Vega VEGAFLEX 67 (-40…+150°C PFA insulated) Foundation User Manual

Browse online or download User Manual for Equipment Vega VEGAFLEX 67 (-40…+150°C PFA insulated) Foundation . VEGA VEGAFLEX 67 (-40…+150°C PFA insulated) Foundation Fieldbus User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instructions

Operating InstructionsVEGAFLEX 67-40 … +150 °C, PFA insulatedFoundation FieldbusDocument ID:32306Guided Microwave

Page 2 - Contents

The data for power supply are specified in chapter "Technical data".The optional heating requires its own operating voltage. You can finddetai

Page 3

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Page 4 - 1 About this document

Fig. 3: Measures against moisture penetrationThe reference plane for the measuring range of the sensors is thesealing surface of the thread or flange.K

Page 5 - 2 For your safety

keep in mind that measurement down to the tip of the probe is notpossible. The exact value of the min. distance (lower dead band) isstated in chapter

Page 6 - 2.6 CE conformity

Fig. 5: Lateral loadExtreme vibration caused by the system, e.g. due to agitators orturbulence in the vessel from inflowing medium, can cause the coaxp

Page 7 - 3 Product description

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 8 - 3.2 Principle of operation

In systems without potential equalisation, connect the cable screendirectly to ground potential at the power supply unit and at the sensor.In the conn

Page 9

7 Insert the wire ends into the open terminals according to the wiringplanFig. 6: Connection steps 6 and 78 Press down the opening levers of the termi

Page 10 - 3.3 Operation

I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 7: Electronics and connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inte

Page 11 - 4 Mounting

132Display1 2 5 6 7 8I2CFig. 9: Electronics compartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 12 - 32306-EN-120329

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13

I2C11 2Fig. 11: Wiring plan, double chamber housing1 Voltage supply, signal output5.5 Wiring plan - version IP 66/IP 68, 1 bar12Fig. 12: Wire assignme

Page 14

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 15 - 5 Connecting to power supply

Fig. 13: Insert indicating and adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous me

Page 16 - 5.2 Connection procedure

6.3 Adjustment system2311.1Fig. 14: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mo

Page 17

6.4 Setup stepsAfter VEGAFLEX 67 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30seco

Page 18

Dielectric valueUpper medium0003 Enter the dielectric figure (DK value) of the upper medium andconfirm with [OK].Save the settings with [OK] and move to

Page 19

ApplicationLiquidStandard(dielectric figure ≥ 2)Depending on the dielectric figure (dielectric figure or εr), measuredproducts can have a different reflect

Page 20

2 Select the menu item "Service" with [->] and confirm with [OK].Now the menu item "False signal suppression" is displayed.3 Con

Page 21 - 6.1 Short description

l PINl Sensor length/Sensor typel False signal suppressionCopy sensor dataCopy sensor data?Basic adjustmentIf the function "Reset" is carrie

Page 22

6.5 Menu schematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Upper mediumDielectric figure of the uppermediumenter/calculate1.2M

Page 23 - 6.3 Adjustment system

8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .348.2 Remove interferences. . . . . . .

Page 24 - 6.4 Setup steps

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Sensor5.00 m(d)Rod4.2SimulationStart simulation?4.3ResetSelect reset?4.4Unit of measurementm(

Page 25

6.6 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operatinginstructions manual, and archiving them afterwa

Page 26

7 Set up with PACTware and other adjustmentprograms7.1 Connect the PC312Fig. 15: Connection of the PC via VEGACONNECT directly to the sensor1 USB cabl

Page 27 - Linearisation curve

Necessary components:l VEGAFLEX 67l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustmen

Page 28

8 Maintenance and fault rectification8.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.8.2 Remov

Page 29 - 6.5 Menu schematic

Error Cause RectificationInstrument doesnot appear duringconnection setupProfibus DP cab-le pole-reversedCheck cable and correct, if necessaryIncorrect

Page 30

8.3 Exchanging the electronics moduleIf the electronics module is defective, it can be replaced by the user.In Ex applications only one instrument and

Page 31

At "www.vega.com/downloads" go to "Software". Select under "plicssensors and instruments", "Firmware updates"

Page 32 - 7.1 Connect the PC

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 33

10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting PFA and TFM PTFE 1600

Page 34 - 8.2 Remove interferences

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35

- Rod: ø 10 mm (0.394 in) approx. 620 g/m (6.7 oz/ft)- Cable: ø 4 mm (0.157 in) approx. 80 g/m (0.86 oz/ft)- Gravity weight 325 g (11.5 oz)Insulation

Page 36 - 8.4 Software update

2453124531Fig. 17: Measuring ranges of the VEGAFLEX 67 - rod and cable version1 Reference plane2 Probe length3 Measuring range (default setting refers

Page 37 - 8.5 Instrument repair

10 m (32.82 ft)11 m (36.09 ft)12 m (39.37 ft)13 m (42.65 ft)14 m (45.93 ft)15 m (49.21 ft)16 m (52.49 ft)17 m (55.77 ft)18 m (59.06 ft)23 m (75.46 ft)

Page 38 - 9 Dismounting

TSd1h1h2d21L2L1Fig. 19: Interface measurement (interface is between L1 and L2)1 Reference planed1 Distance to the interface (Secondary Value 2)d2 Dist

Page 39 - 10 Supplement

considerably on t he application. Hard and fastaccuracy specifications are thus not available.Deviation see diagramsThe accuracy values of the diagrams

Page 40

L015 mm(0.591")-15 mm(-0.591")10 mm(0.394")-10 mm(-0.394")0,35 m(13.78")0,2 m(7.874")0,2 m(7.874")0,05 m(1.969"

Page 41

0°C(32°F)40°C(104°F)20°C(58°F)60°C(140°F)80°C(176°F)50°C(122°F)-40°C(-40°F)100°C(212°F)150°C(302°F)12Fig. 22: Ambient temperature -

Page 42

Spring-loaded terminals for wire cross-sec-tion< 2.5 mm² (AWG 14)Electromechanical data - version IP 66/IP 68 (1 bar)Cable entry- Single chamber ho

Page 43

Power supply by/max. number of sensors- H1 power supply max. 32 (max. 10 with Ex)Electrical protective measuresProtection, depending on housing versio

Page 44

10.2 Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block (TB) and Function block (FB) in

Page 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46

Diagram, adjustmentThe following illustration shows the function of the adjustment.Secondary_value_1CalibrationLowest PointCalibrationHighest PointSen

Page 47

l secondary_value_2- This is the distance value (sensor_value) with the status of the transducer block- It is the input for the AIFB when CHANNEL = 3

Page 48

- Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit isdefined in "level_unit"- When writing

Page 49 - 10.2 Foundation Fieldbus

10.3 DimensionsThe following dimensional drawings represent only an extract of thepossible versions. Detailed dimensional drawings can be downloadedon

Page 50

Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm (4.72")~ 105 mm (4.13")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.31

Page 51

VEGAFLEX 67LLL115 mm (4.53")69,4 mm(2.73")ø 10 mm(0.39")ø 20 mm(0.79")ø 4 mm(0.16")70 mm(2.76")71,4 mm(2.81")1 23 4

Page 52

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 53 - 10.3 Dimensions

VEGAFLEX 67 • Foundation Fieldbus 5710 Supplement32306-EN-120329

Page 54

58 VEGAFLEX 67 • Foundation Fieldbus10 Supplement32306-EN-120329

Page 55

VEGAFLEX 67 • Foundation Fieldbus 5910 Supplement32306-EN-120329

Page 56 - 10.5 Trademark

2.5 Safety label on the instrumentThe safety approval markings and safety tips on the device must beobserved.2.6 CE conformityThis device fulfills the

Page 57

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 58

3 Product description3.1 StructureThe scope of delivery encompasses:l Level sensor VEGAFLEX 67l Documentation- this operating instructions manual- Ope

Page 59

l Article numberl Serial numberl Technical datal Article numbers, documentationWith the serial number, you can access the delivery data of theinstrume

Page 60 - ISO 9001

TS d1 h1 h2 d2 1 L2 L1 Fig. 2: Interface measurement1 Reference planed1 Distance to the interfaced2 Distance to the levelTS Thickness of the upper med