Operating InstructionsPressure transmitter with metallic measuring cellVEGABAR 83Probus PADocument ID: 45037

Page 2 - Contents

103 Product descriptionVEGABAR 83 • Probus PA45037-EN-1311074321Fig. 4: Conguration of the METEC® measuring cell1 Process diaphragm2 Isolating liq

Page 3

113 Product descriptionVEGABAR 83 • Probus PA45037-EN-131107The delivery must be checked for completeness and possible transit damage immediately at

Page 4 - 1 About this document

123 Product descriptionVEGABAR 83 • Probus PA45037-EN-131107You can nd further information in the supplementary instructions "Adapter DISADAPT&

Page 5 - 2 For your safety

134 MountingVEGABAR 83 • Probus PA45037-EN-1311074 Mounting4.1 General instructions to use the instrumentMake sure that all parts of the instrument

Page 6 - 2.7 NAMUR recommendations

144 MountingVEGABAR 83 • Probus PA45037-EN-13110712Fig. 5: Temperature ranges1 Process temperature2 Ambient temperature4.2 Ventilation and pressur

Page 7 - 3 Product description

154 MountingVEGABAR 83 • Probus PA45037-EN-1311071 2 34 4 4Fig. 6: Position of the lter element - non-Ex, Ex-ia version1 Housing plastic, stainless

Page 8 - 3.2 Principle of operation

164 MountingVEGABAR 83 • Probus PA45037-EN-131107The lter element is mounted into the electronics housing. It has the following functions:• Ventilat

Page 9

174 MountingVEGABAR 83 • Probus PA45037-EN-131107123Fig. 10: Measurement setup for process pressure measurement of gases in pipelines1 VEGABAR 832

Page 10 - 3 Product description

184 MountingVEGABAR 83 • Probus PA45037-EN-13110714321234Fig. 11: Measurement setup with process pressure measurement of gases in pipelines1 VEGABAR

Page 11

194 MountingVEGABAR 83 • Probus PA45037-EN-131107312Fig. 12: Measurement setup for process pressure measurement of liquids in pipelines1 VEGABAR 832

Page 12

2ContentsVEGABAR 83 • Probus PA45037-EN-131107Contents1 About this document1.1 Function ...

Page 13 - 4 Mounting

204 MountingVEGABAR 83 • Probus PA45037-EN-1311074.5 External housing12345Fig. 14: Setup process assembly, external housing1 Process assembly2 Con

Page 14

215 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-1311075 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the

Page 15

225 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-131107ceramic capacitor (e.g. 1 nF, 1500 V). Low-frequency potential equali-sation curre

Page 16

235 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-131107Fig. 17: Connection steps 5 and 6 - Double chamber housing6. Insert the wire ends

Page 17

245 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-1311075005162738490516273849101678Bus234512+( )(-)1Fig. 18: Electronics and connection

Page 18

255 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-131107Bus512+( )(-)6782341Fig. 20: Connection compartment, double chamber housing1 Vol

Page 19 - 4.4 Level measurement

265 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-131107+Bus212( )(-)1Fig. 22: Connection compartment, double chamber housing Ex d1 Volt

Page 20 - (0.14")

275 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-131107Contact pin Colour connection ca-ble in the sensorTerminal, electronics modulePin

Page 21 - 5 Connecting to power supply

285 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-131107123512( )+(-)6784...20mAFig. 27: Electronics and connection compartment1 Electro

Page 22 - 5.2 Connecting

295 Connecting to power supplyVEGABAR 83 • Probus PA45037-EN-1311075005162738490516273849101678Bus234512+( )(-)1Fig. 29: Electronics and connection

Page 23 - 5.3 Single chamber housing

3ContentsVEGABAR 83 • Probus PA45037-EN-1311078.1 DD adjustment programs ...

Page 24 - 5 Connecting to power supply

306 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-1311076 Set up with the display and adjustment module6.1 Insert dis

Page 25

316 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-1311071 2Fig. 31: Insertion of the display and adjustment module into

Page 26

326 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107 – Conrm selected menu – Edit parameter – Save value• [-] key:

Page 27

336 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-1311074. UnitsIn this menu item you determine the adjustment and temp

Page 28

346 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107The main menu is divided into ve sections with the following f

Page 29

356 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107In the menu item "Sensor TAG" you edit a twelve digit

Page 30

366 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107Unit of measurement:If the level should be adjusted in a height

Page 31 - 6.2 Adjustment system

376 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107Save your settings with [OK] and move with [ESC] and [->] to

Page 32

386 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-1311071. Select the menu item "Setup" with [->] and con

Page 33

396 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107Proceed as follows:1. Select the menu item "Setup" w

Page 34

41 About this documentVEGABAR 83 • Probus PA45037-EN-1311071 About this document1.1 FunctionThis operating instructions manual provides all the info

Page 35

406 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107A linearization is necessary for all vessels in which the vesse

Page 36

416 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107You can change the PIN number under "Additional adjustment

Page 37

426 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107The respective min. and max. measured value is saved in the sen

Page 38

436 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107In delivery status, the PIN is "0000".In this menu it

Page 39

446 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107Menu item Parameter Default valueUnits Unit of measure-mentmbar

Page 40

456 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107Menu item Parameter Default valueCopy in-strument settingsSpeci

Page 41

466 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107In this menu item, you read out the instrument name and the ins

Page 42

476 Set up with the display and adjustment moduleVEGABAR 83 • Probus PA45037-EN-131107into the replacement instrument and the data are likewise writt

Page 43

487 Setup with PACTwareVEGABAR 83 • Probus PA45037-EN-1311077 Setup with PACTware7.1 Connect the PC312Fig. 34: Connection of the PC directly to the

Page 44

497 Setup with PACTwareVEGABAR 83 • Probus PA45037-EN-131107Fig. 35: Example of a DTM viewAll device DTMs are available as a free-of-charge standard

Page 45

52 For your safetyVEGABAR 83 • Probus PA45037-EN-1311072 For your safety2.1 Authorised personnelAll operations described in this operating instruct

Page 46

508 Set up with other systemsVEGABAR 83 • Probus PA45037-EN-1311078 Set up with other systems8.1 DD adjustment programsDevice descriptions as Enhan

Page 47 - 45037-EN-131107

519 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-1311079 Diagnosis, asset management and service9.1 MaintenanceIf the instr

Page 48 - 7 Setup with PACTware

529 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-131107the following tables there are more detailed error messages available

Page 49 - 7 Setup with PACTware

539 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-131107CodeText mes-sageCause RecticationF013no measured value avail-able –

Page 50 - 8 Set up with other systems

549 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-131107CodeText mes-sageCause RecticationF265Measurement function dis-turbe

Page 51 - 9.2 Diagnosis memory

559 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-131107CodeText mes-sageCause RecticationM501Error in the non-active linear

Page 52 - 4 Maintenance - blue

569 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-1311079.5 Calculation of total deviation (according to DIN 16086)The total

Page 53

579 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-131107FT = (0.15 %) x (0.5 + 0.5 x TD)FKl= 0.075 %Fa = 0.15 %Fperf = √((0.1

Page 54

589 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-13110712534Fig. 37: VEGABAR 83 in IP 68 version, 25 bar and lateral cable o

Page 55 - 9.4 Rectify faults

599 Diagnosis, asset management and serviceVEGABAR 83 • Probus PA45037-EN-131107The serial number is stated on the type label of VEGABAR 83 or on the

Page 56 - DIN 16086)

62 For your safetyVEGABAR 83 • Probus PA45037-EN-131107radiated emissions must be taken into account, as is usual with a class A instrument according

Page 57 - IP 68 (25 bar)

6010 DismountingVEGABAR 83 • Probus PA45037-EN-13110710 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process c

Page 58

6111 SupplementVEGABAR 83 • Probus PA45037-EN-13110711 Supplement11.1 Technical dataMaterials and weightsMaterials, wetted (piezoresistive/strain ga

Page 59 - 9.8 Software update

6211 SupplementVEGABAR 83 • Probus PA45037-EN-131107Connection cable, master and slave sensorPE, PURWeightsTotal weight VEGABAR 83 approx. 0.8 … 8 kg

Page 60 - 10 Dismounting

6311 SupplementVEGABAR 83 • Probus PA45037-EN-131107Nominal range Overload capacity, max. pressureOverload capacity, min. pres-sureAbsolute pressure0

Page 61 - 11 Supplement

6411 SupplementVEGABAR 83 • Probus PA45037-EN-131107Adjustment range of the min./max. adjustment relating to the nominal measuring range: Ʋ Percentag

Page 62

6511 SupplementVEGABAR 83 • Probus PA45037-EN-131107Nominal range Overload capacity, max. pressureOverload capacity, min. pres-sureGauge pressure0 …

Page 63

6611 SupplementVEGABAR 83 • Probus PA45037-EN-131107Dynamic behaviour outputRun-up time approx. 10 sDynamic characteristics, depending on medium, tem

Page 64

6711 SupplementVEGABAR 83 • Probus PA45037-EN-131107Accuracy class Non-linearity, hysteresis and re-peatability with TD 1 : 1 up to 5 : 1Non-linearit

Page 65

6811 SupplementVEGABAR 83 • Probus PA45037-EN-131107Nominal measuring range in bar/kPaNominal measuring range in psigIn the compensated temperature r

Page 66

6911 SupplementVEGABAR 83 • Probus PA45037-EN-131107Version Temperature rangeStandard -12 … +150 °C (+10 … +284 °F)High temperature -12 … +180 °C (+1

Page 67

73 Product descriptionVEGABAR 83 • Probus PA45037-EN-1311073 Product description3.1 CongurationThe nameplate contains the most important data for

Page 68

7011 SupplementVEGABAR 83 • Probus PA45037-EN-131107Electromechanical data - version IP 68 (25 bar)Connection cable between IP 68 instrument and exte

Page 69

7111 SupplementVEGABAR 83 • Probus PA45037-EN-131107Interface to the slave sensorData transmission digital (I²C-Bus)Conguration, connection cable 4-

Page 70

7211 SupplementVEGABAR 83 • Probus PA45037-EN-131107Housing material Version IP-protection class NEMA protectionStainless steel, investment castingSi

Page 71

7311 SupplementVEGABAR 83 • Probus PA45037-EN-131107master you can determine the conguration of the cyclical data telegram with these modules. The p

Page 72 - Module of the PA sensors

7411 SupplementVEGABAR 83 • Probus PA45037-EN-131107Byte nByte n+1Bit7VZExponentBit62Bit52Bit42Bit32Bit22Bit12Bit02Bit72Bit62Bit52Bit42Bit32Bit22Bit1

Page 73

7511 SupplementVEGABAR 83 • Probus PA45037-EN-131107Status code Description according to ProbusstandardPossible cause0 x 89 good (non-cascade) - ac

Page 74

7611 SupplementVEGABAR 83 • Probus PA45037-EN-131107Aluminium housing21ø 86 mm(3.39")~ 116 mm(4.57")116 mm(4.57")M20x1,5M20x1,5/½ NPT~

Page 75 - 11.3 Dimensions

7711 SupplementVEGABAR 83 • Probus PA45037-EN-131107Stainless steel housing~ 69 mm(2.72")ø 79 mm(3.11")117 mm(4.61")M20x1,5/½ NPT~ 59

Page 76

7811 SupplementVEGABAR 83 • Probus PA45037-EN-131107Stainless steel housing in protection IP 69K104 mm(4.1")M20x1,5/½ NPT~ 59 mm(2.3")ø 80

Page 77

7911 SupplementVEGABAR 83 • Probus PA45037-EN-131107External housing with IP 68 version1234582 mm(3.23")80 mm(3.15")108 mm(4.25")41,6

Page 78 - (4.1")

83 Product descriptionVEGABAR 83 • Probus PA45037-EN-131107This operating instructions manual applies to the following instrument versions:• Hardware

Page 79

8011 SupplementVEGABAR 83 • Probus PA45037-EN-131107VEGABAR83,threadedttingnotfront-ush23 mm(0.91")G ½ 63 mm(2.48")3 mm(0.12")ø

Page 80

8111 SupplementVEGABAR 83 • Probus PA45037-EN-131107VEGABAR83,threadedttingfront-ushDAC9DA- 180°C/200°CLU LW78 mm(3.07")22 mm(0.87")ø

Page 81

8211 SupplementVEGABAR 83 • Probus PA45037-EN-131107VEGABAR83,hygienictting150°C(piezoresistive/straingaugemeasuringcell)FRESARL .LPAA79 mm

Page 82

8311 SupplementVEGABAR 83 • Probus PA45037-EN-131107VEGABAR83,hygienictting150°C(METEC® measuring cell)78 mm(3.07")78 mm(3.07")ø 64

Page 83

8411 SupplementVEGABAR 83 • Probus PA45037-EN-131107VEGABAR83,angeconnection150°C(piezoresistive/straingaugemeasuringcell)5.91"6.50&qu

Page 84

8511 SupplementVEGABAR 83 • Probus PA45037-EN-131107VEGABAR83,angeconnection180°C/200°C(METEC® measuring cell)5.91"6.50"7.87"4

Page 85 - measuring cell)

8611 SupplementVEGABAR 83 • Probus PA45037-EN-13110711.4 Industrial property rightsVEGA product lines are global protected by industrial property ri

Page 86 - 11.5 Trademark

87INDEXVEGABAR 83 • Probus PA45037-EN-131107INDEXAAdjust Date/Time 43Adjustment – Level 39 – Process pressure 37, 38 – System 32 – Unit 35Adjust

Page 87

Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany45037-EN-131107All statements concerning scope of delivery, application, practi

Page 88 - Printing date:

93 Product descriptionVEGABAR 83 • Probus PA45037-EN-131107• Gauge pressure• Absolute pressure• VacuumMeasured products are gases, vapours and liquid