Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 63Modbus and Levelmaster protocolDocument ID: 41364
103 Product descriptionVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302283 Product description3.1 CongurationThe nameplate contains the
113 Product descriptionVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022821Fig. 5: Position of Modbus and sensor electronics1 Modbus elect
123 Product descriptionVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228can be actually reached depend on the measurement conditions, the
133 Product descriptionVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The interface adapter VEGACONNECT enables the connection of commun
144 MountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302284 Mounting4.1 General instructionsWith instruments with threaded process tt
154 MountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228component. By turning the instrument in the connection ange or mounting boss
164 MountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Fig. 9: Mounting of the radar sensor on vessels with conical bottomDo not mou
174 MountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228dhmax.d50 mm/2"80 mm/3"100 mm/4"150 mm/6"100 mm150 mm250
184 MountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228ing reections from the agitators are saved with the blades in dierent posit
194 MountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302280%100%12345678109Fig.15:Congurationsurgepipe1 Radar sensor2 Marking of
2Quick startVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Quick startThe quick start procedure enables a quick setup with many applica-
204 MountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Constructional requirements on the surge pipe:• Material metal, smoother inn
214 MountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Instructions for orientation:• Note marking of the polarisation plane on the
225 Connecting to power supply and bus systemVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302285 Connecting to power supply and bus system
235 Connecting to power supply and bus systemVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The connection to the display and adjustment
245 Connecting to power supply and bus systemVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022810. Place probably existing display and adj
255 Connecting to power supply and bus systemVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228++power supplyMODBUSD0D1IS GNDUSB1213452of
266 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302286 Set up the sensor with the
276 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302286.3 Adjustment system12Fig.
286 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Setup: Settings, for example,
296 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The following options are ava
3Quick startVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302284. Carry out the adjustment in the menu items "Min. adjustment" an
306 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Stirrer vessel (reactor):• S
316 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228 – With empty vessel, the mea
326 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228dielectric gure. Keep in min
336 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Demonstration:• Adjustment f
346 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228100%0%0,5 m(19.68")5 m(1
356 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302284. Enter the suitable distan
366 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The "Echocurve" sh
376 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228• High sockets• Vessel inst
386 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The menu item "Delete&qu
396 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228• Setup: Resetting of the pa
4ContentsVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Contents1 About this document1.1 Function ...
406 Set up the sensor with the display and adjustment moduleVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228If the instrument is equipped
417 Setting up sensor and Modbus interface with PACTwareVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302287 Setting up sensor and Modbus i
427 Setting up sensor and Modbus interface with PACTwareVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The connection of the PC to the R
437 Setting up sensor and Modbus interface with PACTwareVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Fig.27:ExampleofaDTMviewAll
448 Setup with PACTwareVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302288 Setup with PACTware8.1 Connect the PC312Fig. 28: Connection of
458 Setup with PACTwareVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Fig.29:ExampleofaDTMviewAll device DTMs are available as a f
469 Set up with other systemsVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302289 Set up with other systems9.1 DD adjustment programsDevic
4710 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022810 Diagnosis, Asset Management and service10
4810 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Further echo curves: Up to 10 echo curves can
4910 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The following table shows the codes and text
5ContentsVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022810 Diagnosis, Asset Management and service10.1 Maintenance ...
5010 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228CodeText mes-sageCause Rectication PA DevS-p
5110 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The following table shows the error codes and
5210 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228The below tables show typical examples of app
5310 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228MeasurementerrorduringllingFault descript
5410 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Measurement error during emptyingFault descri
5510 Diagnosis, Asset Management and serviceVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228In both cases, the serial number of the senso
5611 DismountingVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022811 Dismounting11.1 Dismounting stepsWarning:Before dismounting, be aware
5712 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022812 Supplement12.1 Technical dataGeneral data316L corresponds to 1.4404 or
5812 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302283421Fig. 45: Data of the input variable1 Reference plane2 Measured varia
5912 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228 Ʋ Reector Plane plate reector Ʋ False reections Biggest false signal,
61 About this documentVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302281 About this document1.1 FunctionThis operating instructions manua
6012 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Gas phase Temperature Pressure1 bar (14.5 psig)10 bar (145 psig)50 bar (72
6112 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Antenna encapsulation Version Process temperature (measured on the process
6212 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Display and adjustment moduleDisplay element LC display with DOT matrix an
6312 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022812.2 Basics ModbusBus descriptionThe Modbus protocol is a communication p
6412 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Parameters for the bus communicationThe VEGAPULS 63 is preset with the def
6512 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Input registerThe input registers consist of 16 bits. They can only be rea
6612 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Register Name Register Number Type NoteStatus 2100 DWord See Register 100P
6712 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Request:Parameter Length Code/DataFunction Code 1 Byte 0x03Start Address 2
6812 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228FC8 DiagnosticsWith this function code dierent diagnostic functions can b
6912 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Request:Parameter Length Code/DataFunction Code 1 Byte 0x11Response:Parame
72 For your safetyVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302282 For your safety2.1 Authorised personnelAll operations described in
7012 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Parameters for the bus communicationThe VEGAPULS 63 is preset with the def
7112 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Response:Parameter Length Code/DataReport Level (and Temperature) 6 charac
7212 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Set Receive to Transmit DelayRequest:Parameter Length Code/DataSet Receive
7312 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022812.6 CongurationoftypicalModbushostsFisher ROC 809Wiring plan++power
7412 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228ABB Total FlowWiring plan++power supplyMODBUSD0D1IS GNDUSB1 213452offon(
7512 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Thermo Electron AutopilotWiring plan++power supplyMODBUSD0D1IS GNDUSB123
7612 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Bristol ControlWave MicroWiring plan++power supplyMODBUSD0D1IS GNDUSB123
7712 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228ScadaPackWiring plan++power supplyMODBUSD0D1IS GNDUSB13213455213496782of
7812 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228Housing1~ 87 mm (3.43")M16x1,5ø 84 mm(3.31")120 mm (4.72")M
7912 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228VEGAPULS63,angeversion,lowtemperature202 mm (7.95")33ø 44 mm(1.
82 For your safetyVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302282.5 CE conformityThe device fullls the legal requirements of the appl
8012 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228VEGAPULS63,hygienictting1ø 90 mm(3.54")ø 78 mm(3.07")101 mm
8112 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228VEGAPULS63,hygienictting2ISO2852DN 50 / 2"wClamp-Stutzenclamp-so
8212 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228VEGAPULS63,hygienictting31552345516,5 mm(0.65")ø 92 mm(3.62"
8312 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228VEGAPULS63,hygienictting4ø 84 mm(3.31")ø 114 mm(4.49")163 m
8412 SupplementVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-13022812.8 Industrial property rightsЛинии продукции фирмы ВЕГА защищаются по в
85INDEXVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228INDEXAAccessories – Display and adjustment module 12 – Flanges 13 – Interface ad
86NotesVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228
87NotesVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-130228
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany41364-EN-130228All statements concerning scope of delivery, application, practi
92 For your safetyVEGAPULS 63 • Modbus and Levelmaster protocol41364-EN-1302282.9 Environmental instructionsProtection of the environment is one of