Page 1 - Operating Instructions

Operating InstructionsVEGALOG 571CPU and carrieron ononPConVEGALOGVEGALOG12345678910571 CPUVEGALOGVEGALOG571 EAVEGALOGVEGALOG571 EPVEGALOGVEGALOG571 A

Page 2 - Contents

4 Mounting4.1 General instructionsThe module cards of VEGALOG 571 can only be mounted intothe 19" carrier BGT LOG 571. It is provided with a spec

Page 3

l With increased ambient temperatures4.3 Mount female multipoint connectorsThe carrier BGT LOG 571 is supplied completely assembled.To mount the indiv

Page 4 - 1 Sequence

Equip the female multipoint connector with the two coded pinsaccording to the "Coding chart" and "Position of the codedpins". The

Page 5 - - Susceptibility EN 50082-1

1Fig. 2: Detail coded pin mounting1 Coded pinVEGALOG 571 - CPU and carrier 13Mounting31947-EN-060606

Page 6

5 Connecting to power supply5.1 General connection instructionsAlways observe the following safety instructions:l Connect only in the complete absence

Page 7 - 3 Product description

Connect the cable screen on both ends to ground potential. Inthe sensor, the screen must be connected directly to theinternal ground terminal. The gro

Page 8 - 3.4 Storage and transport

5.3 Wiring plan312Fig. 3: Connection with NF filter1 Supply cables2 NF filter3 Signal cables21L (+)N (-)2612202422101618302832dbz142684Fig. 4: Terminal

Page 9 - Relative humidity 20 … 85 %

Coupling of the carriersIf the number of the available modules of a carrier (BGT) is notsufficient, the VEGALOG 571 can be also completed with asecond B

Page 10 - - 10 TE for VEGASTAB 593

MSMS54321Fig. 5: Coupling of two carriers1 Hook switch2 Slide switch3 BGT 1 (modules 1 … 16)4 Bus cable5 BGT 2 (modules 17 … 32)18 VEGALOG 571 - CPU a

Page 11 - 4.4 Coding

6 Set up6.1 Indicating and adjustment elements123onPCVEGALOGVEGALOG571 CPU!Fig. 6: Indicating and adjustment elements VEGALOG 571 CPU1 RS232 interface

Page 12 - 31947-EN-060606

Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...

Page 13

l Input cardsl Output cardsl Communication cards for standard bus systemsl Power supply cards for supply of the individual modulecardsThe processor ca

Page 14 - 5 Connecting to power supply

EP cardThe EP card (Eingang Profibus PA, i.e. input PROFIBUS PA)is used as input card for Profibus PA sensors of VEGA or othermanufacturers. Up to max.

Page 15

VEGACOM 558The communication card VEGACOM 558 is an interfaceconverter for Ethernet connection via TCP/IP. Hence theparameter adjustment of VEGALOG as

Page 16 - 5.3 Wiring plan

PACTware™ offers a clear adjustment surface with menustructure, window technology and graphic support as well asan online help. For older VEGALOG syste

Page 17 - - Slide switch - position S

6.5 Creating a projectStarting point for the adjustment of all types of field devices isthe partial or complete mapping of the instrument network in aP

Page 18

from the instrument catalogue to the project window with adouble click or Drag and Drop. If the project window or theinstrument catalogue are not visi

Page 19 - 6 Set up

3 Then the DTMs for the individual VEGALOG module cardsmust be added to the project tree. These are in thisexample: VEGALOG CPU, VEGACOM 558, VEGALOG5

Page 20

Offline modeThe project can be prepared, created and stored in offlinemode without instruments being connected. Later these datacan be transferred in onli

Page 21

l Connection 0/4 … 20 mA instrumentl Arithmetikl Temperature measurementl UniversalDepending on the selected application, a suitable sensor orthe meas

Page 22 - 6.3 Setup requirements

Fig. 11: DTM view, VEGAPULS 61 PAInformation:Detailed expalantions to the parameter adjustmetn and projectcreation are available in the onling help of

Page 23 - 6.4 Start PACTware™

8 Dismounting8.1 Dismounting procedure ...328.2 Disposal ...329 Supplement9.1 Technical data...

Page 24 - 6.5 Creating a project

7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, the module cardVEGALOG 571 CPU is completely maintenance

Page 25 - 6.6 Example projects

7.3 Instrument repairIf a repair is necessary, please proceed as follows:You can download a return form (23 KB) from our homepagewww.vega.com under: &

Page 26 - 6.7 Parameter adjustment

8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high

Page 27

9 Supplement9.1 Technical dataGeneral data carrier BGTSeries 19" carrier for mounting in switching cabinet orhousingDimensions W = 482.6 mm (19 i

Page 28

RS232 interfaceQuantity 1x on front plateData transmission 9600 baud, 8 data bits, 1 stop bit, no parityPlug connection 9-pole D-SUB plugDisplaysLED d

Page 29

9.2 Dimensions185mm (7 9/32")3mm (1/8")132,5mm (57/32")10,5mm (13/32")465mm (18 5/16")19" = 482,6mm84 TE = 426,72mm (16

Page 30 - 7.2 Fault rectification

VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] 9001All st ate

Page 31 - 7.3 Instrument repair

1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th

Page 32 - 8 Dismounting

2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist

Page 33 - 9 Supplement

2.6 Environmental instructionsProtection of the environment is one of our most importantduties. That is why we have introduced an environmentmanagemen

Page 34

3 Product description3.1 ConfigurationThe scope of delivery encompasses:l 19" module card VEGALOG 571 CPUl 19" carrier with integrated bus bo

Page 35 - 9.2 Dimensions

components (FB), input components (EB) and output compo-nents (AB). The input components receive the measuringsignals, the output components make them

Page 36 - ISO 9001

l Relative humidity 20 … 85 %VEGALOG 571 - CPU and carrier 9Product description31947-EN-060606