Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 66 standpipe ver-sion4 … 20 mA/HART - four-wireDocument ID: 365
103 Product descriptionVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011The scope of delivery encompasses:• Radar sensor• Docu
113 Product descriptionVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Up to the time of installation, the packages must be l
123 Product descriptionVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011The protective cover protects the sensor housing again
134 MountingVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded
145 Connecting to power supplyVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210115 Connecting to power supply5.1 Preparing the
155 Connecting to power supplyVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Warning:Signicant potential dierences exist i
165 Connecting to power supplyVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Fig. 3: Connection steps 5 and 66. Insert the
175 Connecting to power supplyVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-12101156784...20mA212+( )(-)1Fig.4:Electronicscom
185 Connecting to power supplyVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011power supply 4...20mA activepassivecommonIS GND
196 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210116 Set up with the indica
2Quick startVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Quick startThe quick start enables a quick setup with many applic
206 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210111 2Fig. 8: Insertion of t
216 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011 – Edit parameter – Save
226 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011You can nd in the operat
236 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011100%0%0,5 m(19.68")5
246 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210114. Enter the suitable di
256 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011The "Echocurve"
266 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011• Vessel installations su
276 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011The menu item "Delet
286 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011When a reset is carried o
296 Set up with the indicating and adjustment moduleVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Menu Menu item Default va
3ContentsVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Contents1 About this document1.1 Function ...
307 Setup with PACTwareVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210117 Setup with PACTware7.1 Connect the PC312Fig. 11: C
317 Setup with PACTwareVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011• Power supply unit or processing systemNote:With powe
327 Setup with PACTwareVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011All device DTMs are available as a free-of-charge stan
338 Set up with other systemsVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210118 Set up with other systems8.1 DD adjustment p
349 Diagnosis, Asset Management and serviceVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210119 Diagnosis, Asset Management and
359 Diagnosis, Asset Management and serviceVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Further echo curves: Up to 10 echo
369 Diagnosis, Asset Management and serviceVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011The following table shows the erro
379 Diagnosis, Asset Management and serviceVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011CodeText mes-sageCause Recticatio
389 Diagnosis, Asset Management and serviceVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011CodeText mes-sageCause Recticatio
399 Diagnosis, Asset Management and serviceVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Error Cause Rectication4 … 20 mA
4ContentsVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210119.6 Software update ...
409 Diagnosis, Asset Management and serviceVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011When loading on site, rst of all
4110 DismountingVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-12101110 Dismounting10.1 Dismounting stepsWarning:Before dismounti
4211 SupplementVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-12101111 Supplement11.1 Technical dataGeneral data316L corresponds
4311 SupplementVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210113421Fig. 15: Data of the input variable1 Reference plane2 Me
4411 SupplementVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011 Ʋ Temperature +18 … +30 °C (+64 … +86 °F) Ʋ Relative humidity
4511 SupplementVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Gas phase Temperature Pressure1 bar (14.5 psig)10 bar (145 psi
4611 SupplementVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011Seal Antenna impedance coneProcess temperature (measured on th
4711 SupplementVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011 Ʋ Inspection window Polyester foilIntegrated clockDate format
4811 SupplementVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011VEGAPULS 66, standpipe versionLø 52 mm(2.05")ø 8 mm(0.32&
4911 SupplementVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-12101111.3 Industrial property rightsVEGA product lines are global
51 About this documentVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210111 About this document1.1 FunctionThis operating instru
50INDEXVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011INDEXAAccessories – External indicating and adjustment unit 11 – Exte
51NotesVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36524-EN-121011All statements concerning scope of delivery, application, practi
62 For your safetyVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210112 For your safety2.1 Authorised personnelAll operations d
72 For your safetyVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210112.5 CE conformityThe device fullls the legal requirements
82 For your safetyVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-121011tection. The environment management system is certied acco
93 Product descriptionVEGAPULS 66 standpipe version • 4 … 20 mA/HART - four-wire36524-EN-1210113 Product description3.1 CongurationThe type label c
Comments to this Manuals