10 VEGAFLEX 54P (Profibus PA)Product description1.6 Bus configurationThe type of sensor you use depends on yourprocess requirements and mounting condi
VEGAFLEX 54P (Profibus PA) 11Product descriptionEx environmentIn Ex environment, intrinsically safe (EEx ia)PA sensors are used with Ex segment cou-pl
12 VEGAFLEX 54P (Profibus PA)Product description32…82Adresse 121 22 52Adresse 21...52Adresse 10Profibus PASegmentcouplerDCS/PLC1 … 32 sensors(Ex: 1 …
VEGAFLEX 54P (Profibus PA) 13Product description3~MM253 54 84Adresse 53...84Adresse 85Adresse 86Adresse 87Profibus DPProfibus PASegmentcoupler1 … 32
14 VEGAFLEX 54P (Profibus PA)Product description1.7 ApprovalsVEGAFLEX sensors are approved for StEx Zone 10.Observe the attached approval documents wh
VEGAFLEX 54P (Profibus PA) 15MoistureMountingLateral loadPressureIn case of gauge or low pressure in the ves-sel, the mounting boss must be sealed on
16 VEGAFLEX 54P (Profibus PA)MountingMeasuring rangeThe electrode (rod / cable) cannot be usedover its entire length.Keep especially in mind that the
VEGAFLEX 54P (Profibus PA) 17Electrical connection3 Electrical connection3.1 Connection – Connection cable– ScreeningSafety information – Qualifiedper
18 VEGAFLEX 54P (Profibus PA)Electrical connectionFig. 3.1 bFig. 3.1 aGrounding at one end (next to the sensor)Grounding at both ends (on the signal c
VEGAFLEX 54P (Profibus PA) 19Connection cable and cable lengthConnection cables must correspond to theProfibus specification and the FISCO model.The s
2 VEGAFLEX 54P (Profibus PA)ContentsSafety information ... 2Note Ex area ...
20 VEGAFLEX 54P (Profibus PA)Electrical connectionIn the so-called Fieldbus Intrinsically SafeConcept (FISCO), the general conditions foran Ex safe bu
VEGAFLEX 54P (Profibus PA) 21Electrical connection3.2 Sensor addressIn a Profibus system composed of ProfibusDP and Profibus PA subsystem, each partic
22 VEGAFLEX 54P (Profibus PA)Electrical connectionExample 2You want to set address 27.16 + 8 + 2 + 1 = 27You must set the DIP switches5 = 164 = 82 = 2
VEGAFLEX 54P (Profibus PA) 23Electrical connectionESCESC+-OKOK–++1 2- 5 6 7 8DisplayBusAddr.ON8 7654321Voltage supply andProfibus signalTo the indicat
24 VEGAFLEX 54P (Profibus PA)Electrical connection3.4 Connection of the external indicating instrument-+ESCOKTank 1m (d)12.34532156784+-+1 2- 5 6 7 8D
VEGAFLEX 54P (Profibus PA) 25Setup4 Setup4.1 Adjustment mediaAll VEGA Profibus sensors operate in profile3 and can be adjusted with:- the adjustment p
26 VEGAFLEX 54P (Profibus PA)Adjustment with PACTwareTMThe adjustment with PACTwareTM corre-sponds to VVO adjustment, in this case, VVOruns as a subpr
VEGAFLEX 54P (Profibus PA) 27-+ESCOKTank 1m (d)12.345Setup▼▼15342▼▼Adjustment elementsThe adjustment module MINICOM is menu-driven. The clear text ind
28 VEGAFLEX 54P (Profibus PA)SetupAdjust-mentPara-meteradjust-mentSensorm(d) 4.700w.o.mediumAd-just-mentinm(d)0.0 %atm (d)XX.XXX(min. adjustment)OKOKO
VEGAFLEX 54P (Profibus PA) 29Setup2. ConditioningUnder the menu item "Conditioning", youchoose the distance at 0 % and at 100 %filling. Then
VEGAFLEX 54P (Profibus PA) 3Contents4 Setup4.1 Adjustment media ... 254.2 Adjustment with t
30 VEGAFLEX 54P (Profibus PA)CreatenewEmptyvesselprofileCreatenewNow ! OK ?Meas.dist.m (d) X.XXLearn-ing!UpdateUpdateNow !OK ?Learn-ing!DeleteDele-ti
VEGAFLEX 54P (Profibus PA) 31Simu-lationSimu-lationNow!OK ?Simu-lation%XXX.Xact.dist. m X,XXBolt print figures are sensor ormeasured value informati
32 VEGAFLEX 54P (Profibus PA)SetupVEGA signal condit. instrument RxVEGAMET 513, 514, 515, 602 50 … 100 OhmVEGAMET 614 no additionalVEGADIS 371 resista
VEGAFLEX 54P (Profibus PA) 335 Diagnosis5.1 SimulationTo simulate a certain filling, you can call upthe function "Simulation“ on the adjustmentmo
34 VEGAFLEX 54P (Profibus PA)Function diagram and PA parametersFilterAdjustment min-max Life-adjustment Dry-adjustment possibleCal point hi, Cal point
VEGAFLEX 54P (Profibus PA) 35Function diagram and PA parametersminmaxMin/Max memorySimulation distance value (DS_50)[sensor unit (m,ft)](manuf. spec.
36 VEGAFLEX 54P (Profibus PA)Function diagram and PA parametersPDMVVOFDTMINICOMPDMVVOFDTMINICOMScaled (PA-Out)SimulationSimulated value:- primary valu
VEGAFLEX 54P (Profibus PA) 37Function diagram and PA parametersOut Scale - primary value (%,m,ft ...)- secondary value 1 (%,m,ft ...)- secondary value
38 VEGAFLEX 54P (Profibus PA)5.4 PA parametersThe following parameter listing and functiondiagram is used for setup with the automationsystem if there
VEGAFLEX 54P (Profibus PA) 39PA parametersIndex P arameter Object Read Write Type Size Store UnitOptionalma nda t ory0 Directory object header DM Yes
4 VEGAFLEX 54P (Profibus PA)Product description1 Product description1.1 FunctionHigh frequency microwave impulses areguided along a steel rope or a ro
40 VEGAFLEX 54P (Profibus PA)PA parametersIndex P arameter Object Read Write Type Size Store UnitOptionalma nda t ory66 Block object PB Yes No DS-32 2
VEGAFLEX 54P (Profibus PA) 41PA parametersIndex P arameter Object Read Write T ype Size Store UnitOptionalm anda t ory121 St rev TB_Level Yes No Unsig
42 VEGAFLEX 54P (Profibus PA)PA parametersIndex P arameter Object Read Write Type Size Store UnitOptionalma nda t ory157 Tab X Y value TB_Level Yes Ye
VEGAFLEX 54P (Profibus PA) 43Technical data6 Technical data6.1 Technical dataPower supplySupply voltage 9 … 32 V DC(output voltage UO of the segment (
44 VEGAFLEX 54P (Profibus PA)Technical dataCharacteristicsMin. span between full and empty adjustment- digital output signal 10 mmAdjustment time 1)&g
VEGAFLEX 54P (Profibus PA) 45Technical dataConnection cablesTwo-wire sensor- power supply and signal via one two-wire cable.The line resistance depend
46 VEGAFLEX 54P (Profibus PA)18521537020511625M20x1,520110˚10191182322M20x1,5165SW411NPTø 47022L80G1A55ø 8 ø 8ø 20SW601 1/2NPTø 47026L80G1 1/2A55ø 20ø
VEGAFLEX 54P (Profibus PA) 47Technical dataø 824L 534ø 200ø 138ø 8SW411NPT22LG1A55ø 8SW601 1/2NPT33, 5LG1 1/2A5521518537020511625½" NPTAluminium
ISO 9001All statements concerning scope of delivery, application, practicaluse and operating conditions of the sensors and processing sys-tems corresp
VEGAFLEX 54P (Profibus PA) 5-+ESCOKTank 1m (d)12.345Pluggable adjustment module MINICOMProduct descriptionAdjustment with PCThe setup and adjustment o
6 VEGAFLEX 54P (Profibus PA)Product description1.4 Profibus output signalAs a process automation bus, Profibus PAenables power supply over the bus. Up
VEGAFLEX 54P (Profibus PA) 7Product description233VVOSPSAdr. 10Adr. 1Master-Class 1Adr. 58Adr. 60Adr. 57Adr. 59Adr. 24Adr. 23Adr. 22Adr. 21Adr. 25 … 5
8 VEGAFLEX 54P (Profibus PA)Product description244 ... 20 mA-+ESCOKTank 1m (d)12.345-+ESCOKTank 1m (d)12.345Adjustment with detachable adjustment modu