Operating InstructionsVEGAFLEX 66-110 … +400 °CProfibus PAGuided Microwave

Page 2

Itis designed for industrial use in all areas of processtechnology and can be used in non-conductive liquids.High frequency microwave pulses are guide

Page 3

3.4 Packaging, transport and storageYour instrument was protected by packaging during transport.Its capacity to handle normal loads during transport i

Page 4 - 1.3 Symbolism used

4 Mounting4.1 General instructionsSelectan installation position you can easily reach formounting and connecting as well as later retrofitting of anind

Page 5 - 2.3 Warning about misuse

Keepin mind that a min. distance must be maintained belowthe reference plane and possibly also at the end of the probe -measurement in these areas is

Page 6 - 2.6 CE conformity

min. distance (lowerdead band) is stated in chapter "Technicaldata".Fig. 3: Vesselwith conical bottomStandpipes or bypass tubes are normally

Page 7 - 2.10 Environ

Keepin mind that buildup can form on the spacers. Strongbuildup can influence the measurement.1Fig. 4: Positionof the spacer1 SpacerNote:Measurement in

Page 8 - 3.1 Configurat

Fig. 5: LateralloadExcessive system vibration or shocks, e.g. caused by agitatorsor turbulence in the vessel (e.g. from fluidisation) can causethe coax

Page 9 - 3.2 Principle of operation

Makesure that with heated vessels the permissible ambienttemperature on the housing is not exceeded. The permissibleambient temperature is stated in c

Page 10 - 3.3 Operation

5 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the following safety instructions:l Connect only in the complete absence o

Page 11 - 3.4 Pack

Caution:Nogrease should be used when screwing the NPT cablegland or steel tube into the threaded insert. Standard greasecan contain additives that cor

Page 12 - 4.1 General instructions

Content1 About this document1.1 Function .. . . . . . . . . . . . . . . . . . . . . . . . . . . .41.2 Target group . . . . . . . . . . . . . . . . . .

Page 13 - 4.2 Mounting instructions

4 Removeapprox. 10 cm (4 in) of the cable mantle, stripapprox. 1 cm (0.4 in) insulation from the ends of theindividual wires5 Insert the cable through

Page 14 - 32764-EN-080716

55551 243Fig. 8: Materialversions, single chamber housing1 Plastic2 Aluminium3 Stainless steel, investment casting4 Stainless steel, electro-polished5

Page 15

I2CDisplay11 2 56 7 8Fig. 10: Wiringplan, single chamber housing1 Voltage supply/Signal output5.4 Wiring plan, double chamber housingThefollowing illu

Page 16

132Display1 2 5 6 7 8I2CFig. 12: Electronicscompartment, double chamber housing1 Plug connector for VEGACONNECT (I²C interface)2 Internal connection c

Page 17

I2C11 2Fig. 14: Wiringplan, double chamber housing1 Voltage supply/Signal output5.5 Wiring plan - version IP 66/IP 68, 1 bar+-12Fig. 15: Wireassignmen

Page 18 - 5.1 Preparin

6 Setup with the indicating andadjustment module PLICSCOM6.1 Short descriptionTheindicating and adjustment module is used for measuredvalue display, a

Page 19

Fig. 16: Installationof the indicating and adjustment moduleNote:Ifyou intend to retrofit the instrument with an indicating andadjustment module for co

Page 20

6.3 Adjustment system1.1231Fig. 17: Indicatingand adjustment elements1 LC display2 Indication of the menu item number3 Adjustment keysl [OK] key:- Mov

Page 21

6.4 SetupprocedureAfter VEGAFLEX 66 is connected to voltage supply or aftervoltage recurrence, the instrument carries out a self-check forapprox. 30 s

Page 22 - Ex-ia version

Keepin mind that interfaces can cause faulty measurements.If you want to measure the total height of both liquids reliably,please contact our service

Page 23 - 1 2 5 6 7 8

7 Setupwith PACTware and other adjustment programs7.1 Connecting the PC . . . . . . . . . . . . . . . . . . . . .377.2 Parameter adjustment with PACTw

Page 24

2 Enterthe appropriate distance value in m (correspondingto the percentage value) for the full vessel. Keep in mindthat the max. level must lie below

Page 25 - 6.1 Short description

A linearizationis necessary for all vessels in which the vesselvolume does not increase linearly with the level - e. g. with acylindrical or spherical

Page 26

level measurement. A false echo memory should be createdwith empty vessel so that all potential interfering reflections willbe detected.Probes in coax

Page 27 - - Select

l Languagel Sensitivityl PA scaling unitl PV-Out-Scalel Channell Additional PA valueThe following safety-relevant data are not read out or written:l H

Page 28 - 6.4 Setup

Function ResetvalueSensor address no resetLanguage no resetFactory settingLike basic adjustment, furthermore special parameters arereset to default va

Page 29

6.5 MenuschematicBasic adjustment1▶Basic adjustmentDisplayDiagnosticsServiceInfo1.1Sensor address0001.2Min. adjustment0.00 %=10.000 m(d)8.000 m(d)1.3M

Page 30

Service4Basic adjustmentDisplayDiagnostics▶ServiceInfo4.1Sensor5 mRod4.2ApplicationLiquidStandard(DK ≥ 2)4.3Gating out of false signalsChange now?4.4A

Page 31 - Sensor-TAG

7 Setupwith PACTware and otheradjustment programs7.1 Connecting the PC~=Power supplyVEGACONNECT 3PACTware /TM>P A<231Fig. 18: Connectionof th

Page 32 - Change now?

Allcurrently available VEGA DTMs are provided in the DTMCollection on CD and can be obtained from the responsibleVEGA agency for a token fee. This CD

Page 33 - Copy sensor data?

8 Maintenance and fault rectification8.1 MaintenanceWhenused in the correct way, no special maintenance isrequired in normal operation.8.2 Remove inter

Page 34

1 About this document1.1 FunctionThisoperating instructions manual provides all the informationyou need for mounting, connection and setup as well asi

Page 35 - 6.5 Menu

? Wrongpresentation of the measured value in Simatic S5l Simatic S5 cannotinterpret the number format IEEE ofthe measured valueà Insert converting com

Page 36

? E017l Adjustment span too smallà Carry out a fresh adjustment and increase the distancebetween min. and max. adjustment? E036l no operable sensor so

Page 37 - >P A<

Inboth cases, the serial number of VEGAFLEX 66 is required.The serial numbers are stated on the type label of VEGAFLEX66, on the inner wall of the hou

Page 38

Seealso chapter "Maintenance and fault rectification"/"Exchange cable/rod"VEGAFLEX 66 • Profibus PA 438 Maintenance and fault rectifi

Page 39 - 8.2 Remove interferences

9 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high temp

Page 40

10 Supplement10.1 Technical dataGeneraldataMaterial 316L corresponds to 1.4404 or 1.4435Materials, wetted parts- Process fitting - coax version 316L an

Page 41

Weight- Instrumentweight (depending onprocess fitting)approx. 0.8 … 8 kg (0.176 … 17.64 lbs)- Tube: ø 21.3 mm (0.839 in) approx. 920 g/m (9.9 oz/ft)- R

Page 42 - 8.4 Instrument repair

Deadband - coax version- top 30 mm (1.181 in)- bottom 0 mm2 4 3 1 Fig. 19: Measuringrange of VEGAFLEX 66 - coax version1 Reference plane2 Probe length

Page 43

Deadband - rod version- top 80 mm (3.15 in)- bottom 0 mmDead band - cable version- top 150 mm (5.91 in)- bottom 250 mm (9.843 in) gravity weight + 100

Page 44 - 9.2 Disposal

OutputvariableOutput signal digital output signal, format according toIEEE-754Sensor address 126 (default setting)Current value 10 mA, ±0.5 mAIntegrat

Page 45 - 10.1 Technical data

2 Foryour safety2.1 Authorised personnelAlloperations described in this operating instructions manualmust be carried out only by trained specialist pe

Page 46

-3mm(-1/8")3mm(1/8")10mm(25/64")-10mm(-25/64")0,5 m(1.6 ft)0,15 m(0.5 ft)32 m/60 m(105 ft/197 ft)Fig. 22: Accuracy - Cablevers

Page 47

21-110°C(-166°F)0°C(32°F)-40°C(-40°F)60°C(140°F)80°C(176°F)100°C(212°F)200°C(392°F)100°C(212°F)400°C(752°F)300°C(572°F)Fig. 24: Ambienttemperature - p

Page 48

Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 barCable entry/plug4)- Single chamber housing l 1 x cable gland M20 x 1.5 (cable:ø 5

Page 49

Connection cable- Wire cross-section 0.5 mm² (AWG 20)- Wire resistance < 0.036 Ω/m- Tensile strength < 1200 N (270 lbf)- Standard length 5 m (16

Page 50

Electrical protective measuresProtection, depending on housing version- Plastic housing IP 66/IP 67- Aluminium housing, stainless steelhousing - inves

Page 51 - Ambient temperature

10.2 Profibus PAInstrument master fileThe instrument master file (GSD) contains the characteristic data of the Profibus PAinstrument. These data are, e.g.

Page 52

m(d) % Lin%Min-MaxadjustmentLinearizationPROFIBUS PA-outputPrimaryValueSecondaryValue 2SecondaryValue 1TargetModeFailuremodeAlarmsScalingSource forsca

Page 53

l Long for Profibus master only supporting the "IdentifierFormat" byte, e.g. Siemens S7-300/400Examples of telegram configurationIn the followi

Page 54

Byte nByte n+1Bit7VZExponentBit62Bit52Bit42Bit32Bit22Bit12Bit02Bit72Bit62Bit52Bit42Bit32Bit22Bit12Bit02SignBitSignificant765432 10-1-2-3-4-5-6 -7Byte

Page 55 - 10.2 Profibus P

StatuscodeDescriptionaccording to Pro-fibus standardPossible cause0x8a good (non-cascade) - active ad-visory alarm - high limitedHi-Alarm0x8d good (non

Page 56 - - PA-OUT value of

Duringthe entire duration of use, the user is obliged todetermine the compliance of the required occupational safetymeasures with the current valid ru

Page 57

10.3 DimensionsHousing in protection IP 66/IP 67 and IP 66/IP 68; 0.2 bar~ 69 mm(2 23/32")ø 77 mm(3 1/32")112 mm (4 13/32")M20x1,5/½ NP

Page 58

Housingin protection IP 66/IP 68, 1 bar117mm (4 39/64")120mm (4 23/32")~ 103mm(4 1/16")~ 105mm (4 9/64")ø 77mm(3 1/32")116mm

Page 59

VEGAFLEX 66 - cable, rodversion (-110 … +400 °C/-166 … +752 °F)L 150 mm (5.91")53 mm(2.09")ø 6 mm(0.24")12 mm(0.47")ø 54 mm(2.13&q

Page 60 - 10.3 Dim

VEGAFLEX 66 - coaxversion (-110 … +400 °C/-166 … +752 °F)L271 mm (10 5/8")18 mm (45/64")29 mm (1 9/64")ø 21,1 mm(53/64")SW 50(1 31

Page 61

10.4 Industrial property rightsVEGA product lines are global protected by industrial propertyrights. Further information see http://www.vega.com.Only

Page 62 - G1½ / 1½”NPT

VEGAFLEX 66 • Profibus PA 6510 Supplement32764-EN-080716

Page 63

66 VEGAFLEX 66 • Profibus PA10 Supplement32764-EN-080716

Page 64 - 10.5 Trademark

VEGAFLEX 66 • Profibus PA 6710 Supplement32764-EN-080716

Page 65

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] date:ISO 9

Page 66

l via PACTwarel onthe type label of the electronicsl via the indicating and adjustment moduleYou canview all software histories on our website www.veg

Page 67

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l VEGAFLEX 66 level sensorl Documentation- thisoperating instructions manual- O

Page 68 - ISO 9001

1 2 3Fig. 1: VEGAFLEX 66 - cableversion with plastic housing1 Housing cover with integrated indicating and adjustment module (optional)2 Housing with