2 Connection plics® sensor
With
this version, connection of VEGACONNECT 3 is carried out via
the I²C interface integrated in the sensor. This is the easiest and
fastest way to make a connection. The housing cover of the sensor
cannot be closed when VEGACONNECT 3 is connected.
Note:
Use this conne
ction variant only if the connection is to be short-term, in
a dry environment and not in an Ex-area.
5
6
2
3
1
4
Fig. 2: Connection
plics
®
series via I²C interface
1 Analogue telephone connection (not applicable in case of GSM radio
modem)
2 Standard analogue modem or GSM radio modem
3 Special cable, art. no.: MODEM.KX
4 VEGACONNECT 3
5 I²C adapter (in the scope of delivery of VEGACONNECT 3)
6 Sensor from the plics® serie
With this version, connection of VEGACONNECT 3 is carried out via
the HART protocol and the supply cable of the sensor. Hence, the
connection can be made at any point between power supply/
processing system and sensor.
This version can also be used for connection in Ex
-areas. The modem
and VEGACONNECT 3 themselves must not be located in Ex-area.
If the resistance of the connected processing system is less than
230 Ω, the digital adjustment signal is extremely damped or short-
circuited. Digital communication with the PC is then no longer possible.
With low impedance processing systems, a resistance of approx.
230 Ω must be integrated into the 4 20 mA connection cable. The
connection can be either carried out in parallel to the sensor or via the
resistor.
Connection to the sen-
sor (I²C)
Connection to cable
(HART)
Remote parameter adjustment and remote maintenance Conguration and
connection 3
2 Connection plics® sensor
23051-EN-090302