H1 power supply max. 32 (max. 10 with Ex)Electrical protective measuresProtection, depending on housing versio
10.2 Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block (TB) and Function block (FB) in
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
Diagram, adjustmentThe following illustration shows the function of the adjustment.Secondary_value_1CalibrationLowest PointCalibrationHighest PointSen
l secondary_value_2- This is the distance value (sensor_value) with the status of the transducer block- It is the input for the AIFB when CHANNEL = 3
- Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit isdefined in "level_unit"- When writing
10.3 DimensionsThe following dimensional drawings represent only an extract of thepossible versions. Detailed dimensional drawings can be downloadedon
Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm (4.72")~ 105 mm (4.13")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.31
VEGAFLEX 67LLL115 mm (4.53")69,4 mm(2.73")ø 10 mm(0.39")ø 20 mm(0.79")ø 4 mm(0.16")70 mm(2.76")71,4 mm(2.81")1 23 4
10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only
VEGAFLEX 67 • Foundation Fieldbus 5710 Supplement32306-EN-120329
58 VEGAFLEX 67 • Foundation Fieldbus10 Supplement32306-EN-120329
VEGAFLEX 67 • Foundation Fieldbus 5910 Supplement32306-EN-120329
2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
3 Product description3.1 StructureThe scope of delivery encompasses:l Level sensor VEGAFLEX 67l Documentation- this operating instructions manual- Ope
l Article numberl Serial numberl Technical datal Article numbers, documentationWith the serial number, you can access the delivery data of theinstrume
TS d1 h1 h2 d2 1 L2 L1 Fig. 2: Interface measurement1 Reference planed1 Distance to the interfaced2 Distance to the levelTS Thickness of the upper med