Operating InstructionsUltrasonic sensor for continuous level measurementVEGASON 62Foundation FieldbusDocument ID: 28791
104MountingVEGASON 62 • Foundation Fieldbus28791-EN-1304174 Mounting4.1 General instructionsMakesurethatallpartsoftheinstrumentcomingindir
114MountingVEGASON 62 • Foundation Fieldbus28791-EN-13041712Fig. 3: Minimum distance to the max. level1 Dead band2 Reference planeInformation:If th
124MountingVEGASON 62 • Foundation Fieldbus28791-EN-130417When mounting the sensor, keep a distance of at least 200 mm (7.874in)tothevesselwall.
134MountingVEGASON 62 • Foundation Fieldbus28791-EN-130417ca. 10 mmFig. 7: Recommended socket mountingIfthereectivepropertiesofthemediumareg
144MountingVEGASON 62 • Foundation Fieldbus28791-EN-130417~200~400x40045°Fig.10:BeamdeectorThe ultrasonic sensor should be installed at a locatio
154MountingVEGASON 62 • Foundation Fieldbus28791-EN-130417Fig. 12: AgitatorsDonotmounttheinstrumentsinorabovethellingstream.Makesuretha
164MountingVEGASON 62 • Foundation Fieldbus28791-EN-130417Byusingastandpipe(surgeorbypasstube),theinuenceofvesselinstallations, foam gen
175 Connecting to power supplyVEGASON 62 • Foundation Fieldbus28791-EN-1304175 Connecting to power supply5.1 Preparing the connectionAlways keep in
185 Connecting to power supplyVEGASON 62 • Foundation Fieldbus28791-EN-130417low frequency potential equalisation currents are thus suppressed, butth
195 Connecting to power supplyVEGASON 62 • Foundation Fieldbus28791-EN-13041710. Connect the screen to the internal ground terminal, connect the oute
2ContentsVEGASON 62 • Foundation Fieldbus28791-EN-130417Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGASON 62 • Foundation Fieldbus28791-EN-130417I²C34512DisplayTyp:12 5678 BusSim.Fig. 17: Electronics and connection com
215 Connecting to power supplyVEGASON 62 • Foundation Fieldbus28791-EN-1304171 2 345Fig. 19: Double chamber housing1 Housing cover, connection compar
225 Connecting to power supplyVEGASON 62 • Foundation Fieldbus28791-EN-130417123Display12I2CFig. 21: Connection compartment, double chamber housing1
235 Connecting to power supplyVEGASON 62 • Foundation Fieldbus28791-EN-1304175.6 Switch-on phaseAfter VEGASON 62 is connected to voltage supply or af
246SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-1304176 Set up with the display and adjustment mod
256SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-130417Fig. 24: Insert display and adjustment module
266SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-130417 – Save value• [->] key to select: – Menu
276SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-1304172. Selectthemenuitem"Basic adjustme
286SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-130417Apartfromthemedium,thevesselshapecana
296SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-130417False signal suppressionChange now?Proceed as
3ContentsVEGASON 62 • Foundation Fieldbus28791-EN-1304178.4 Software update ...
306SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-130417• PINCopy sensor dataCopy sensor data?Basic a
316SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-130417Basic adjustment▶Basic adjustment 1DisplayDia
326SetupwiththedisplayandadjustmentmodulePLICSCOMVEGASON 62 • Foundation Fieldbus28791-EN-130417ServiceBasic adjustment 4DisplayDiagnostics▶S
337 Set up with PACTware and other adjustment programsVEGASON 62 • Foundation Fieldbus28791-EN-1304177 Set up with PACTware and other adjustment prog
347 Set up with PACTware and other adjustment programsVEGASON 62 • Foundation Fieldbus28791-EN-1304177.2 Parameter adjustment with PACTwareFurther se
358MaintenanceandfaultrecticationVEGASON 62 • Foundation Fieldbus28791-EN-1304178 Maintenanceandfaultrectication8.1 MaintenanceIf the instru
368MaintenanceandfaultrecticationVEGASON 62 • Foundation Fieldbus28791-EN-130417Error Cause RecticationInstrument does not appear during connect
378MaintenanceandfaultrecticationVEGASON 62 • Foundation Fieldbus28791-EN-130417Information:Whenloadingonsite,rstofalltheorderdatamust
388MaintenanceandfaultrecticationVEGASON 62 • Foundation Fieldbus28791-EN-1304178.5 Instrument repairIf a repair is necessary, please proceed as
399 DismountingVEGASON 62 • Foundation Fieldbus28791-EN-1304179 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous pro
41 About this documentVEGASON 62 • Foundation Fieldbus28791-EN-1304171 About this document1.1 FunctionThis operating instructions manual provides all
4010 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-13041710 Supplement10.1 Technical dataGeneral dataMaterials,wettedparts Ʋ Processtting,t
4110 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-130417 Ʋ Relativehumidity 45…75% Ʋ Air pressure 860…1060mbar/86…106kPa(12.5…15.4
4210 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-130417Processtemperature(transducertem-perature)-40…+80°C(-40…+176°F)Vibration resis
4310 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-130417 Ʋ Colour - standard PE Black Ʋ Colour-standardPUR Blue Ʋ Colour - Ex-version BlueDis
4410 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-13041710.2 Foundation FieldbusBlock diagram, measured value processingThefollowingillustrat
4510 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-130417Secondary_value_1CalibrationLowest PointCalibrationHighest PointSensor_valuecal_level_lo
4610 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-130417• CURVE_STATUS – Resultoftableplausibilitycheck• SUB_DEVICE_NUMBER• SENSOR_ELEMENT_T
4710 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-130417• solids_vessel_type – Setuptosuittheprocessconditions.IfSpecial-Parameteradjus
4810 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-13041710.3 DimensionsHousing in protection IP 66/IP 68 (0.2 bar)~ 69 mm(2.72")ø 77 mm(3.0
4910 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-130417Housing in protection IP 66/IP 68 (1 bar)117 mm (4.61")~ 103 mm(4.06")ø 77 mm(
52 For your safetyVEGASON 62 • Foundation Fieldbus28791-EN-1304172 For your safety2.1 Authorised personnelAll operations described in this operating
5010 SupplementVEGASON 62 • Foundation Fieldbus28791-EN-13041710.4 Industrial property rightsVEGA product lines are global protected by industrial pr
51NotesVEGASON 62 • Foundation Fieldbus28791-EN-130417
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany28791-EN-130417All statements concerning scope of delivery, application, practi
62 For your safetyVEGASON 62 • Foundation Fieldbus28791-EN-130417successfultesting.YoucanndtheCEconformitydeclarationinthedownloadareaof
73 Product descriptionVEGASON 62 • Foundation Fieldbus28791-EN-1304173 Product description3.1 CongurationThe scope of delivery encompasses:• VEGASO
83 Product descriptionVEGASON 62 • Foundation Fieldbus28791-EN-130417product surface and received back by the transducer as echoes. The running time o
93 Product descriptionVEGASON 62 • Foundation Fieldbus28791-EN-130417Transport must be carried out under consideration of the notes on the transport p