Vega VEGAFLEX 67 (-200…+400°C) Foundation Fieldbus User Manual

Browse online or download User Manual for Equipment Vega VEGAFLEX 67 (-200…+400°C) Foundation Fieldbus. VEGA VEGAFLEX 67 (-200…+400°C) Foundation Fieldbus User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instructions

Operating InstructionsVEGAFLEX 67-200 … +400 °CFoundation FieldbusDocument ID:32314Guided Microwave

Page 2 - Contents

TSd1h1h2d21L2L1Fig. 2: Interface measurement1 Reference planed1 Distance to the interfaced2 Distance to the levelTS Thickness of the upper medium (d1

Page 3

The data for power supply are specified in chapter "Technical data".The optional heating requires its own operating voltage. You can finddetai

Page 4 - 1 About this document

4 Mounting4.1 General instructionsMake sure that all parts of the instrument exposed to the process, inparticular the sensor element, process seal and

Page 5 - 2 For your safety

Fig. 3: Measures against moisture penetrationThe reference plane for the measuring range of the sensors is thesealing surface of the thread or flange.K

Page 6 - 2.5 CE conformity

keep in mind that measurement down to the tip of the probe is notpossible. The exact value of the min. distance (lower dead band) isstated in chapter

Page 7 - 3 Product description

more than 1 m (3.281 in) length, you must secure the probe byfastening a suitable insulated brace or guy directly above the end ofthe rod.If there is

Page 8 - 3.2 Principle of operation

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 9

In systems without potential equalisation, connect the cable screendirectly to ground potential at the power supply unit and at the sensor.In the conn

Page 10 - 32314-EN-120329

7 Insert the wire ends into the open terminals according to the wiringplanFig. 7: Connection steps 6 and 78 Press down the opening levers of the termi

Page 11 - 3.3 Operation

I²C34512DisplayTyp:1 2 5 6 7 8 BusSim.Fig. 8: Electronics and connection compartment, single chamber housing1 Plug connector for VEGACONNECT (I²C inte

Page 12 - 4 Mounting

Contents1 About this document1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . .

Page 13

132Display1 2 5 6 7 8I2CFig. 10: Electronics compartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection

Page 14

I2C11 2Fig. 12: Wiring plan, double chamber housing1 Voltage supply, signal output5.5 Wiring plan - version IP 66/IP 68, 1 bar12Fig. 13: Wire assignme

Page 15

6 Set up with the indicating and adjustmentmodule PLICSCOM6.1 Short descriptionThe indicating and adjustment module is used for measured valuedisplay,

Page 16 - 5 Connecting to power supply

Fig. 14: Insert indicating and adjustment moduleNote:If you intend to retrofit the instrument with an indicating and adjustmentmodule for continuous me

Page 17 - 5.2 Connection procedure

6.3 Adjustment system2311.1Fig. 15: Indicating and adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mo

Page 18

6.4 Setup stepsAfter VEGAFLEX 67 is connected to voltage supply or after voltagerecurrence, the instrument carries out a self-check for approx. 30seco

Page 19

Dielectric valueUpper medium0003 Enter the dielectric figure (DK value) of the upper medium andconfirm with [OK].Save the settings with [OK] and move to

Page 20

ApplicationLiquidStandard(DK ≥ 2)Measured products have different reflective properties that depend onthe dielectric figure (dielectric constant). For th

Page 21

1 Move from the measured value display to the main menu bypushing [OK].2 Select the menu item "Service" with [->] and confirm with [OK].No

Page 22 - 6.1 Short description

The following safety-relevant data are not read out or written:l HART model PINl Sensor length/Sensor typel False signal suppressionCopy sensor dataCo

Page 23

8 Maintenance and fault rectification8.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .358.2 Remove interferences. . . . . . .

Page 24 - 6.3 Adjustment system

6.5 Menu schematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Upper mediumDielectric figure of the uppermediumenter/calculate1.2M

Page 25 - 6.4 Setup steps

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Sensor5.00 m(d)Rod4.2SimulationStart simulation?4.3ResetSelect reset?4.4Unit of measurementm(

Page 26

6.6 Saving the parameter adjustment dataWe recommended noting the adjusted data, e.g. in this operatinginstructions manual, and archiving them afterwa

Page 27

7 Set up with PACTware and other adjustmentprograms7.1 Connect the PC312Fig. 16: Connection of the PC via VEGACONNECT directly to the sensor1 USB cabl

Page 28 - Linearisation curve

Necessary components:l VEGAFLEX 67l PC with PACTware and suitable VEGA DTMl VEGACONNECTl Power supply unit or processing system7.2 Parameter adjustmen

Page 29

8 Maintenance and fault rectification8.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.8.2 Remov

Page 30 - 6.5 Menu schematic

Error Cause RectificationIncorrect termina-tionCheck termination at the beginningand end points of the bus and termin-ate, if necessary, according to t

Page 31

If there is no electronics module available on site, one can be orderedfrom the VEGA agency serving you.The new electronics module must be loaded with

Page 32

Connect the signal conditioning instrument to power supply andprovide the connection from the PC to the instrument via the interfaceadapter. Start PAC

Page 33 - 7.1 Connect the PC

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process conditions suchas e.g. pressure in the vessel, high temper

Page 34

1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as

Page 35 - 8.2 Remove interferences

10 Supplement10.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts - version -200 … +400°C (-328 … +752°

Page 36

- Rod: ø 16 mm (0.63 in) approx. 1600 g/m (17 oz/ft)- Cable: ø 6 mm (0.236 in) approx. 170 g/m (1.8 oz/ft)- Gravity weight approx. 730 g (25.8 oz)Prob

Page 37 - 8.4 Software update

24351Fig. 18: Measuring ranges of VEGAFLEX 67 - coax version1 Reference plane2 Probe length3 Measuring range (default setting refers to the measuring

Page 38 - 8.5 Instrument repair

2435124531Fig. 19: Measuring ranges of the VEGAFLEX 67 - rod and cable version1 Reference plane2 Probe length3 Measuring range4 Upper dead band (see d

Page 39 - 9 Dismounting

10 m (32.82 ft)11 m (36.09 ft)12 m (39.37 ft)13 m (42.65 ft)14 m (45.93 ft)15 m (49.21 ft)16 m (52.49 ft)17 m (55.77 ft)18 m (59.06 ft)23 m (75.46 ft)

Page 40 - 10 Supplement

TSd1h1h2d21L2L1Fig. 21: Interface measurement (interface is between L1 and L2)1 Reference planed1 Distance to the interface (Secondary Value 2)d2 Dist

Page 41

interface.Depending on the installation conditions, there canbe deviations which can be rectified with anadaptation of the adjustment or a change of th

Page 42

L0-10 mm (-0.394")10 mm (0.394")0,1 m (3.937")0,15 m(1.968")1 1Fig. 24: Deviation VEGAFLEX 67 in coax version1 Dead zone - no meas

Page 43

21-100°C(-148°F)-200°C(-328°F)100 bar(1450 psig)200 bar(2900 psig)300 bar(4350 psig)400 bar(5800 psig)380 bar(5510 psig)350 bar(5070 psig)0°C(32°F)200

Page 44

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry/plug4)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable: ø

Page 45

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist

Page 46

- Min. bending radius 25 mm (0.984 in) with 25 °C (77 °F)- Diameter approx. 8 mm (0.315 in)- Colour - standard PE Black- Colour - standard PUR Blue- C

Page 47

ApprovalsInstruments with approvals can have different technical data depending on the version.That's why the associated approval documents have t

Page 48

10.2 Foundation FieldbusBlock diagram, measured value processingThe following illustration shows the Transducer Block (TB) and Function block (FB) in

Page 49

Diagram, adjustmentThe following illustration shows the function of the adjustment.Secondary_value_1CalibrationLowest PointCalibrationHighest PointSen

Page 50

l secondary_value_2- This is the distance value (sensor_value) with the status of the transducer block- It is the input for the AIFB when CHANNEL = 3

Page 51

- Min./Max. adjustment: this is the value of level at "Calibration Lowest Point". The unit isdefined in "level_unit"- When writing

Page 52 - 10.2 Foundation Fieldbus

10.3 DimensionsThe following dimensional drawings represent only an extract of thepossible versions. Detailed dimensional drawings can be downloadedon

Page 53

Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm (4.72")~ 105 mm (4.13")116 mm (4.57")~ 150 mm (5.91")ø 84 mm (3.31

Page 54

VEGAFLEX 67, rod, cable version (-200 … +400 °C/-328 … +752 °F)SW60G1½ /1½ NPTø 16mm(5/8")ø 30mm(1 3/16")ø 6mm(15/64")L292mm (11 1/2&qu

Page 55

VEGAFLEX 67, coax version (-200 … +400 °C/-328 … +752 °F)G1½ / 1½ NPT ø 42,4 mm(1.67")L 292 mm (11.45")57 mm(2.24")35 mm(1.38")SW

Page 56 - 10.3 Dimensions

2.5 CE conformityThis device fulfills the legal requirements of the applicable ECguidelines. By attaching the CE mark, VEGA provides a confirmationof su

Page 57 - 112 mm (4.41")

10.4 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only

Page 58

VEGAFLEX 67 • Foundation Fieldbus 6110 Supplement32314-EN-120329

Page 59

62 VEGAFLEX 67 • Foundation Fieldbus10 Supplement32314-EN-120329

Page 60 - 10.5 Trademark

VEGAFLEX 67 • Foundation Fieldbus 6310 Supplement32314-EN-120329

Page 61

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 62

3 Product description3.1 StructureThe scope of delivery encompasses:l Level sensor VEGAFLEX 67l Documentation- this operating instructions manual- Ope

Page 63

123Fig. 1: VEGAFLEX 67 - cable version with plastic housing1 Housing cover with integrated indicating and adjustment module (optional)2 Housing with e

Page 64 - ISO 9001

It is designed for industrial use in all areas of process technology andcan be used in liquids.High frequency microwave impulses are guided along a st