Page 1 - VEGABAR 52

Operating InstructionsPressure transmitter with CERTEC® measuring cellVEGABAR 524 … 20 mA/HARTDocument ID: 36717

Page 2 - Contents

103 Product descriptionVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321The delivery must be checked for completeness and possible transit damage immediately

Page 3

113 Product descriptionVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Youcanndadditionalinformationinthesupplementaryinstructionsmanual"Fla

Page 4 - 1 About this document

124 MountingVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303214 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in direct c

Page 5 - 2 For your safety

134 MountingVEGABAR 52 • 4 … 20 mA/HART36717-EN-13032121212112Fig. 4: Position of the lter element1 Filter element2 Blind plugCaution:Duetothel

Page 6 - 2 For your safety

144 MountingVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303214.2 Mounting stepsFormountingVEGABAR52,aweldedsocketisrequired.Youcanndthesecompo

Page 7 - 3 Product description

154 MountingVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Tip:Mount the wall mounting plate so that the cable entry of the socket housing points downward.

Page 8 - 3.2 Principle of operation

165 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303215 Connecting to power supply5.1 Preparing the connectionAlways keep in mind

Page 9 - 3.3 Operation

175 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321housing.Thiswouldinuencethestabilityoftheconnectionandthetightness

Page 10 - 3 Product description

185 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303218. Press down the opening levers of the terminals, you will hear the terminal

Page 11

195 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321321Fig. 8: Components of the external housing1 Screws2 Wall mounting plate3

Page 12 - 4 Mounting

2ContentsVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Contents1 About this document1.1 Function ...

Page 13

205 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321I²CDisplay12 56783412Fig. 9: Electronics and connection compartment, single ch

Page 14 - 4.2 Mounting steps

215 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321132Display12 5678I2CFig. 11: Electronics compartment, double chamber housing1

Page 15

225 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321I2C112Fig. 13: Wiring plan, double chamber housing1 Voltage supply, signal ou

Page 16 - 5 Connecting to power supply

235 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303211212Fig. 15: Connection compartment, Ex-d double chamber housing1 Spring-load

Page 17 - 5.2 Connection procedure

245 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303215.7 Wiring plan, external housing with version IP 68 (25 bar)Fig. 18: VEGABAR

Page 18 - 5 Connecting to power supply

255 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303211234634125Fig. 20: Connection of the sensor in the housing socket1 Brown2 Bl

Page 19

265 Connecting to power supplyVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Then the corresponding current is outputted to the cable (the value correspond

Page 20

276 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303216 Set up with the display and adjustment module P

Page 21 - Connection compartment

286 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Fig. 22: Insert display and adjustment moduleNote:

Page 22 - Wiring plan

296 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321 – Save value• [->] key to select: – Menu chang

Page 23

3ContentsVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303218.1 Maintain ...

Page 24

306 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Information:The steps 1, 3 and 4 are not necessary

Page 25

316 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303214. Conrmwith[OK],thesubmenu"Density un

Page 26

326 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303214. Set the requested mbar value with [+] and [-&g

Page 27 - 6.1 Short description

336 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Inthemenuitems"zero"and"span&

Page 28 - 6.3 Adjustment system

346 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321UnitUnitofmeasurementbar▼Temperature unit°C▼3.

Page 29 - 6.4 Setup steps

356 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Information:Thezeroadjustmentshiftsthevalueo

Page 30

366 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Caution:Note the following if the VEGABAR 52 with

Page 31 - Selection options: °C, °F

376 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Basic adjustmentThe"Reset""Basic

Page 32 - 0000.0 mbar

386 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321itemsintheoperatinginstructionsmanual"D

Page 33

396 Set up with the display and adjustment module PLICSCOMVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321DiagnosticsBasic adjustment 3Display▶DiagnosticsSe

Page 34

41 About this documentVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303211 About this document1.1 FunctionThis operating instructions manual provides all the

Page 35

407 Set up with PACTware and other adjustment programsVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303217 Set up with PACTware and other adjustment programs7

Page 36

417 Set up with PACTware and other adjustment programsVEGABAR 52 • 4 … 20 mA/HART36717-EN-13032112 43OPENTWISTUSBLOCKFig. 26: Connecting the PC via HA

Page 37

427 Set up with PACTware and other adjustment programsVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303217.3 Parameter adjustment with AMS™ and PDMFor VEGA se

Page 38 - 6.5 Menu schematic

438MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303218 Maintenanceandfaultrectication8.1 MaintainIf the instrument is

Page 39

448MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Error code Cause Rectication4 … 20 mA signal not stableLeveluctuati

Page 40

458MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Fperf=√((FT)2 + (FKl)2 + (Fa)2)With:• Ftotal: Total deviation• Fperf

Page 41 - 1 VEGABAR 52

468MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Total deviation analogue output signal absolute:Ftotal = 0.365 % x 8 b

Page 42

478MaintenanceandfaultrecticationVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321data and displays the actual hardware and software version of the sens

Page 43 - 8.2 Rectifyfaults

489 DismountingVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303219 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process

Page 44 - DIN16086)

4910 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-13032110 Supplement10.1 Technical dataGeneral dataParameter, pressure Gauge pressure, absolute pre

Page 45

52 For your safetyVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303212 For your safety2.1 Authorised personnelAll operations described in this operating inst

Page 46 - 8.5 Software update

5010 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321 Ʋ Connection cable with IP 68 1 bar versionPEWeight approx.0.8 … 8 kg (1.764 … 17.64 lbs), d

Page 47 - 8.6 Instrument repair

5110 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Accuracy Ʋ in the range of 0 … +100 °C (+32 … +212 °F)±3 K Ʋ in the range of -50 … 0 °C (-58

Page 48 - 9 Dismounting

5210 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sure-0.2 … +0.2 ba

Page 49 - 10 Supplement

5310 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sure0 … 14.5 psi 5

Page 50

5410 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Applies to the digitalsignaloutput(HART,ProbusPA,FoundationFieldbus)aswellastoan

Page 51

5510 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321 Ʋ Version IP 66/IP 68 (1 bar), connec-tion cable PE-20 … +60 °C (-4 … +140 °F)Process condit

Page 52

5610 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321 Ʋ Single chamber housing – 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind plug M2

Page 53

5710 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Electromechanical data - version IP 68Connection cable between IP 68 instrument and external

Page 54

5810 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321 Ʋ 100Hz…10kHz Uss < 10 mVLoad see diagram100075050025012 181614 20 22 24 26 28 30 32

Page 55

5910 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321For that reason the associated approval documents of these instruments have to be carefully n

Page 56

62 For your safetyVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303212.6 CE conformityThisdevicefulllsthelegalrequirementsoftheapplicableECguide-li

Page 57

6010 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Aluminium housing in protection rating IP 66/IP 68 (1 bar)120 mm (4.72")~ 105 mm (4.13&q

Page 58

6110 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321Stainless steel housing in protection rating IP 66/IP 68 (1 bar)117 mm (4.61")~ 103 mm(4

Page 59 - 10.2 Dimensions

6210 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-13032112368 mm(2.68")68 mm(2.68")92 mm(3.62")42mm(1.65")40mm(1.57")110 mm

Page 60

6310 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321VEGABAR52,threadedtting1GI GM/GNGV/GCGBGSGL/GUG½AG¼AG½AG¼AG½A½"NPTM20x1,5SW 27 mm(1

Page 61

6410 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321VEGABAR52,threadedtting2GFGEGWGGSW46SW55G1 ½ AG2 AG1 ½ A50 mm(1.97")55 mm(2.17"

Page 62

6510 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321VEGABAR52,hygienictting1SW4651 mm(2 1/64")51 mm(2 1/64")51 mm(2 1/64")60

Page 63

6610 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321VEGABAR52,hygienictting2SW4650 mm(1 31/32")51 mm(2 1/64")60 mm(2 23/64")5

Page 64 - 28 mm (1.1 in)

6710 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321VEGABAR52,angeconnection3.46"4.02"5.43" 0.12" 0.12" 0.12"

Page 65

6810 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321VEGABAR52,threadedttingforpaperindustryM 44 x 1,25SW 46 mm (1.81")M 56 x 1,25 M 4

Page 66

6910 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321VEGABAR52,angeconnectionforpaperindustry1FGTRTSEW158 mm(6.22")40 mm(1.58")ø

Page 67

73 Product descriptionVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303213 Product description3.1 CongurationThe scope of delivery encompasses:• VEGABAR 52

Page 68

7010 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321VEGABAR52,angeconnectionforpaperindustry243 mm(1.69")ø 48 mm(1.89")23 mm(0.

Page 69

7110 SupplementVEGABAR 52 • 4 … 20 mA/HART36717-EN-13032110.3 Industrial property rightsVEGA product lines are global protected by industrial propert

Page 70

72INDEXVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321INDEXAAccessories – Display and adjustment module 10 – External display and adjustment unit 10 – Ex

Page 71 - 10.4 Trademark

73NotesVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321

Page 72

74NotesVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321

Page 73

75NotesVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321

Page 74

Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36717-EN-130321All statements concerning scope of delivery, application, practi

Page 75

83 Product descriptionVEGABAR 52 • 4 … 20 mA/HART36717-EN-1303212113105436789111214Fig. 2: Layout of the type label (example)1 Instrument type2 Prod

Page 76 - Printing date:

93 Product descriptionVEGABAR 52 • 4 … 20 mA/HART36717-EN-130321The CERTEC® measuring cell is also equipped with a temperature sensor. The temperature