Vega VEGAVIB 67 - two-wire User Manual

Browse online or download User Manual for Equipment Vega VEGAVIB 67 - two-wire. VEGA VEGAVIB 67 - two-wire User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - Operating Instructions

Operating InstructionsVEGAVIB 67with two-wire output

Page 2 - Contents

l signal lamp for indication of the switching condition (green/red)l potentiometer for adaptation to the product densityl mode switch for selection of

Page 3

4 Mounting4.1 GeneralIn general, VEGAVIB 67 can be mounted in any position. Theinstrument must be mounted in such a way that the vibratingelement is a

Page 4 - 1 Sequence

Warning:The housing must not be used to screw in the instrument!Applying tightening force on the housing can damage itsinternal mechanical parts.To sc

Page 5 - 2 For your safety

Fig. 3: Inflowing materialVEGAVIB 67 can be mounted with a lock fitting for heightadjustment. Take note of the pressure information of the lockfitting.Th

Page 6 - 2.8 Manufacturer declaration

ddd6d6Fig. 4: Filling and emptying centereddd6123Fig. 5: Filling in the center, emptying laterally1 VEGAVIB 672 Emptying opening3 Filling opening14 VE

Page 7

To minimise flow resistance caused by the tuning fork,VEGAVIB 67 should be mounted in such a way that thesurfaces of the fork are parallel to the produ

Page 8 - 3 Product description

5 Connecting to power supply5.1 Preparing the connectionAlways observe the following safety instructions:l Connect only in the complete absence of lin

Page 9 - 3.3 Adjustment

3 Remove approx. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires4 Insert the cable into t

Page 10 - 3.4 Storage and transport

14442 3Fig. 9: Material versions, single chamber housing1 Plastic (not with EExd)2 Aluminium3 Stainless steel (not with EExd)4 Filter element for pres

Page 11 - 4 Mounting

If the mode switch of VEGAVIB 67 is correctly set to "max.",the control lamp on VEGAVIB 67 lights.l red - with submerged vibrating elementl

Page 12 - 4.2 Mounting information

Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...

Page 13 - 29298-EN-060508

6 Set up6.1 GeneralThe numbers in brackets refer to the following illustrations.On the electronics module you will find the following indicatingand adj

Page 14

6.2 Adjustment elements51234Fig. 13: Oscillator VB60Z - two-wire output1 Potentiometer for switching point adaptation2 DIL switch for mode adjustment3

Page 15

min.-min.detection or dry run detection) on the signalconditioning instrument.When used on a control system, the following values apply:l Mode min.- V

Page 16 - 5 Connecting to power supply

Mode on thesensorLevel Signal current -SensorSignal lamp -sensorFault signal(min./max. mode)any <2.3 mAflashes redVEGAVIB 67 level switch with signa

Page 17

Mode on thesignal condi-tioning in-strumentLevel Signal cur-rent - Sen-sorSignal lamp- sensorSignallamp - sig-nal condi-tioning in-strumentFault signa

Page 18

key is lowered in the front plate of the signal conditioninginstrument. Push the test key for >2 seconds with a suitableobject (screwdriver, pen, e

Page 19

SensorcurrentVEGAVIBLevel re-lay VEGA-TOR A -OverfillprotectionLevel re-lay VEGA-TOR B -Dry runprotectionLEDVEGATORA - OverfillprotectionLEDVEGATORB - D

Page 20 - 6 Set up

7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, VEGAVIB 67 iscompletely maintenance-free.7.2 Fault recti

Page 21 - 6.2 Adjustment elements

à Check if there is buildup on the vibrating element, and ifso, remove it.l Unfavourable installation locationà Mount the instrument at a location in

Page 22 - 6.3 Function chart

21Fig. 15: Loosen the screws1 Electronics module2 Screws (2 pcs.)6 Remove the old oscillator7 Compare the new oscillator with the old one. The type la

Page 23

8 Dismounting8.1 Dismounting procedure ...318.2 Disposal ...319 Supplement9.1 Technical data...

Page 24 - 6.4 Recurring function test

7.4 Instrument repairIf a repair is necessary, please proceed as follows:You can download a return form (23 KB) from our homepagewww.vega.com under: &

Page 25 - 1,5 3 4,5 t/s

8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high

Page 26

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] 9001All stateme

Page 27 - 7.2 Fault rectification

1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th

Page 28

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist

Page 29

2.6 SIL conformityVEGAVIB 67 fulfills the requirements of functional safetyaccording to IEC 61508/IEC 61511. You can find furtherinformation in the supp

Page 30 - 7.4 Instrument repair

l Make sure that the cable gland is tight and strain-relieved.The outer diameter of the connection cable must beadapted to the cable gland. Tighten th

Page 31 - 8 Dismounting

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAVIB 67 level sensorl documentation- this operating instructions manual- S

Page 32 - ISO 9001

Typical applications are overfill and dry run protection. Thanksto its simple and robust measuring system, VEGAVIB 67 isvirtually unaffected by the chem