Operating InstructionsVEGADIS 175Document ID:24386Indicationandadjustment
5 Connect to the signal circuit5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absenc
1 2 3 4 + – 12Fig. 3: Wiring plan VEGADIS 175 to activesensors1 To the sensor2 Internal bridge1 2 3 4 + – – + 312Fig. 4: Wiringplan VEGADIS 175 topa
6 Setup6.1 Indicationand adjustmentVEGADIS 175OK321Fig. 5: Adjustment elements of VEGADIS 1751 LC display2 Adjustmentkey3 Selection keysLC displayl Ac
VEGADIS 175OK > 3s > 3s+++-67123445OKOKOKOKOK+-+-+-Fig. 6: Adjustment system of VEGADIS 1751 Access to the adjustment menu2 Selection of adjustm
Parameter Meaning Adjustment options FactorysettingsdI dP Decimal point: Positionsafterthe comma of thenumerical indicationSelection range: 0 up to 4p
1 Push the "OK" keylonger than three seconds to get to theadjustment menu. The display shows again: "dI dP"2 Push the "OK&quo
7 Maintenance and fault rectification7.1 MaintenanceIf the instrument is used properly, no special maintenance is requiredin normal operation.7.2 Remov
Error code Cause RectificationE090 Loop currenttoo small. Tosave the adjustment data,there must be at least 3.6 mAon the input.Check measurement loopE1
You can download a return form (23 KB) from our Internet homepagewww.vega.com under: "Downloads - Forms and certificates - Repairform".By doi
8 Dismounting8.1 Dismounting stepsTake note of chapters "Mounting" and "Connecting to power supply"and carry out the listed steps
Contents1 About thisdocument1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . .
9 Supplement9.1 TechnicaldataGeneral dataMaterials- Housing front Aluminium die-casting- Housing Sheet steel galvanized- Rear of the housing plastic A
DeviationCurrent measurement error, referring to thefinal value< 0.1 %Temperature drift < 0.1 %/10 KElectrical protective measuresProtection rati
9.2 DimensionsVEGADIS 1751 2 3 4-+OKVEGADIS 17596 mm (3 25/32")48 mm(1 57/64")91 mm (3 37/64")91 mm (3 37/64")80 mm (3 5/32")
9.3 Industrial property rightsVEGA product lines are global protected by industrial property rights.Further information see http://www.vega.com.Only i
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9
Editing status: 2012-05-29VEGADIS 175 3Contents24386-EN-120531
1 About this document1.1 FunctionThis operating instructions manual provides all the information youneed for mounting, connection and setup as well as
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manual must becarried out only by trained specialist
The instrument is designed for us e in an industrial environment.Nevertheless, electromagnetic interference from electrical conductorsand radiated emi
3 Product description3.1 StructureThe scope of delivery encompasses:l Digital indicating instrument VEGADIS 175l Documentation- this operating instruc
Unless otherwise indicated, the packages must be stored only underthe following conditions:l Not in the openl Dry and dust freel Not exposed to corros
4 Mounting4.1 General instructionsMake sure that there are no vibrations in the mounting place.Protect your instrument against heat, e.g. by other ins