Operating InstructionsCapacitive rod electrode for level detectionVEGACAP 62- two-wireDocument ID: 30007
103 Product descriptionVEGACAP 62 • - two-wire30007-EN-130916Transport must be carried out in due consideration of the notes on the transport packagin
114 MountingVEGACAP 62 • - two-wire30007-EN-1309164 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in direct conta
124 MountingVEGACAP 62 • - two-wire30007-EN-130916Theprocessttingmustbesealedifthereisgaugeorlowpressureinthe vessel. Before use, check
134 MountingVEGACAP 62 • - two-wire30007-EN-130916The probe should protrude into the vessel to avoid buildup. For that reason,avoidusingmountingbo
144 MountingVEGACAP 62 • - two-wire30007-EN-130916dd6123Fig. 7: Filling in the centre, emptying laterally1 VEGACAP 622 Discharge opening3 Filling o
155 Connecting to power supplyVEGACAP 62 • - two-wire30007-EN-1309165 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the
165 Connecting to power supplyVEGACAP 62 • - two-wire30007-EN-130916Fig. 8: Connection steps 5 and 66. Insert the wire ends into the open terminals a
175 Connecting to power supplyVEGACAP 62 • - two-wire30007-EN-1309164123Fig. 10: Electronics and connection compartment1 DIL switch for measuring ran
185 Connecting to power supplyVEGACAP 62 • - two-wire30007-EN-1309165.4 Wiring plan - version IP 66/IP 68, 1 bar12Fig. 12: Wire assignment, connectio
196 SetupVEGACAP 62 • - two-wire30007-EN-1309166 Setup6.1 General informationTheguresinbracketsrefertothefollowingillustrations.Ontheelect
2ContentsVEGACAP 62 • - two-wire30007-EN-130916Contents1 About this document1.1 Function ...
206 SetupVEGACAP 62 • - two-wire30007-EN-130916change the sensitivity of the probe to the electrical properties of the product and the conditions in t
217MaintenanceandfaultrecticationVEGACAP 62 • - two-wire30007-EN-1309167 Maintenanceandfaultrectication7.1 MaintenanceIf the instrument is u
227MaintenanceandfaultrecticationVEGACAP 62 • - two-wire30007-EN-130916Error Cause Rectication – The instrument signals covered without cover-in
237MaintenanceandfaultrecticationVEGACAP 62 • - two-wire30007-EN-1309161 2 3Fig. 15: Check the resistance in the probe1 Shielding2 Probe3 Ground
247MaintenanceandfaultrecticationVEGACAP 62 • - two-wire30007-EN-13091621Fig. 16: Loosening the holding screws1 Electronics module2 Screws (2 p
257MaintenanceandfaultrecticationVEGACAP 62 • - two-wire30007-EN-13091621Fig. 17: Compensation key1 Measuring range selection switch (compensati
267MaintenanceandfaultrecticationVEGACAP 62 • - two-wire30007-EN-130916• Clean the instrument and pack it damage-proof• Attach the completed form
278 DismountingVEGACAP 62 • - two-wire30007-EN-1309168 Dismounting8.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process cond
289 SupplementVEGACAP 62 • - two-wire30007-EN-1309169 Supplement9.1 Technical dataGeneral dataMaterial 316L corresponds to 1.4404 or 1.4435Materials,
299 SupplementVEGACAP 62 • - two-wire30007-EN-130916Switching delay Ʋ When immersed 0.7 s Ʋ When laid bare 0.7 s Ʋ In case of failure 1 sAmbient condi
3ContentsVEGACAP 62 • - two-wire30007-EN-130916Supplementary documentationInformation:Supplementary documents appropriate to the ordered version come
309 SupplementVEGACAP 62 • - two-wire30007-EN-130916Spring-loaded terminals for wire cross-section up to 1.5 mm² (AWG 16)Electromechanical data - vers
319 SupplementVEGACAP 62 • - two-wire30007-EN-130916Functional safety according to IEC 61508-4 Ʋ Single channel architecture (1oo1D) up to SIL2 Ʋ doub
329 SupplementVEGACAP 62 • - two-wire30007-EN-130916Housing in protection IP 66/IP 68 (1 bar)117 mm(4.61")~ 103 mm(4.06")ø 77 mm(3.03")
339 SupplementVEGACAP 62 • - two-wire30007-EN-130916ø 16 mm (0.63")100 mm(3.94")12 mm (0.47")LG 3/4 A, G 1 A, G 11/2 A56 mm(2.21")
349 SupplementVEGACAP 62 • - two-wire30007-EN-130916108 mm (4.25")ø 40 mm (1.58")Fig. 23: Temperature adapter
359 SupplementVEGACAP 62 • - two-wire30007-EN-130916ø 16 mm (0.63")L7 mm (0.28")Fig. 24: VEGACAP 62, screening tube, for example against str
369 SupplementVEGACAP 62 • - two-wire30007-EN-130916ø 16 mm (0.63")LFig. 25: VEGACAP 62, concentric tube, for example with small dielectric const
379 SupplementVEGACAP 62 • - two-wire30007-EN-1309169.3 Industrial property rightsVEGA product lines are global protected by industrial property righ
38NotesVEGACAP 62 • - two-wire30007-EN-130916
39NotesVEGACAP 62 • - two-wire30007-EN-130916
41 About this documentVEGACAP 62 • - two-wire30007-EN-1309161 About this document1.1 FunctionThis operating instructions manual provides all the info
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany30007-EN-130916All statements concerning scope of delivery, application, practi
52 For your safetyVEGACAP 62 • - two-wire30007-EN-1309162 For your safety2.1 Authorised personnelAll operations described in this operating instruct
62 For your safetyVEGACAP 62 • - two-wire30007-EN-1309162.5 Safety label on the instrumentThe safety approval markings and safety tips on the device
73 Product descriptionVEGACAP 62 • - two-wire30007-EN-1309163 Product description3.1 CongurationThe scope of delivery encompasses:• VEGACAP 62 poin
83 Product descriptionVEGACAP 62 • - two-wire30007-EN-130916211110131214159364578Fig. 2: Layout of the type label (example)1 Instrument type2 Produc
93 Product descriptionVEGACAP 62 • - two-wire30007-EN-130916123Fig. 3: Functional principle - Plate capacitor1 Distance between the electrode surface