4 Mounting4.1 General instructionsThe module cards of VEGALOG 571 can only be mounted intothe 19" carrier BGT LOG 571. It is provided with a spec
l With increased ambient temperatures4.3 Mount female multipoint connectorsThe carrier BGT LOG 571 is supplied completely assembled.To mount the indiv
Equip the female multipoint connector with the two coded pinsaccording to the "Coding chart" and "Position of the codedpins". The
1Fig. 2: Detail coded pin mounting1 Coded pinVEGALOG 571 - CPU and carrier 13Mounting31947-EN-060606
5 Connecting to power supply5.1 General connection instructionsAlways observe the following safety instructions:l Connect only in the complete absence
Connect the cable screen on both ends to ground potential. Inthe sensor, the screen must be connected directly to theinternal ground terminal. The gro
5.3 Wiring plan312Fig. 3: Connection with NF filter1 Supply cables2 NF filter3 Signal cables21L (+)N (-)2612202422101618302832dbz142684Fig. 4: Terminal
Coupling of the carriersIf the number of the available modules of a carrier (BGT) is notsufficient, the VEGALOG 571 can be also completed with asecond B
MSMS54321Fig. 5: Coupling of two carriers1 Hook switch2 Slide switch3 BGT 1 (modules 1 … 16)4 Bus cable5 BGT 2 (modules 17 … 32)18 VEGALOG 571 - CPU a
6 Set up6.1 Indicating and adjustment elements123onPCVEGALOGVEGALOG571 CPU!Fig. 6: Indicating and adjustment elements VEGALOG 571 CPU1 RS232 interface
Contents1 About this document1.1 Function ...41.2 Target group ...41.3 Symbolism used ...
l Input cardsl Output cardsl Communication cards for standard bus systemsl Power supply cards for supply of the individual modulecardsThe processor ca
EP cardThe EP card (Eingang Profibus PA, i.e. input PROFIBUS PA)is used as input card for Profibus PA sensors of VEGA or othermanufacturers. Up to max.
VEGACOM 558The communication card VEGACOM 558 is an interfaceconverter for Ethernet connection via TCP/IP. Hence theparameter adjustment of VEGALOG as
PACTware™ offers a clear adjustment surface with menustructure, window technology and graphic support as well asan online help. For older VEGALOG syste
6.5 Creating a projectStarting point for the adjustment of all types of field devices isthe partial or complete mapping of the instrument network in aP
from the instrument catalogue to the project window with adouble click or Drag and Drop. If the project window or theinstrument catalogue are not visi
3 Then the DTMs for the individual VEGALOG module cardsmust be added to the project tree. These are in thisexample: VEGALOG CPU, VEGACOM 558, VEGALOG5
Offline modeThe project can be prepared, created and stored in offlinemode without instruments being connected. Later these datacan be transferred in onli
l Connection 0/4 … 20 mA instrumentl Arithmetikl Temperature measurementl UniversalDepending on the selected application, a suitable sensor orthe meas
Fig. 11: DTM view, VEGAPULS 61 PAInformation:Detailed expalantions to the parameter adjustmetn and projectcreation are available in the onling help of
8 Dismounting8.1 Dismounting procedure ...328.2 Disposal ...329 Supplement9.1 Technical data...
7 Maintenance and fault rectification7.1 MaintenanceWhen used as directed in normal operation, the module cardVEGALOG 571 CPU is completely maintenance
7.3 Instrument repairIf a repair is necessary, please proceed as follows:You can download a return form (23 KB) from our homepagewww.vega.com under: &
8 Dismounting8.1 Dismounting procedureWarning:Before dismounting, be aware of dangerous process con-ditions such as e.g. pressure in the vessel, high
9 Supplement9.1 Technical dataGeneral data carrier BGTSeries 19" carrier for mounting in switching cabinet orhousingDimensions W = 482.6 mm (19 i
RS232 interfaceQuantity 1x on front plateData transmission 9600 baud, 8 data bits, 1 stop bit, no parityPlug connection 9-pole D-SUB plugDisplaysLED d
9.2 Dimensions185mm (7 9/32")3mm (1/8")132,5mm (57/32")10,5mm (13/32")465mm (18 5/16")19" = 482,6mm84 TE = 426,72mm (16
VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermanyPhone +49 7836 50-0Fax +49 7836 50-201E-mail: [email protected] 9001All st ate
1 About this document1.1 FunctionThis operating instructions manual has all the information youneed for quick setup and safe operation. Please read th
2 For your safety2.1 Authorised personnelAll operations described in this operating instructions manualmust be carried out only by trained specialist
2.6 Environmental instructionsProtection of the environment is one of our most importantduties. That is why we have introduced an environmentmanagemen
3 Product description3.1 ConfigurationThe scope of delivery encompasses:l 19" module card VEGALOG 571 CPUl 19" carrier with integrated bus bo
components (FB), input components (EB) and output compo-nents (AB). The input components receive the measuringsignals, the output components make them
l Relative humidity 20 … 85 %VEGALOG 571 - CPU and carrier 9Product description31947-EN-060606