Operating InstructionsPressure transmitter with ceramic measuring cellVEGABAR 824 … 20 mADocument ID: 45027
103 Product descriptionVEGABAR 82 • 4 … 20 mA45027-EN-13101023415Fig. 4: Front-ish mounting of the CERTEC® measuring cell1 Seal for the process tti
113 Product descriptionVEGABAR 82 • 4 … 20 mA45027-EN-1310103.3 Packaging, transport and storageYour instrument was protected by packaging during tra
123 Product descriptionVEGABAR 82 • 4 … 20 mA45027-EN-131010Youcanndfurtherinformationintheoperatinginstructions"VE-GADIS 62" (Doc
134 MountingVEGABAR 82 • 4 … 20 mA45027-EN-1310104 Mounting4.1 General instructions to use the instrumentMake sure that all parts of the instrument e
144 MountingVEGABAR 82 • 4 … 20 mA45027-EN-13101012Fig. 7: Temperature ranges1 Process temperature2 Ambient temperature4.2 Ventilation and pressure
154 MountingVEGABAR 82 • 4 … 20 mA45027-EN-1310101 2 34 4 4Fig. 8: Position of the lter element - non-Ex, Ex-ia version1 Plastic, stainless steel pr
164 MountingVEGABAR 82 • 4 … 20 mA45027-EN-131010• Ventilation electronics housing• Atmospheric pressure compensation (with relative pressure meas-uri
174 MountingVEGABAR 82 • 4 … 20 mA45027-EN-131010123Fig. 12: Measurement setup for process pressure measurement of gases in pipelines1 VEGABAR 822 B
184 MountingVEGABAR 82 • 4 … 20 mA45027-EN-131010A protective accumulation of water is formed through condensation in the pipe bends. Even in applicat
194 MountingVEGABAR 82 • 4 … 20 mA45027-EN-1310104.5 External housing12345Fig. 16: Setup process assembly, external housing1 Process assembly2 Conn
2ContentsVEGABAR 82 • 4 … 20 mA45027-EN-131010Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGABAR 82 • 4 … 20 mA45027-EN-1310105 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the f
215 Connecting to power supplyVEGABAR 82 • 4 … 20 mA45027-EN-131010This can lead to unacceptably high shield currents if the cable shield is grounded
225 Connecting to power supplyVEGABAR 82 • 4 … 20 mA45027-EN-131010Information:Solidcoresaswellasexiblecoreswithwireendsleevesareinsert-e
235 Connecting to power supplyVEGABAR 82 • 4 … 20 mA45027-EN-1310105.5 External housing with version IP 68 (25 bar)123Fig. 21: VEGABAR 82 in IP 68 ve
245 Connecting to power supplyVEGABAR 82 • 4 … 20 mA45027-EN-1310101234634125Fig. 23: Connection of the sensor in the housing base1 Brown2 Blue3 Ye
255 Connecting to power supplyVEGABAR 82 • 4 … 20 mA45027-EN-131010Then the actual measured value is outputted to the signal cable. The value takes al
266 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-1310106 Set up with the display and adjustment module6.1 Insert disp
276 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-1310106.2 Adjustment system12Fig. 26: Display and adjustment elements
286 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010Carry out the following steps in the below sequence.Youcannd
296 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010Enter the percentage value and the corresponding value for the m
3ContentsVEGABAR 82 • 4 … 20 mA45027-EN-1310108.4 Rectify faults ...
306 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010plete menus "Display", "Diagnosis", "Ad
316 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010Unit of measurement:If the level should be adjusted in a height
326 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010VEGABAR 82 always measures pressure independently of the pro-ces
336 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-1310103. Set the requested mbar value with [+] and store with [OK].4.
346 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-1310102. Edit the percentage value with [OK] and set the cursor to th
356 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010required.Correspondinglinearizationcurvesarepreprogrammedf
366 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010Caution:With active PIN, adjustment via PACTware/DTM as well as
376 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010In this menu item, the device status is displayed.The respective
386 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010Inthismenuitem,thePINisdisplayedoreditedaswellasmod
396 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010Menu item Parameter Default valuePosition correc-tion0.00 barAdj
41 About this documentVEGABAR 82 • 4 … 20 mA45027-EN-1310101 About this document1.1 FunctionThis operating instructions manual provides all the infor
406 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010Menu item Parameter Default valueScaling Scalingsize Volume in
416 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-131010In menu item"Current output, size" you determine which
426 Set up with the display and adjustment moduleVEGABAR 82 • 4 … 20 mA45027-EN-1310106.5 Saving the parameter adjustment dataWe recommended noting t
437 Setup with PACTwareVEGABAR 82 • 4 … 20 mA45027-EN-1310107 Setup with PACTware7.1 Connect the PC312Fig. 28: Connection of the PC directly to the
447 Setup with PACTwareVEGABAR 82 • 4 … 20 mA45027-EN-131010Fig. 29: Example of a DTM viewAll device DTMs are available as a free-of-charge standard v
458 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-1310108 Diagnosis, asset management and service8.1 MaintenanceIf the instru
468 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-131010the following tables there are more detailed error messages available
478 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-131010CodeText mes-sageCause RecticationF013no measured value avail-able –
488 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-131010CodeText mes-sageCause RecticationF265Measurement function dis-turbed
498 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-131010CodeText mes-sageCause RecticationM501Error in the non-active lineari
52 For your safetyVEGABAR 82 • 4 … 20 mA45027-EN-1310102 For your safety2.1 Authorised personnelAll operations described in this operating instructi
508 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-131010Error Cause Rectication4 … 20 mA signal missing – Electrical con-nect
518 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-131010• FT:Thermalchangeofzerosignalandoutputspan• FKl: Deviation• F
528 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-13101012534Fig. 31: VEGABAR 82 in IP 68 version, 25 bar and lateral cable ou
538 Diagnosis, asset management and serviceVEGABAR 82 • 4 … 20 mA45027-EN-131010Youcannddetailedinformationontheelectronicsexchangeinthebo
549 DismountingVEGABAR 82 • 4 … 20 mA45027-EN-1310109 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process condi
5510 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-13101010 Supplement10.1 Technical dataMaterials and weightsMaterials, wetted partsProcesstting 316L,
5610 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Input variableAdjustmentAdjustment range of the min./max. adjustment relating to the nominal measu
5710 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Nominal range Overload capacity, max. pressureOverload capacity, min. pres-sure0 … 0.1 bar/0 … 10
5810 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Nominal range Overload capacity, max. pressureOverload capacity, min. pres-sure0 … 5 psi 435 psi 0
5910 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-13101090 %100 %10 %ttTAttS21Fig. 32: Behaviour in case of sudden change of the process variable. tT: dea
62 For your safetyVEGABAR 82 • 4 … 20 mA45027-EN-131010radiated emissions must be taken into account, as is usual with a class A instrument according
6010 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Applies to the digitalsignaloutput(HART,ProbusPA,FoundationFieldbus)aswellastotheana
6110 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Thermal change, current output < 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C (-40 … +
6210 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Nominal measuring range in bar/kPaNominal meas-uring range in psigMeasuring cell ø 28 mm Measuring
6310 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Product temperature depending on the ambient temperatureAmbient temperature Product temperature+50
6410 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Electromechanical data - version IP 68 (25 bar)Connection cable between IP 68 instrument and exter
6510 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Accuracy ±1 °C (1.8 °F)Voltage supplyOperating voltage UB Ʋ Non-Ex instrument 9.6 … 35 V DC Ʋ Ex-d
6610 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010Protection class IIApprovalsInstrumentswithapprovalscanhavedierenttechnicaldatadepending
6710 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010External housing with IP 68 version1234582 mm(3.23")80 mm(3.15")108 mm(4.25")41,6 m
6810 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010VEGABAR82,threadedttingnotfront-ushDD DLDUC2DQDIG½ G¼ G½ G¼ SW 27 mm(1.06")G½23 mm(0.9
6910 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010VEGABAR82,threadedttingfront-ushC1C322 mm(0.87")44 mm(1.73")ø 24 mm (0.95")ø
73 Product descriptionVEGABAR 82 • 4 … 20 mA45027-EN-1310103 Product description3.1 CongurationThenameplatecontainsthemostimportantdatafori
7010 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010VEGABAR82,hygienicttingARAAESFR EZ/E1 E350 mm(1.97")51 mm(2.01")51 mm(2.01")ø 7
7110 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010VEGABAR82,angeconnection3.46"4.02"5.43" 0.12" 0.12" 0.12"4xø 0
7210 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-131010VEGABAR82,extensionttingF1 F2AF/AGF9ø 32...60 mm(1.26...2.36")ø 48...90 mm(1.89...3.54&qu
7310 SupplementVEGABAR 82 • 4 … 20 mA45027-EN-13101010.3 Industrial property rightsVEGA product lines are global protected by industrial property rig
74INDEXVEGABAR 82 • 4 … 20 mA45027-EN-131010INDEXAAdjust Date/Time 38Adjustment – Level 33, 34 – Menu 29 – Process pressure 32, 33 – System 27 –
75NotesVEGABAR 82 • 4 … 20 mA45027-EN-131010
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany45027-EN-131010All statements concerning scope of delivery, application, practi
83 Product descriptionVEGABAR 82 • 4 … 20 mA45027-EN-131010This operating instructions manual applies to the following instrument versions:• Hardware
93 Product descriptionVEGABAR 82 • 4 … 20 mA45027-EN-131010Sensor element is the CERTEC® measuring cell with robust ceramic diaphragm.Theprocesspre
Comments to this Manuals