Operating InstructionsRadar sensor for continuous level measurement of bulk solidsVEGAPULS 674 … 20 mA/HART - two-wireDocument ID: 36531
103 Product descriptionVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210113 Product description3.1 CongurationThe type label contains the most i
113 Product descriptionVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011The scope of delivery encompasses:• Radar sensor• Documentation – this op
123 Product descriptionVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Unless otherwise indicated, the packages must be stored only under the fo
133 Product descriptionVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011You will nd additional information in the supplementary instructions man
144 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded process tting, su
154 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Fig. 5: Flange mounting of the radar sensor4.3 Mounting strapThe mounting strap ena
164 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011 – Angle of inclination in three steps 0°, 90° and 180°• Double chamber housing – An
174 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Mount the instrument at least 200 mm (7.874 in) away from the vessel wall.200 mm(7.8
184 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Fig. 12: Mounting of the radar sensor with inowing medium with lateral llingA corr
194 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011If the medium has good reective properties, VEGAPULS 67 can also be mounted on a l
2Quick startVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Quick startThe quick start enables a quick setup with many applications. You can nd
204 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Fig. 15: Alignment in silosTo detect nearly the complete vessel volume the sensor sh
214 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Fig. 17: Mounting on the vessel ceilingCaution:When mounting on the vessel ceiling m
224 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Information:Keep in mind that for these applications, the sensors are designed for r
234 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Fig. 21: AgitatorsFor level measurements in concrete silos, the sensors are often mo
244 MountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Fig. 23: Installation and orientation in multiple chamber silosFig. 24: Installation
255 Connecting to power supplyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210115 Connecting to power supply5.1 Preparing the connectionAlways k
265 Connecting to power supplyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Warning:Signicant potential dierences exist inside galvanization
275 Connecting to power supplyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210115. Insert the cable into the sensor through the cable entryFig. 2
285 Connecting to power supplyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011512+( )(-)6784...20mA2341Fig. 27: Electronics and connection comp
295 Connecting to power supplyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210114...20mA2312+( )(-)1Fig. 29: Connection compartment, double chamb
3Quick startVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210114. Carry out the adjustment in the menu items "Min. adjustment" and "
305 Connecting to power supplyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210114...20mA212+( )(-)1Fig. 32: Connection compartment, Ex-d double c
315 Connecting to power supplyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011• Indication of the instrument type, hardware and software version
326 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210116 Set up with the indicating and adjustment
336 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210111 2Fig. 36: Insertion of the indicating and
346 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011 – Edit parameter – Save value• [->] key:
356 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011You can nd in the operating instructions ma
366 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011The selection "Standpipe" opens a
376 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011 – Fast lling and emptying – Vessel is very
386 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011 – Extreme damping of output signal due to w
396 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011 – Automatic false signal suppression with p
4ContentsVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Contents1 About this document1.1 Function ...
406 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011With this selection, the operating range of
416 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011210,5 m(19.68")10 m(393.7")100%0%F
426 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210114. Enter the suitable distance value in m f
436 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011The "Echo curve" shows the signal
446 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011The following circumstances cause interferin
456 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011If a false signal suppression has already be
466 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011The following reset functions are available:
476 Set up with the indicating and adjustment moduleVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Menu Menu item Default valueDisplay Language
487 Setup with PACTwareVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210117 Setup with PACTware7.1 Connect the PC312Fig. 39: Connection of the PC
497 Setup with PACTwareVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011such cases, the interface converter can be connected parallel to the 4 …
5ContentsVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210119.1 Maintenance ... 5
507 Setup with PACTwareVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011and echo curves. In addition, there is a tank calculation program as well
518 Set up with other systemsVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210118 Set up with other systems8.1 DD adjustment programsDevice descr
529 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210119 Diagnosis, Asset Management and service9.1 Mainten
539 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011• PC with PACTware/DTM • Control system with EDD • In
549 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011This status message is inactive by default. It can be
559 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011CodeText mes-sageCause RecticationF261Error in the c
569 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011CodeText mes-sageCause RecticationM500Error with the
579 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Error Cause Rectication4 … 20 mA signal not stable –
589 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210119.4 Measurement error with constant levelFault descr
599 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210119.4 Measurement error during emptyingFault descripti
61 About this documentVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210111 About this document1.1 FunctionThis operating instructions manual provi
609 Diagnosis, Asset Management and serviceVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011• In the factory• Or on site by the userIn both cases
6110 DismountingVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-12101110 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dan
6211 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-12101111 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435
6311 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210113421Fig. 52: Data of the input variable1 Reference plane2 Measured variable, ma
6411 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011 Ʋ Relative humidity 45 … 75 % Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5
6511 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Step response time2)≤ 3 sTracking speed of the measuring window max.1 m/minBeam a
6611 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Electromechanical data - version IP 66/IP 68 (1 bar)Options of the cable entry Ʋ
6711 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011 Ʋ Ex-ia instrument 9.6 … 30 V DC Ʋ Ex-d-ia instrument 14 … 36 V DC Ʋ Ex-d-ia ins
6811 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011ApprovalsInstruments with approvals can have dierent technical data depending on
6911 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Aluminium housing in protection rating IP 66/IP 68 (1 bar)120 mm (4.72")~ 10
72 For your safetyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210112 For your safety2.1 Authorised personnelAll operations described in this op
7011 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011Stainless steel housing in protection rating IP 66/IP 68, 1 bar117 mm (4.61"
7111 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011VEGAPULS 67, version with mounting strap125 mm(4.92")2,5 mm(0.10")75 mm
7211 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011VEGAPULS67,versionwithcompressionange126 mm(4.96")10,5 mm(0.41")1
7311 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011VEGAPULS67,versionwithadapterange21138 mm (5.43")31 mm(1.22")20 m
7411 SupplementVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-12101111.3 Industrial property rightsVEGA product lines are global protected by indust
75INDEXVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011INDEXAAccessories – External indicating and adjustment unit 12 – External radio unit 12
76INDEXVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011TType label 10VVessel form 40Vessel height 40Vessel installations 22Voltage supply 2
77NotesVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011
78NotesVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011
79NotesVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-121011
82 For your safetyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210112.5 CE conformityThe device fullls the legal requirements of the applicable
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36531-EN-121011All statements concerning scope of delivery, application, practi
92 For your safetyVEGAPULS 67 • 4 … 20 mA/HART - two-wire36531-EN-1210112.9 Environmental instructionsProtection of the environment is one of our mos
Comments to this Manuals