Vega VEGABAR 54 Foundation Fieldbus User Manual

Browse online or download User Manual for Equipment Vega VEGABAR 54 Foundation Fieldbus. VEGA VEGABAR 54 Foundation Fieldbus User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - VEGABAR 54

Operating InstructionsPressure transmitter with MINI-CERTEC® measuring cellVEGABAR 54Foundation FieldbusDocument ID: 36732

Page 2 - Contents

103 Product descriptionVEGABAR 54 • Foundation Fieldbus36732-EN-130321The packaging of standard instruments consists of environment-friendly, recyclab

Page 3

113 Product descriptionVEGABAR 54 • Foundation Fieldbus36732-EN-130321Youcanndadditionalinformationinthesupplementaryinstructionsmanual&quo

Page 4 - 1 About this document

124 MountingVEGABAR 54 • Foundation Fieldbus36732-EN-1303214 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in dir

Page 5 - 2 For your safety

134 MountingVEGABAR 54 • Foundation Fieldbus36732-EN-13032121212112Fig. 4: Position of the lter element1 Filter element2 Blind plugCaution:Duetot

Page 6 - 2 For your safety

144 MountingVEGABAR 54 • Foundation Fieldbus36732-EN-1303214.2 Mounting stepsFormountingVEGABAR54,aweldedsocketisrequired.Youcanndthese

Page 7 - 3 Product description

154 MountingVEGABAR 54 • Foundation Fieldbus36732-EN-130321Tip:Mount the wall mounting plate so that the cable entry of the socket housing points down

Page 8 - 3.2 Principle of operation

165 Connecting to power supplyVEGABAR 54 • Foundation Fieldbus36732-EN-1303215 Connecting to power supply5.1 Preparing the connectionAlways keep in

Page 9 - 3.3 Operation

175 Connecting to power supplyVEGABAR 54 • Foundation Fieldbus36732-EN-130321low frequency potential equalisation currents are thus suppressed, butth

Page 10 - 3 Product description

185 Connecting to power supplyVEGABAR 54 • Foundation Fieldbus36732-EN-130321Fig. 7: Connection steps 6 and 7Proceed as follows:1. Loosen the four sc

Page 11

195 Connecting to power supplyVEGABAR 54 • Foundation Fieldbus36732-EN-130321Information:The cable gland can be mounted in three positions each displa

Page 12 - 4 Mounting

2ContentsVEGABAR 54 • Foundation Fieldbus36732-EN-130321Contents1 About this document1.1 Function ...

Page 13

205 Connecting to power supplyVEGABAR 54 • Foundation Fieldbus36732-EN-130321I2CDisplay112 5 678Fig. 10: Wiring plan, single chamber housing1 Voltage

Page 14 - 4.2 Mounting steps

215 Connecting to power supplyVEGABAR 54 • Foundation Fieldbus36732-EN-130321123Display12I2CFig. 12: Connection compartment, double chamber housing1

Page 15

225 Connecting to power supplyVEGABAR 54 • Foundation Fieldbus36732-EN-1303215.6 Wiring plan, external housing with version IP 68Fig. 15: VEGABAR 54

Page 16 - 5 Connecting to power supply

235 Connecting to power supplyVEGABAR 54 • Foundation Fieldbus36732-EN-1303211234634125Fig. 17: Connection of the sensor in the housing socket1 Brown

Page 17 - 5.2 Connection procedure

246 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-1303216 Set up with the display and adjustment mod

Page 18 - 5 Connecting to power supply

256 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321Fig. 19: Insert display and adjustment module

Page 19

266 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321 – Save value• [->] key to select: – Menu

Page 20

276 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321The actual measured value is also displayed i

Page 21

286 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321Density0001000kg/dm³6. Enter the requested d

Page 22

296 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321Iftheadjustmentrangesareexceeded,theme

Page 23

3ContentsVEGABAR 54 • Foundation Fieldbus36732-EN-1303218 Maintenanceandfaultrectication8.1 Maintain ...

Page 24 - 6.1 Short description

306 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321The display and adjustment module enables the

Page 25 - 6.3 Adjustment system

316 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321The adjustment unit is thus switched over fro

Page 26 - 6.4 Setup steps

326 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321Proceed as follows:1. Editthembarvaluein

Page 27

336 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321• LanguageThe following safety-relevant data

Page 28 - Selection options: °C, °F

346 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321Default settingLike basic adjustment, but in

Page 29 - 0000.0 mbar

356 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-130321DiagnosticsBasic adjustment 3Display▶Diagnost

Page 30

366 Set up with the display and adjustment module PLICSCOMVEGABAR 54 • Foundation Fieldbus36732-EN-1303216.10 Saving the parameter adjustment dataWe

Page 31

377 Set up with PACTware and other adjustment programsVEGABAR 54 • Foundation Fieldbus36732-EN-1303217 Set up with PACTware and other adjustment prog

Page 32

387 Set up with PACTware and other adjustment programsVEGABAR 54 • Foundation Fieldbus36732-EN-1303217.2 Parameter adjustment with PACTwareFurther se

Page 33

398MaintenanceandfaultrecticationVEGABAR 54 • Foundation Fieldbus36732-EN-1303218 Maintenanceandfaultrectication8.1 MaintainIf the instrumen

Page 34 - 6.5 Menu schematic

41 About this documentVEGABAR 54 • Foundation Fieldbus36732-EN-1303211 About this document1.1 FunctionThis operating instructions manual provides all

Page 35

408MaintenanceandfaultrecticationVEGABAR 54 • Foundation Fieldbus36732-EN-130321Error Cause RecticationMeasured val-ue on the display and adjust

Page 36

418MaintenanceandfaultrecticationVEGABAR 54 • Foundation Fieldbus36732-EN-130321• Fperf: Basic accuracy• Fstab: Long-term drift• FT:Temperature

Page 37 - 7.1 Connect the PC

428MaintenanceandfaultrecticationVEGABAR 54 • Foundation Fieldbus36732-EN-1303218.4 Exchanging the electronics moduleIn case of a defect, the el

Page 38

438MaintenanceandfaultrecticationVEGABAR 54 • Foundation Fieldbus36732-EN-130321Pushthebutton"Update software"andselecttheprevio

Page 39 - 8.2 Rectifyfaults

449 DismountingVEGABAR 54 • Foundation Fieldbus36732-EN-1303219 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous pro

Page 40 - DIN16086)

4510 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-13032110 Supplement10.1 Technical dataGeneral dataParameter, pressure Gauge pressure, absolut

Page 41

4610 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321 Ʋ Transport cover PFAWeight approx.0.8 … 8 kg (1.764 … 17.64 lbs), depending on process

Page 42 - 8.5 Software update

4710 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321Additional output parameter - temperatureProcessingismadeviaoutputsignalHARTmulti

Page 43 - 8.6 Instrument repair

4810 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sure-1 … +25

Page 44 - 9 Dismounting

4910 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sure-7 … +7 p

Page 45 - 10 Supplement

52 For your safetyVEGABAR 54 • Foundation Fieldbus36732-EN-1303212 For your safety2.1 Authorised personnelAll operations described in this operating

Page 46

5010 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321 Ʋ Turn down up to 10 : 1 < 0.15 %/10 KOutside the compensated temperature range:Aver

Page 47

5110 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321 Ʋ Flange 316L PN 40Product temperature depending on the measuring cell seal11)Measuring

Page 48

5210 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321 Ʋ Single chamber housing – 1 x IP 68 cable gland M20 x 1.5; 1 x blind plug M20 x 1.5or

Page 49

5310 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321 Ʋ unassembled IP 20 Ʋ mounted into the sensor without cover IP 40Material Ʋ Housing ABS

Page 50

5410 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321tiSimulateALARMSOutPVFIELD-VALUEMode & StatusPVF-TIMELOW-CUTOFFL-TYPEOUT-SCALEPV-SCA

Page 51

5510 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321• secondary_value_2 – Valueaftermin/max-adjustment.SelectedasinputtoAIFBbysetti

Page 52

5610 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321 – Highest calibrated value. For calibration of the high limit point you give the high m

Page 53

5710 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321Plastic housing~ 69 mm(2.72")ø 79 mm(3.03")112 mm (4.41")M20x1,5/½ NPT~ 8

Page 54 - Parameter list

5810 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321AluminiumhousinginprotectionratingIP66/IP68(1bar)120 mm (4.72")~ 105 mm (4

Page 55

5910 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321StainlesssteelhousinginprotectionratingIP66/IP68(1bar)117 mm (4.61")~ 103

Page 56 - 10.3 Dimensions

62 For your safetyVEGABAR 54 • Foundation Fieldbus36732-EN-1303212.6 CE conformityThisdevicefulllsthelegalrequirementsoftheapplicableECgui

Page 57 - Aluminium housing

6010 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-13032112368 mm(2.68")68 mm(2.68")92 mm(3.62")42mm(1.65")40mm(1.57")11

Page 58 - 36732-EN-130321

6110 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321VEGABAR54,threadedttingGAGDGB22 mm(0.87")59 mm(2.32")40 mm(1.58")44 m

Page 59

6210 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321VEGABAR54,hygienictting1RI44,5 mm(1.75")G1 AGK67,5 mm(2.66")ø 52 mm (2.05

Page 60

6310 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321VEGABAR54,hygienictting2ø 62,5 mm(2.46")45 mm(1.77")REFig. 36: VEGABAR 54

Page 61 - SW 32 mm

6410 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321VEGABAR54,angeconnection1DB, FZ, DA, F1d4kd2Dfb50 mm(1.97")DNmmPN DkbDB 15 40

Page 62 - VEGABAR54,hygienictting1

6510 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321VEGABAR54,angeconnection2d2d4kDfbFA47,8 mm(1 7/8")2 43/64" 5/64"4xø

Page 63 - VEGABAR54,hygienictting2

6610 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321VEGABAR54,connectionforpaperindustry145,5 mm(1 51/64")ø 26,3 mm (1 1/32"

Page 64

6710 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-130321VEGABAR54,connectionforpaperindustry2VP VR ø 29,3 mm (1 5/32")30 mm(1 3/16&qu

Page 65

6810 SupplementVEGABAR 54 • Foundation Fieldbus36732-EN-13032110.4 Industrial property rightsVEGA product lines are global protected by industrial pr

Page 66

69INDEXVEGABAR 54 • Foundation Fieldbus36732-EN-130321INDEXAAccessories – Display and adjustment module 10 – External display and adjustment unit 10

Page 67

73 Product descriptionVEGABAR 54 • Foundation Fieldbus36732-EN-1303213 Product description3.1 CongurationThe scope of delivery encompasses:• VEGABA

Page 68 - 10.5 Trademark

70NotesVEGABAR 54 • Foundation Fieldbus36732-EN-130321

Page 69

71NotesVEGABAR 54 • Foundation Fieldbus36732-EN-130321

Page 70

Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36732-EN-130321All statements concerning scope of delivery, application, practi

Page 71

83 Product descriptionVEGABAR 54 • Foundation Fieldbus36732-EN-1303212113105436789111214Fig. 2: Layout of the type label (example)1 Instrument type2

Page 72 - Printing date:

93 Product descriptionVEGABAR 54 • Foundation Fieldbus36732-EN-130321The CERTEC® measuring cell is also equipped with a temperature sensor. The temper