Fig. 2: Measures
against moisture penetration
The reference plane for the measuring range of the sensors is the
sealing surface of the thread or ange.
Keep in mind that a min. distance must be maintained below the
reference plane and p ossibly also at the end of the probe -
measurement in these areas is not possible (dead band). Keep in mind
that the cable length cannot be used all the way to the end because
measurement in the area of the gravity weight is not possible. These
dead bands are listed in chapter "Technical data". Keep in mind for the
adjustment that the default setting for the measuring range refers to
water.
The process tting must be sealed if there is gauge or low pressure in
the vessel. Before use, check if the seal material is resistant against
the measured product and the process temperature.
The max. permissible pressure is specied in chapter "Technical data"
or on the type label of the sensor.
4.2 Mounting instructions
Mount VEGAFLEX 62 in such a way that the distance to vessel
installations or to the vessel wall is at least 300 mm (12 in).
During operation, the probe must not touch any installations or the
vessel wall. If necessary, fasten the probe end.
In vessels with conical bottom it can be advantageous to mount the
sensor in the center of the vessel, as measurement is then possible
down to the lowest point of the bottom. When using the cable version,
Measuring range
Pressure
Mounting position
VEGAFLEX 62 Foun
dation Fieldbus 11
4 M
ounting
31840-EN-100426