Vega VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - f User Manual

Browse online or download User Manual for Equipment Vega VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - f. VEGA VEGAPULS 62 (≥ 2.0.0 - ≥ 4.0.0) 4 … 20 mA_HART - four-wire User Manual

  • Download
  • Add to my manuals
  • Print

Summary of Contents

Page 1 - VEGAPULS 62

Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 624 … 20 mA/HART - four-wireDocument ID: 36504

Page 2 - Quick start

103 Product descriptionVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210113 Product description3.1 CongurationThe type label contains the most

Page 3

113 Product descriptionVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011The instrument is available in two dierent electronics versions. Each v

Page 4 - Contents

123 Product descriptionVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011The packaging of standard instruments consists of environment-friendly,

Page 5

133 Product descriptionVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011VEGADIS 62 is suitable for measured value indication and adjustment of s

Page 6 - 1 About this document

144 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded process tting, s

Page 7 - 2 For your safety

154 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210113 4 1 2 Fig. 5: Dismounting of the horn antenna1 Marking of the polarisation plane

Page 8 - 2.7 Radio license for Europe

164 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011cient air ow (the air is led through the holes to the feed system. A rinsing of t

Page 9

174 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011is expected. In this case, we recommend repeating a false echo stor-age later with

Page 10 - 3 Product description

184 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Fig.10:MountingoftheradarsensorwithinowingmediumThe socket piece should b

Page 11 - 3.2 Principle of operation

194 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011sensor increases. Additional false reections may be generated which can inuence t

Page 12

2Quick startVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Quick startThe quick start enables a quick setup with many applications. You can n

Page 13

204 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Socket diameter d Socket length h Recommended anten-na diameter40 mm 100 mm 40 mm50

Page 14 - 4 Mounting

214 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Small, inclined sheet metal baes above the installations scatter the radar signals

Page 15 - 4 Antenna

224 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210110%100%123123458679Fig.19:Congurationsurgepipe1 Radar sensor2 Marking of the

Page 16

234 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Constructional requirements on the surge pipe:• Material metal, smoother inner tube

Page 17 - > 200 mm

244 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Instructions for orientation:• Note marking of the polarisation plane on the sensor

Page 18 - (0.39")

254 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011max. 50 mm (1.97")123Fig. 21: Mounting of the instrument with insulate

Page 19

264 MountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-12101123 ... 4 x hmax90°hmaxdB1Fig.23:FlowmeasurementwithKhafagi-Venturiume:d=M

Page 20

275 Connecting to power supplyVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210115 Connecting to power supply5.1 Preparing the connectionAlways

Page 21 - Fig. 18: Agitators

285 Connecting to power supplyVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Warning:Signicant potential dierences exist inside galvanizatio

Page 22

295 Connecting to power supplyVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Fig. 24: Connection steps 5 and 66. Insert the wire ends into th

Page 23

3Quick startVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210114. Carry out the adjustment in the menu items "Min. adjustment" and &quo

Page 24

305 Connecting to power supplyVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-12101156784...20mA212+( )(-)1Fig.25:Electronicscompartment,double

Page 25

315 Connecting to power supplyVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011power supply 4...20mA activepassivecommonIS GND51/L/N2+( )(-)67

Page 26 - 2 Venturiume

326 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210116 Set up with the indicating and adjustmen

Page 27 - 5 Connecting to power supply

336 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210111 2Fig. 29: Insertion of the indicating and

Page 28 - 5.2 Connecting

346 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011 – Edit parameter – Save value• [->] key

Page 29

356 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011You can nd in the operating instructions m

Page 30

366 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011The selection "Standpipe" opens a

Page 31

376 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011 – Fast lling and emptying – Vessel is ver

Page 32

386 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011 – Extreme damping of output signal due to

Page 33 - 6.2 Adjustment system

396 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011 – Automatic false signal suppression with

Page 34 - 6.3 Parameter adjustment

4ContentsVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Contents1 About this document1.1 Function ...

Page 35

406 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Also the vessel form can inuence the measu

Page 36

416 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011100%0%0,5 m(19.68")5 m(196.9")21F

Page 37

426 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210114. Enter the suitable distance value in m

Page 38

436 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011The "Echocurve" shows the signal

Page 39

446 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011• Vessel installations such as struts• Agit

Page 40

456 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011The menu item "Delete" is used to

Page 41

466 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011signal suppression, user-programmed lineari

Page 42

476 Set up with the indicating and adjustment moduleVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Menu Menu item Default valueAdditional adju

Page 43

487 Setup with PACTwareVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210117 Setup with PACTware7.1 Connect the PC312Fig. 32: Connection of the P

Page 44

497 Setup with PACTwareVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011• Power supply unit or processing systemNote:With power supply units wit

Page 45

5ContentsVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210119.4 Rectify faults ...

Page 46

507 Setup with PACTwareVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011All device DTMs are available as a free-of-charge standard version and a

Page 47

518 Set up with other systemsVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210118 Set up with other systems8.1 DD adjustment programsDevice desc

Page 48 - 7 Setup with PACTware

529 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210119 Diagnosis, Asset Management and service9.1 Mainte

Page 49

539 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Further echo curves: Up to 10 echo curves can be sto

Page 50

549 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011The following table shows the error codes in the sta

Page 51 - 8 Set up with other systems

559 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011CodeText mes-sageCause RecticationF264Installation/

Page 52 - 9.1 Maintenance

569 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011CodeText mes-sageCause RecticationM501Error in the

Page 53 - 4 Maintenance - blue

579 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Error Cause Rectication4 … 20 mA signal not stable

Page 54

589 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210119.4 Measurement error with constant levelFault desc

Page 55

599 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Fault description Error pattern Cause Rectication7.

Page 56 - 9.4 Rectify faults

61 About this documentVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210111 About this document1.1 FunctionThis operating instructions manual prov

Page 57

609 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Fault description Error pattern Cause Rectication13

Page 58 - 36504-EN-121011

619 Diagnosis, Asset Management and serviceVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011You can nd the actual sensor software as well as de

Page 59

6210 DismountingVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-12101110 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of da

Page 60 - 9.6 Software update

6311 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-12101111 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.443

Page 61

6411 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Input variableMeasured variable The measured quantity is the distance between pr

Page 62 - 10 Dismounting

6511 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Signal resolution 0.3 µAFailure signal current output (adjustable) mA-value unch

Page 63 - 11 Supplement

6611 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Temperature drift - Digital output ±3 mm/10 K relating to the max. measuring ran

Page 64 - 4 Usefulmeasuringrange

6711 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Tracking speed of the measuring window max.1 m/minBeam angle2) Ʋ Horn antenna ø

Page 65 - 2 Antenna edge

6811 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011 Ʋ Antenna impedance cone PEEK -1 … 100 bar (-100 … 10000 kPa/-14.5 … 1450 psig)

Page 66

6911 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011Plug options Ʋ Signal circuit M12 x 1, according to ISO 4400, Harting HAN, 7/8&q

Page 67

72 For your safetyVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210112 For your safety2.1 Authorised personnelAll operations described in this o

Page 68

7011 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011For that reason the associated approval documents of these instruments must be c

Page 69

7111 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011VEGAPULS 62, horn antenna in threaded versionmm inch 38 mm (1.50")22 mm (0.

Page 70

7211 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011VEGAPULS62,hornantennainangeversionxy2160 mm(2.36")mminch8.50"1

Page 71

7311 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011VEGAPULS62,hornantennainangeversion450°Cyxinch8.50"11.30"ø 1.

Page 72

7411 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011VEGAPULS 62, horn antenna and swivelling holdermm inch 20 mm(0.79")20 mm(0.

Page 73

7511 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011VEGAPULS 62, parabolic antenna and swivelling holder130 mm (5.12")ø 243 mm

Page 74 - 1 Standard

7611 SupplementVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-12101111.3 Industrial property rightsVEGA product lines are global protected by indus

Page 75

77INDEXVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011INDEXAAccessories – External indicating and adjustment unit 12, 13 – External radio uni

Page 76 - 11.4 Trademark

78INDEXVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011SSensor orientation 20Service hotline 60Shielding 27Socket 18Status messages 53Stor

Page 77

79NotesVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011

Page 78

82 For your safetyVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-1210112.5 CE conformityThe device fullls the legal requirements of the applicable

Page 79

Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36504-EN-121011All statements concerning scope of delivery, application, practi

Page 80 - Printing date:

92 For your safetyVEGAPULS 62 • 4 … 20 mA/HART - four-wire36504-EN-121011tection. The environment management system is certied according to DIN EN IS